background image

UPS MAINTENANCE

EATON

Powerware

®

9125 Two-in-One UPS (2500/3000 VA) User’s Guide

S

164201374 Rev D

www.powerware.com

56

UPS Battery Connector

EBM Battery
Connectors

Joining Brackets

EBM Cables

Figure 45. EBM Connections (120V UPS Model Shown)

Testing New Batteries

Press and hold the

button for three seconds to initiate a self-test.

After the five-second test is complete, the

indicator should turn off

(it may take a few seconds to turn off). If the

indicator stays on,

check the battery connections. Call your service representative if the
problem persists.

Summary of Contents for Powerware 9125

Page 1: ...Powerware 9125 Two in One UPS 2500 3000 VA User s Guide ...

Page 2: ...ments of the Canadian Interference Causing Equipment Regulations ICES 003 Cet appareil numérique de la classe A respecte toutes les exigences du Reglement sur le matériel brouilleur du Canada EN 50091 2 Some configurations are classified under EN 50091 2 as Class A UPS for Unrestricted Sales Distribution For these configurations the following applies WARNING This is a Class A UPS Product In a dome...

Page 3: ...quipment designed for use within certain voltage limits 93 68 EEC Amending Directive 73 23 EEC 89 336 EEC Council Directive relating to electromagnetic compatibility 92 31 EEC Amending Directive 89 336 EEC relating to EMC The EC Declaration of Conformity is available upon request for products with a CE mark For copies of the EC Declaration of Conformity contact Eaton Power Quality Oy Koskelontie 1...

Page 4: ...EPTACLE For 230V models only this receptacle provides network interface connections Do not plug telephone or telecommunications equipment into this receptacle This symbol indicates that you should not discard the UPS or the UPS batteries in the trash This product contains sealed lead acid batteries and must be disposed of properly For more information contact your local recycling reuse or hazardou...

Page 5: ...ded Battery Module Installation 22 Plug Receptacle UPS Installation 25 Hardwired UPS Installation 27 Remote Emergency Power off Installation 31 UPS Rear Panels 33 4 Operation 35 Turning the UPS On 35 Starting the UPS on Battery 35 Turning the UPS Off 36 Initiating the Self Test 36 Operating Modes 37 Normal Mode 38 Battery Mode 39 Bypass Mode 40 Standby Mode 40 5 Configuration 41 6 Additional UPS F...

Page 6: ...teries 52 How to Replace UPS Internal Batteries 53 How to Replace Extended Battery Modules 55 Testing New Batteries 56 Recycling the Used Battery or UPS 57 8 Specifications 59 9 Troubleshooting 63 Audible Alarms and UPS Conditions 63 Silencing an Audible Alarm 63 Service and Support 66 10 Warranty 67 Two Year Limited Warranty US and Canada 67 Ten Year Pro Rated Limited Warranty US and Canada 69 Lo...

Page 7: ...25 you can safely eliminate the effects of power disturbances and guard the integrity of your equipment Figure 1 shows the Powerware 9125 UPS with an optional Extended Battery Module EBM Figure 1 The Powerware 9125 UPS with Optional EBM Providing outstanding performance and reliability the Powerware 9125 s unique benefits include the following S Online UPS design with pure sine wave output The UPS...

Page 8: ...ional X Slott cards with enhanced communication capabilities for increased power protection and control S Network transient protector that guards your network communications equipment from surges Low voltage models can also protect modems fax machines or other telecommunications equipment S Advanced power management with the Software Suite CD for graceful shutdowns and power monitoring S Sequentia...

Page 9: ... as in most European applications the voltage to the output receptacles is 0V With line to line input wiring the voltage to the output receptacles is 110 120V measured from line to ground or line to neutral depending on the UPS wiring S Do not remove or unplug the input cord when the UPS is turned on This removes the safety ground from the UPS and the equipment connected to the UPS S To reduce the...

