PRODUCT SPECIFICATIONS
Eaton
Power Xpert 9395P-600 (380V-600V) UPS Installation and Operation Manual
S
P-164000710 Rev 1
www.eaton.com/powerquality
10-2
Battery Charging Capacity
Configurable per UPM at nominal line voltage:
Up to 120A with less than 85% load
Up to 80A with 100% load
Battery Shunt Trip
48 Vdc
10.2.2
UPS Output
UPS Output Capacity
100% rated current
Output Voltage Regulation
"
1.5% (10% to 100% load)
Output Voltage Adjustment
(N/–3%)
600 Vac nominal, adjustable from 582 Vac to 618 Vac
575 Vac nominal, adjustable from 558 Vac to 592 Vac
480 Vac nominal, adjustable from 466 Vac to 494 Vac
400 Vac nominal, adjustable from 388 Vac to 412 Vac
380 Vac nominal, adjustable from 369 Vac to 391 Vac
Output Voltage Harmonic Content
1% maximum THD (linear load)
5% maximum THD (nonlinear load)
Output Current
See Table 3‐6 or Table 3‐7 for 600V One/Two/Three UPM models.
See Table 3‐8 or Table 3‐9 for 575V One/Two/Three UPM models.
See Table 3‐10 or Table 3‐11 for 480V One/Two/Three UPM models.
See Table 3‐12 or Table 3‐13 for 415V One/Two/Three UPM models.
See Table 3‐14 or Table 3‐15 for 400V One/Two/Three UPM models.
See Table 3‐16 or Table 3‐17 for 380V One/Two/Three UPM models.
Output Voltage Balance
2.5% for 100% maximum load imbalance (linear load)
Output Voltage Phase
Displacement
"
4° for 100% maximum load imbalance (linear load)
Output Transients
Meets Class 1 IEC 62040-3 (10% to 100% load)
Frequency Regulation
"
0.1 Hz free running
Synchronous to Bypass
+10% to -10%
Frequency Slew Rate
.7 Hz per second maximum
Load Compatibility
0.9 pF Leading
0.7 pF Lagging
Overload Capability (kW)
110% for 10 minutes
125% for 120 seconds
150% for 15 seconds
NOTE
The 125% and 150% overloads are based on the non-derated hardware capability
of the UPS.
10.2.3
UPS Environmental
Operating Temperature
All ratings except 600 kW, 300 kW: 0 to 40°C (32 to 104°F) at
elevation up to 1000m without derating. For 600 kW, 300 kW:
0 to 35°C at elevation up to 1000m without derating.The
recommended operating temperature is 25°C (77°F).
Operating Altitude
Maximum 1000m (3300 ft) at 40°C without derating
Storage Temperature
–25 to +60°C, excluding batteries (prolonged storage above
40°C causes rapid battery self‐discharge)