3 UPS system installation
3.1 Preliminary installation information
WARNING
Installation should be performed only by qualified personnel.
Refer to the following while installing the UPS system:
Chapter 2 for cabinet dimensions, equipment weight, wiring and terminal data, and
•
installation notes.
Do not tilt the cabinet more than ±10° during installation.
•
The landing plates are to be removed to add holes as required. Plate material is 16 gauge
•
steel (1.5 mm/0.06” thick).
If perforated floor tiles are required for ventilation, place them in front of the UPS.
•
3.2 Unloading the UPS cabinet from the pallet and mechan-
ical installation
The UPS cabinet is bolted to a wooden pallet supported by wood skids. To remove the pallet
and mechanically install the UPS, perform the following procedure:
NOTE
When a line-up-and-match UPS system is ordered together with battery cabinets, the first
battery cabinet is supplied with two cosmetic covers. The UPS cabinet, additional battery
cabinets, and other ancillary cabinets are supplied without cosmetic covers.
NOTE
When a UPS system is ordered together with battery cabinets for standalone installation,
the first battery cabinet is supplied with two cosmetic covers. Additional battery cabinets
are supplied without cosmetic covers. Cosmetic covers must be ordered for the UPS
cabinet and/or other ancillary cabinets.
WARNING
The UPS cabinet is heavy. See Table 2-1 on page 11 for weight of cabinets. If unloading
instructions are not closely followed, the cabinet may cause serious injury.
Summary of Contents for Powerware 9395E
Page 1: ...Powerware 9395E UPS 200 kVA User s and Installation Guide...
Page 6: ...UPS 200 kVA User s and Installation Guide 6 Figure 1 1 Powerware 9395E 200 cabinet...
Page 23: ...UPS 200 kVA User s and Installation Guide 23 Figure 3 1 Removing left side shipping bracket...
Page 31: ...User s and Installation Guide 31 Figure 3 7 Interface terminal locations UPS 200 kVA...
Page 76: ......