Page 10: ...le kan repareres af brugeren ADVARSEL S Denne UPS indeholder egen energiforsyning batterier Udgangsnetstikkene kan lede strøm selv når UPS en ikke er tilsat en AC energikilde S Netledningen må ikke fjernes og stikket må ikke trækkes ud mens UPS en er tændt Dette fjerner sikkerhedsjorden fra UPS en og fra det udstyr der er sat til S Installér denne UPS i et temperatur og fugtighedskontrolleret inde...

Page 11: ...n batterijen De uitgangsaansluitingen kunnen onder spanning staan wanneer de UPS niet op een wisselstroom voeding is aangesloten S Verwijder de ingangsnoer niet of haal de stekker van de ingangsnoer er niet uit terwijl de UPS aan staat Hierdoor zou de UPS en uw aangesloten apparatuur geen aardebeveiliging meer hebben S Teneinde de kans op brand of elektrische schok te verminderen dient deze UPS in...

Page 12: ...i olla jännite kun UPS ei ole liitettynä verkkojännitteeseen S Älä poista tai irrota sisääntulojohtoa kun UPS on kytkettynä Tämä poistaa turvamaadoituksen UPS laitteesta ja siihen liitetystä laitteistosta S Vähentääksesi tulipalon ja sähköiskun vaaraa asenna tämä UPS sisätiloihin joissa lämpötila ja kosteus on säädettävissä ja joissa ei ole virtaa johtavia epäpuhtauksia Ympäristön lämpötila ei saa...

Page 13: ...iaux conducteurs où la température et l humidité ambiantes sont contrôlées La température ambiante ne doit pas dépasser 40 C Ne pas utiliser à proximité d eau ou dans une atmosphère excessivement humide 95 maximum S Afin d être conforme aux normes et règlements internationaux de câblage le courant de fuite à la terre de la totalité du matériel branché sur la sortie de l onduleur ne doit pas dépass...

Page 14: ...ngssteckverbindern 0 Volt Bei einer Verkabelung mit Außenleitern beträgt die Spannung an den Ausgangssteckverbindern 110 120 Volt gemessen von Leitung zu Masse oder Leitung zu Masseleiter abhängig von der UPS USV Verkabelung S Das Eingangskabel nicht entfernen oder abziehen während die USV eingeschaltet ist weil hierdurch die Sicherheitserdung von der USV und den daran angeschlossenen Geräten entf...

Page 15: ...iene una fonte di energia autonoma le batterie Le prese di uscita possono condurre tensione energizzata quando il gruppo statico di continuità non è collegato con una fonte di alimentazione a corrente alternata S Non rimuovere nè scollegare il cavo di ingresso quando il gruppo statico di continuità è acceso poichè in tal modo si disattiverebbe il collegamento a terra di sicurezza del gruppo static...

Page 16: ...ikke sikkerhetsjordingen fjernes fra UPS en og det utstyret som er forbundet med den S For å redusere fare for brann eller elektriske støt bør denne UPS en installeres i et innendørs miljø med kontrollert temperatur og luftfuktighet som er fritt for ledende forurensende stoffer Romtemperaturen må ikke overskride 40 C Den må ikke brukes i nærheten av vann eller ved meget høy luftfuktighet 95 maks S...

Page 17: ...e a UPS em ambiente interno com temperatura e umidade controladas e livres de contaminadores condutíveis A temperatura ambiente não deve exceder 40 C Não opere próximo a água ou em umidade excessiva máx 95 S Para estar de acordo com os padrões internacionais e os regulamentos de fiação o equipamento total conectado à saída desta UPS não deve ter uma corrente de fuga à terra maior que 1 5 miliampèr...

Page 18: ... оборудования подключенного к ИПБ S Для снижения опасности пожара или поражения электрическим током устанавливайте ИБП в закрытом помещении с контролируемыми температурой и влажностью в котором отсутствуют проводящие загрязняющие вещества Температура окружающего воздуха не должна превышать 40 С Не эксплуатируйте устройство около воды или в местах с повышенной влажностью макс 95 S Для обеспечения с...

