UPS INSTALLATION PLAN AND UNPACKING
Eaton
Power Xpert 9395P-600 (380V-600V) UPS Installation and Operation Manual
S
P-164000710 Rev 1
www.eaton.com/powerquality
3-36
Table 3‐24. 480V Power Cable Conduit Recommendations
UPS Model
Voltage
Terminal
Number of Wires
in Conduit
Minimum Conduit
Trade Size
Number of
Conduits
Eaton 9395P-600/600
Eaton 9395P-600/550
480 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
2.5
4
AC Input to Bypass and Output
(A, B, C, Ground)
4
2.5
3
DC
(Common
Battery)
Battery
(Positive, Negative, Ground)
7
4
2
Eaton 9395P-600/500
Eaton 9395P-600/450
Eaton 9395P-600/400
480 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
2.5
3
AC Input to Bypass and Output
(A, B, C, Ground)
4
2.5
3
DC
(Common
Battery)
Battery
(Positive, Negative, Ground)
7
4
2
Eaton 9395P-600/300
Eaton 9395P-600/275
Eaton 9395P-600/250
Eaton 9395P-600/225
Eaton 9395P-600/200
See Note
480 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
2.5
4
AC Input to Bypass and Output
(A, B, C, Ground)
4
2.5
3
DC
(Common
Battery)
Battery
(Positive, Negative, Ground)
7
4
2
All models
DC
(Separate
Battery - per
UPM)
Battery
(Positive, Negative, Ground)
7
4
1
NOTE
Bypass conduit data is not applicable to IOM configurations.