User’s and Installation Guide
74
10 Product specifications
10.1 Model numbers
The UPS systems are housed in free-standing cabinets with safety shields behind the doors. The
UPS systems are available in 50/60 Hz with various output power ratings.
Models
Power Rating
Frequency
Powerware 9395E-200
200 kVA
50/60 Hz
The following sections detail the input, output, environmental, and battery specifications for the
UPS.
10.2 Single module specifications
10.2.1 UPS system input
Operating Input Voltage
400 Vac for operation from 320 Vac to 480 Vac
Operating Input Frequency Range
±5 Hz
Operating Input Current
See Table 3-4 on page 3-6.
Reduced for Generator Adjustable
Input Current Harmonic Content
3% THD at full load
Power Factor
Minimum 0.98
Line Surges
6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801-4
Battery Voltage
480 Vdc
10.2.2 UPS system output
UPS Output Capacity
100% rated current
Output Voltage Regulation
±1% (10% to 100% load)
Output Voltage Adjustment (N/–3%)
380 Vac nominal, adjustable from 368.6 Vac to 391.4 Vac
400 Vac nominal, adjustable from 388 Vac to 412 Vac
415 Vac nominal, adjustable from 402.5 Vac to 427.5 Vac
Output Voltage Harmonic Content
1.5% max THD (linear load)
5% max THD (nonlinear load)
Output Current
See Table 3-4 on page 3-6.
Output Voltage Balance
3% for 100% maximum load imbalance (linear load)
Output Voltage Phase Displacement
3° for 100% maximum load imbalance (linear load)
Output Transients
±5% for 100% load step or removal
Frequency Regulation
±0.1 Hz free running
Synchronous to Bypass
Bypass within voltage limits of +5%, –8% of output setting;
bypass within ±3 Hz
Frequency Slew Rate
1 Hz per second maximum
Max battery charging current
60 A
UPS 200 kVA
Summary of Contents for Powerware 9395E
Page 1: ...Powerware 9395E UPS 200 kVA User s and Installation Guide...
Page 6: ...UPS 200 kVA User s and Installation Guide 6 Figure 1 1 Powerware 9395E 200 cabinet...
Page 23: ...UPS 200 kVA User s and Installation Guide 23 Figure 3 1 Removing left side shipping bracket...
Page 31: ...User s and Installation Guide 31 Figure 3 7 Interface terminal locations UPS 200 kVA...
Page 76: ......