Page 19: ...to con temperatura y humedad controladas libre de contaminantes conductores La temperatura ambiente no debe exceder los 40 C No trabaje cerca del agua o con humedad excesiva 95 máximo S Para cumplir con los estándares internacionales y las normas de instalación la totalidad de los equipos conectados a la salida de este SIE no debe tener una intensidad de pérdida a tierra superior a los 1 5 miliamp...

Page 20: ...ektriska stötar genom att installera denna UPS enhet inomhus där temperatur och luftfuktighet är kontrollerade och där inga ledande föroreningar förekommer Omgivande temperatur får ej överstiga 40 C Använd inte utrustningen nära vatten eller vid hög luftfuktighet max 95 S För att överensstämma med internationell standard och installationsföreskrifter får inte den totala utrustning som anslutits ti...

Page 21: ... during shipment keep the shipping cartons and packing materials for the carrier or place of purchase and file a claim for shipping damage If you discover damage after acceptance file a claim for concealed damage To file a claim for shipping damage or concealed damage 1 File with the carrier within 15 days of receipt of the equipment 2 Send a copy of the damage claim within 15 days to your service...

Page 22: ... Removing the UPS Front Cover 3 Connect the internal battery connector see Figure 3 Figure 3 Connecting the Internal Battery Connector 4 Replace the UPS front cover see Figure 4 Figure 4 Replacing the UPS Front Cover 5 Continue to the following section UPS Setup UPS Setup The Powerware 9125 UPS is designed for flexible configurations and can be installed in a rack or as a standalone cabinet If you...

Page 23: ...ot already installed in your rack contact your local distributor to order rail kits To install the UPS and optional EBMs in a rack 1 Place the UPS on a flat stable surface with the front of the UPS facing toward you 2 Attach the supplied mounting handles to the mounting brackets and secure with the supplied screws see Figure 5 3 Align the mounting brackets with the screw holes on the side of the U...

Page 24: ...ug Receptacle UPS Installation on page 25 or Hardwired UPS Installation on page 27 to complete the installation Tower Setup The setup varies depending on the number of cabinets you are installing 1 For one cabinet the pedestals must be installed Continue to Step 2 For two cabinets the pedestals and the joining brackets must be installed Skip to Step 6 For three or more cabinets the joining bracket...

Page 25: ...the cabinet upright with the air vents at the top see Figure 8 5 Continue to Plug Receptacle UPS Installation on page 25 or Hardwired UPS Installation on page 27 to complete the installation Air Vents Figure 8 Pedestals with One Cabinet 6 Place the UPS cabinet horizontally so that the left end of the cabinet is accessible see Figure 9 Figure 9 Installing UPS Pedestals for Two Cabinets ...

Page 26: ... end of the cabinet is accessible see Figure 10 Figure 10 Installing EBM Pedestals 8 Align the pedestals with the screw holes on the end of the EBM cabinet Secure the pedestals with the screws provided in the accessory kit 9 Carefully position the cabinets upright with the air vents at the top see Figure 11 or Figure 12 Air Vents Figure 11 Pedestals with Two Cabinets ...

Page 27: ...gn each joining bracket with the adjacent corner screw holes and secure with the supplied screws see Figure 13 Joining Bracket EBM UPS Joining Bracket Figure 13 Installing the Joining Brackets Top View with Pedestals 11 If installing additional EBMs repeat Step 10 for each cabinet 12 If installing optional EBMs continue to the following section Extended Battery Module Installation Otherwise contin...

Page 28: ...e UPS battery connector quickly and firmly To install the optional EBMs 1 If installing an EBM with an E EH UPS model skip to Step 4 otherwise continue to Step 2 2 Plug the EBM cable s into the battery connector s as shown in Figure 14 Up to four EBMs may be connected to the UPS 3 Continue to Plug Receptacle UPS Installation on page 25 or Hardwired UPS Installation on page 27 UPS Battery Connector...

