Product Specifications
10.1
Model Numbers
The UPS is housed in one or two free‐standing cabinets with safety shields behind
the door and front panels. The UPS is available in 50 or 60 Hz with various output
power ratings.
Models
Power Rating
Frequency
Eaton 9395P-600/600 (one, two, or three UPM)
600 kVA, 600 kW
50/60 Hz
Eaton 9395P-600/550 (one, two, or three UPM)
600 kVA, 550 kW
50/60 Hz
Eaton 9395P-600/500 (one, two, or three UPM)
600 kVA, 500 kW
50/60 Hz
Eaton 9395P-600/450 (one, two, or three UPM)
600 kVA, 450 kW
50/60 Hz
Eaton 9395P-600/400 (one, two, or three UPM)
600 kVA, 400 kW
50/60 Hz
Eaton 9395P-600/300 (one, two, or three UPM)
600 kVA, 300 kW
50/60 Hz
Eaton 9395P-600/275 (one, two, or three UPM)
600 kVA, 275 kW
50/60 Hz
Eaton 9395P-600/250 (one, two, or three UPM)
600 kVA, 250 kW
50/60 Hz
Eaton 9395P-600/225 (one, two, or three UPM)
600 kVA, 225 kW
50/60 Hz
Eaton 9395P-275/200 (one, two, or three UPM)
600 kVA, 200 kW
50/60 Hz
10.2
Specifications
The following sections detail the input, output, environmental, and battery
specifications for the UPS.
10.2.1
UPS Input
Operating Input Voltage
600 Vac, 480 Vac, 415 Vac, 400 Vac, 380 Vac
Operating Input Frequency Range
50/60 Hz
Operating Input Current
See Table 3‐6 or Table 3‐7 for 600V One/Two/Three UPM models.
See Table 3‐8 or Table 3‐9 for 575V One/Two/Three UPM models.
See Table 3‐10 or Table 3‐11 for 480V One/Two/Three UPM models.
See Table 3‐12 or Table 3‐13 for 415V One/Two/Three UPM models.
See Table 3‐14 or Table 3‐15 for 400V One/Two/Three UPM models.
See Table 3‐16 or Table 3‐17 for 380V One/Two/Three UPM models.
Reduced for Generator
Adjustable
Input Current Harmonic Content
3% THD at full load
Power Factor
Minimum 0.99 at full load
Line Surges
6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801‐4
Battery Voltage
480 Vdc
Figure