Page 29: ...d screws for future use If the UPS is stored or used without an EBM the battery connector cover must be installed as a safety precaution Battery Connector Cover Screws Figure 15 Battery Connector Cover E EH UPS Models Only 5 Remove the cover from the EBM cable as shown in Figure 16 NOTE Keep the EBM cable cover and screws for future use If the EBM is stored or removed from the UPS the EBM cable co...

Page 30: ...ttery Connector with Cover UPS EBM EBM UPS Battery Connector Figure 17 EBM Installation for E EH UPS Models Only 8 If additional EBMs are to be installed remove the EBM battery connector cover Remove the cover from the EBM cable of the second cabinet and plug the EBM cable into the battery connector on the first EBM Attach the fixed cover plate to the EBM cable Repeat for each additional EBM Up to...

Page 31: ...ement software connect your computer to the UPS communication port using the supplied communication cable Power Cord Output Receptacles Communication Port UPS EBM EBM Figure 18 Typical Installation 120V UPS Model Shown 2 Plug the equipment to be protected into the appropriate UPS output receptacles see page 50 for more information on load segments NOTE DO NOT protect laser printers with the UPS be...

Page 32: ...UPS is in Standby mode with the equipment offline If the or indicator flashes see page 65 Site Wiring Fault Indicator Battery Service Indicator Figure 19 Fault Indicators 6 Press the On button The μ indicator illuminates solid and the bar graph indicators display the percentage of load being applied to the UPS The UPS is now in Normal mode and supplying power to your equipment To change the factor...

Page 33: ...es to the UPS or accessories otherwise damage may occur to your equipment and void your warranty The Powerware 9125 hardwired models require a dedicated branch circuit that meets the following requirements S 16A 2 pole circuit breaker for EH and GH models 20A 2 pole circuit breaker for EUH models to provide short circuit and overcurrent protection S The protection device requires a two pole discon...

Page 34: ...ill be connected Be absolutely sure there is no power Communication Port Terminal Block Cover UPS EBM EBM Figure 20 Typical Hardwired UPS Installation 3 Remove the terminal block cover and the wiring knockouts see Figure 21 Retain the terminal block cover and screws Input Wiring Access Output Wiring Access Terminal Block Cover Screws Figure 21 Wiring Access and Terminal Block 4 Pull the input and ...

Page 35: ...UT 1 3 OUTPUT 2 4 6 5 Figure 22 Terminal Block Table 1 UPS Wiring Specifications Wire Terminal UPS Wire Function Terminal Wire Tightening Wire Function Terminal Position EUH Models EH and GH Models Terminal Wire Size Rating Tightening Torque Input 1 L2 N p 2 G G 2 10 mm2 14 8 AWG 4 38 Nm 35 lb in 3 L1 L 14 8 AWG 4 38 Nm 35 lb in Output 4 L2 N p 5 G G 2 10 mm2 14 8 AWG 4 38 Nm 35 lb in 6 L1 L 14 8 ...

Page 36: ... indicator flashes see page 65 Site Wiring Fault Indicator Battery Service Indicator Figure 23 Fault Indicators 11 Press the On button The μ indicator illuminates solid and the bar graph indicators display the percentage of load being applied to the UPS The UPS is now in Normal mode and supplying power to your equipment To change the factory set defaults see Configuration on page 41 NOTE The batte...

Page 37: ...started until the On button is pressed WARNING The REPO circuit is an IEC 60950 safety extra low voltage SELV circuit This circuit must be separated from any hazardous voltage circuits by reinforced insulation CAUTION To ensure the UPS stops supplying power to the load during any mode of operation the input power must be disconnected from the UPS when the emergency power off function is activated ...

Page 38: ...m2 0 5 mm2 18 20 AWG NOTE A separate contact must simultaneously cause UPS input AC power to be removed Pin 1 Pin 2 Figure 24 REPO Connector 4 Reconnect the REPO connector to the REPO port 5 Verify that the externally connected REPO switch is not activated to enable power to the UPS output 6 Plug in the UPS or switch the main utility breaker on for hardwired units and start the UPS by pressing the...

Page 39: ... Receptacles Fuse Holder Circuit Protector Figure 25 2500 3000 VA 120V Rear Panel REPO Port Battery Connector X Slot Communication Bay Four 10A IEC 320 C13 Receptacles 16A IEC 320 Input Connector Network Transient Protector 16A IEC 320 C19 Receptacle Communication Port Figure 26 2500 3000 VA 208V Rear Panel Battery Connector with Cover Four 10A IEC 320 C13 Receptacles 16A IEC 320 Input Connector 1...

Page 40: ... Port Terminal Block REPO Port Battery Connector Network Transient Protector X Slot Communication Bay Figure 28 2500 3000 VA 208 240V Hardwired Rear Panel Communication Port Terminal Block REPO Port Battery Connector with Cover Network Transient Protector X Slot Communication Bay Figure 29 2500 3000 VA 230V Hardwired Rear Panel ...

Page 41: ...nducts a self test and enters Standby mode To turn on the UPS press the On button on the front panel The μ indicator illuminates solid and the bar graph indicators display the percentage of load being applied to the UPS Starting the UPS on Battery To turn on the UPS without using utility power press and hold the On button for at least four seconds The UPS starts up in Battery mode and supplies bat...

Page 42: ...plug or remove utility power from the UPS the UPS shuts down in five seconds All front panel indicators flash briefly prior to shutdown If you do not unplug or remove utility power from the UPS it remains in Standby mode Initiating the Self Test NOTE The batteries must be fully charged and the UPS must not be in Battery mode to perform the self test NOTE AC input power must be applied to the UPS f...

Page 43: ...ront panel indicates the UPS status through the UPS indicators Figure 30 shows the UPS front panel indicators and controls Normal Mode Indicator Flashing Unlit Lit Indicator Legend Test Alarm Reset Button On Button Off Button Bypass Mode Indicator Bar Graph Indicators Alarm Indicators see page 63 Battery Mode Indicator Figure 30 UPS Front Panel ...

Page 44: ...he percentage of UPS load capacity being used by the protected equipment see Figure 31 The UPS monitors and charges the batteries as needed and provides power protection to your equipment 10 10 25 26 50 51 75 76 100 100 Figure 31 Load Level Indicators When all of the bar graph indicators are illuminated and the indicator flashes power requirements exceed UPS capacity see page 65 for more informati...

Page 45: ...ecomes low while in Battery mode the indicator starts flashing and the alarm becomes continuous indicating approximately three minutes of battery time remaining When shutdown is imminent the indicator flashes NOTE Depending on the UPS load the 3 minute warning may occur before the batteries reach 25 capacity the front panel immediately displays the 3 minute warning For UPS and Extended Battery Mod...

Page 46: ... The UPS has an overtemperature condition S The UPS has an overload condition of 101 to 150 for 30 seconds S The UPS detects a fault in the battery or UPS electronics Standby Mode When the UPS is turned off and remains connected to utility power the UPS is in Standby mode The μ indicator flashes and the bar graph indicators are off indicating that power is not available to your equipment The batte...

Page 47: ...ltaneously for one beep The UPS transfers to Configuration mode The LEDs flash briefly and then display the enabled options 2 Press the On button to scroll through the options Each time you press the button the UPS beeps The LED for the selected option indicates the current setting flashing represents disabled options see Figure 33 and Table 2 Scrolling past the last LED returns to the first confi...

Page 48: ...ss and hold the On and Test Alarm Reset buttons simultaneously to toggle between Configuration and Operation modes 4 Press the Test Alarm Reset button to select an option 3 Press the On button to scroll to the next option 2 On Button Test Alarm Reset Button Configuration Mode Indicators Figure 33 Using Configuration Mode ...

Page 49: ...H and G GH models Flashing Disabled one of the other input voltage options is selected 127 or 240V Nominal Input Voltage On Selecting this option changes the nominal input voltage to one of the following S 127V for U models S 240V for EU EUH E EH and G GH models Flashing Disabled one of the other input voltage options is selected Site Wiring Fault Alarm On default Alarm sounds when the polarity of...

Page 50: ...CONFIGURATION EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide S 164201374 Rev D www powerware com 44 ...

Page 51: ...ernet 10 100BaseT network It has a built in switching hub that allows three additional network devices to be connected to the network without the requirement of additional network drops In addition a Powerware Environmental Monitoring Probe can be attached to obtain humidity temperature smoke alarm and security information S Relay Interface Card has isolated dry contact Form C relay outputs for UP...

Page 52: ...are Expansion Chassis for multiple communication options To establish communication between the UPS and a computer connect your computer to the UPS communication port using the supplied communication cable When the communication cable is installed power management software can exchange data with the UPS The software polls the UPS for detailed information on the status of the power environment If a...

Page 53: ...mon tied to chassis 6 DSR To external device tied to Pin 4 Out 7 RTS PnP from external device default or On Bypass relay contact jumper selectable In Out 8 AC Fail AC Fail relay contact 20 mA 30 Vdc contact rating Out 9 Power Source V 8 to 24 volts DC power Out The On Bypass Relay Contact You can enable the On Bypass relay using the jumper on the Single Port Card The jumper default is disabled To ...

Page 54: ...n Bypass Disabled On Bypass Enabled AS 400 NORM Figure 37 On Bypass Relay Jumper 3 To prevent electrostatic discharge ESD place one hand on a metal surface such as the UPS rear panel Align the Single Port Card with the slot guides and slide the card into the slot until it is firmly seated 4 Secure the Single Port Card with the screws removed in Step 1 ...

Page 55: ... 11 telephone connector that provides protection for modems fax machines or other telecommunications equipment As with most modem equipment it is not advisable to use this jack in digital PBX Private Branch Exchange environments NOTE DO NOT connect any telephone or fax modem equipment to the 230V models only network protection is available for 230V models 1 Connect the input connector of the equip...

Page 56: ... This feature allows you to save battery power See your power management software manual for details refer to the Software Suite CD or www powerware com for the latest information NOTE If power management software is not used the individual load segments cannot be controlled For hardwired UPSs there is only one load segment The terminal block serves as Load Segment 1 Each plug receptacle UPS has t...

Page 57: ...using the steps in Connecting the UPS Internal Battery on page 16 in reverse order NOTE The batteries in the UPS are rated for a 3 5 year service life The length of service life varies depending on the frequency of usage and ambient temperature Batteries used beyond expected service life will often have severely reduced runtimes Replace batteries at least every 5 years to keep units running at pea...

Page 58: ...es while the UPS is in Battery mode With the hot swappable battery feature UPS batteries can be replaced easily without turning the UPS off or disconnecting the load If you prefer to remove input power to change the batteries see Turning the UPS Off on page 36 Consider all warnings cautions and notes before replacing batteries WARNING S Batteries can present a risk of electrical shock or burn from...

Page 59: ...rface The battery is unsupported when you pull it out of the UPS To replace the UPS internal batteries 1 Remove the UPS front cover by pulling on both ends see Figure 41 Figure 41 Removing the UPS Front Cover 2 Push down on and unsnap the LED panel see Figure 42 3 Disconnect the battery cable from the UPS and cut the battery cable wire tie LED Panel Battery Cable Figure 42 Disconnecting the Batter...

Page 60: ...ace see Figure 44 See Recycling the Used Battery or UPS on page 57 for proper disposal Figure 44 Removing the Battery Trays 6 Slide the new battery trays into the UPS The battery trays are keyed to prevent improper connection The battery tray with the battery cable goes in the bay to the right 7 Reinstall the battery retaining bracket removed in Step 4 8 Reconnect the battery cable Secure the cabl...

Page 61: ...estals installed remove the pedestals and retain 4 If the EBM is in a rack install the mounting handles and brackets on the new EBM 5 Replace the EBM See Recycling the Used Battery or UPS on page 57 for proper disposal 6 Reinstall the pedestals if removed in Step 3 7 Reinstall the joining brackets if removed in Step 2 8 Plug the EBM cable s into the battery connectors as shown in Figure 45 For E E...

Page 62: ...ackets EBM Cables Figure 45 EBM Connections 120V UPS Model Shown Testing New Batteries Press and hold the button for three seconds to initiate a self test After the five second test is complete the indicator should turn off it may take a few seconds to turn off If the indicator stays on check the battery connections Call your service representative if the problem persists ...

Page 63: ...ies is required Refer to your local codes for disposal requirements S Do not open or mutilate the battery or batteries Released electrolyte is harmful to the skin and eyes It may be toxic CAUTION Do not discard the UPS or the UPS batteries in the trash This product contains sealed lead acid batteries and must be disposed of properly For more information contact your local recycling reuse or hazard...

Page 64: ...UPS MAINTENANCE EATON Powerware 9125 Two in One UPS 2500 3000 VA User s Guide S 164201374 Rev D www powerware com 58 ...

Page 65: ...20V default 110 120 127V selectable 80 144V PW9125 2500EU 2500 VA 1750W PW9125 2500G 2500 VA 1750W 208V d f lt 230 240V l t bl 160 288V PW9125 3000EU 3000 VA 2100W 208V default 230 240V selectable 160 288V PW9125 3000G 3000 VA 2100W PW9125 2500E 2500 VA 1750W 230V d f lt 220 240V l t bl 160 288V PW9125 3000E 3000 VA 2100W 230V default 220 240V selectable 160 288V PW9125 2500EUH 2500 VA 1750W PW912...

Page 66: ...EU PW9125 2500E PW9125 3000E 16A IEC 320 C20 input connector Country specific detachable power cord 4 10A IEC 320 C13 1 16A IEC 320 C19 PW9125 3000E PW9125 2500G PW9125 3000G power cord PW9125 2500EUH PW9125 3000EUH PW9125 2500EH PW9125 3000EH PW9125 2500GH PW9125 3000GH Terminal block Terminal block N A Table 6 Technical Specifications Nominal Frequency 45 65 Hz 50 60 Hz auto sensing Noise Filter...

Page 67: ...F to 77 F Transit Temperature 25 C to 55 C 13 F to 131 F Relative Humidity 5 95 noncondensing Operating Altitude Up to 3 000 meters above sea level Transit Altitude Up to 10 000 meters above sea level Audible Noise Less than 45 dBA Normal mode typical load Less than 50 dBA Battery mode Surge Suppression IEEE C62 41 Category B IEEE C62 41 Category B IEC 61000 4 5 IEC 61000 4 5 Safety Conformance UL...

Page 68: ...city at nominal line voltage after full load discharge External battery no more than 20x discharge time to 90 usable capacity at nominal line voltage after full load discharge Monitoring Advanced monitoring for earlier failure detection and warning auto detection of additional EBMs Table 10 Battery Runtimes in Minutes at Full Half Load Model UPS Internal Batteries 1 EBM 2 EBMs 3 EBMs 4 EBMs 2500 V...

Page 69: ...ons NOTE Some alarms such as the Overtemperature and Overload alarms must be cleared by shutting down and restarting the UPS see page 65 for more information Flashing Unlit Lit Indicator Legend Self Test Test Alarm Reset Button Battery Service Site Wiring Fault Overtemperature Overload Figure 46 Alarm Indicators Silencing an Audible Alarm Before silencing an alarm check the alarm condition and per...

Page 70: ...eceptacles For hardwired models contact a qualified electrician to check connections to the power source The output receptacle circuit breaker if applicable is open Check the load Disconnect faulty load equipment Wait several minutes before resetting the UPS circuit breaker One of the load segments has been turned off through the power management software Reactivate the segment with the software T...

Page 71: ...ndicator If the indicator is still flashing see Replacing Batteries on page 52 The batteries are not connected correctly Check the battery connections Call your service representative if the problem persists Site Wiring Fault 120V models only Ground wire connection does not exist or the line and neutral wires are reversed in the wall outlet Have a qualified electrician correct the wiring To disabl...

Page 72: ... number S Serial number S Version number if available S Date of failure or problem S Symptoms of failure or problem S Customer return address and contact information If repair is required you will be given a Returned Material Authorization RMA Number This number must appear on the outside of the package and on the Bill Of Lading if applicable Use the original packaging or request packaging from th...

Page 73: ... repaired or replaced at a Company site or such other location as determined by Company If the Warranted Item is to be replaced by Company and the End User supplies a credit card number or purchase order for the value of the replacement Product Company will use commercially reasonable business efforts to ship via standard ground shipment and at no cost to the End User the replacement Warranted Ite...

Page 74: ...L OTHER WARRANTIES INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTIES OF MERCHANTABILITY TITLE NON INFRINGEMENT AND FITNESS FOR A PARTICULAR PURPOSE CORRECTION OF NON CONFORMITIES IN THE MANNER AND FOR THE PERIOD OF TIME PROVIDED ABOVE SHALL CONSTITUTE COMPANY S SOLE LIABILITY AND END USER S EXCLUSIVE REMEDY FOR FAILURE OF COMPANY TO MEET ITS WARRANTY OBLIGATIONS WHETHER CLAIMS OF THE END USER AR...

Page 75: ...duct is initially sold by Company for resale to an End User WHAT THIS WARRANTY COVERS In addition to the standard Two Year Limited Warranty covering the applicable Product the warrantor warrants that the Product will have a service life defined below of ten years from the date of purchase the Ten Year Service Life when used in accordance with the storage handling installation operation and mainten...

Page 76: ...OMPANY SPECIFICALLY DOES NOT WARRANT SOFTWARE SUCH AS LINUX THAT WAS CREATED USING AN OPEN SOURCE MODEL OR IS DISTRIBUTED PURSUANT TO AN OPEN SOURCE LICENSE THIS WARRANTY IS THE SOLE AND EXCLUSIVE WARRANTY OFFERED BY COMPANY WITH RESPECT TO THE PRODUCTS AND SERVICES AND EXCEPT FOR SUCH FOREGOING WARRANTY COMPANY DISCLAIMS ALL OTHER WARRANTIES INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTIES OF ...

Page 77: ...North Carolina 27616 USA Load Protection Guarantee US and Canada Powerware UPS Models 3105 3110 3115 5110 5115 5125 9120 9125 9150 9155 9170 and FERRUPS GUARANTOR The Guarantor for the load protection guaranty set forth herein is Eaton Power Quality Corporation a Delaware Corporation company Company LIMITED GUARANTY This load protection guaranty this Guaranty applies only to the original End User ...

Page 78: ... OF PROFITS OR REVENUE LOSS OF USE OF PRODUCTS LOSS OF DATA COST OF CAPITAL CLAIMS OF CUSTOMERS OF THE END USER OR ANY SPECIAL INDIRECT INCIDENTAL OR CONSEQUENTIAL DAMAGES WHATSOEVER THE TOTAL CUMULATIVE LIABILITY OF COMPANY HEREUNDER WHETHER THE CLAIMS ARE BASED IN CONTRACT INCLUDING INDEMNITY IN TORT INCLUDING NEGLIGENCE OR STRICT LIABILITY OR OTHERWISE SHALL NOT EXCEED THOSE SET FORTH ABOVE Com...

Reviews: