Instruction Booklet 

IB015001EN

Effective June 2015

Power Xpert Solar DC 

breaker recombiner 

  

EATON 

www.eaton.com

Electrical connection of  

Recombiner sections

Electrical connections between Recombiner sections, when 

required, are made using bus splice plates . Consult the 

manufacturer’s drawings for details for each Recombiner section .
Remove structure deadfront covers and side sheets as needed 

to access Recombiner chassis and components . Retain all cover 

mounting hardware and covers for reassembly . Protect hardware  

and parts from moisture, debris, and damage .

Splice plates

Splice plates are short flat pieces of busbar that join the main  

bus running horizontally through a multiple section Recombiner  

(see 

Figure 14

) .

Figure 14. Splice plates

For larger amperage Recombiners, multiple splice plates are to be 

used on the same phase . Maintain the orientation, by phase and 

sequence of the splice plates . The orientation of the splice plates 

must remain identical to the way they were shipped from the 

manufacturer . Clearances must be maintained . If you are unsure 

about the correct orientation or have questions about the installation, 

contact Eaton before installing the splice plates .
Splice plates are used to attach the main horizontal bus between 

Recombiner sections or shipping splits . While maintaining the correct 

phase orientation and sequence, install splice plates with the carriage 

bolts and hex nuts with captive Belleville washers supplied by the 

manufacturer . Refer to 

Appendix A,

 

Table 1

 for torque values .

Carriage bolts must align with the corresponding rectangular  

holes in the fixed horizontal bus and the splice plates . If multiple 

splice plates are used, install in the same sequence as shipped  

from the manufacturer . The ground bus should be connected in the 

same manner .

Inspect splices plates and main fixed horizontal bus prior to 

installation . If there is any suspected damage, contact the 

manufacturer immediately for replacements . NEVER ENERGIZE  

ANY RECOMBINER WITH DAMAGED BUS OR COMPONENTS .
To accommodate future serviceability, the manufacturer 

recommends that the head of the carriage bolt be mounted from  

the rear of the Recombiner for FRONT ACCESSIBLE Recombiners 

with the hex nut with Belleville washer positioned to the front . 
For REAR ACCESSIBLE Recombiners, the manufacturer 

recommends that the head of the carriage bolt be mounted from 

the front of the Recombiner with the hex nut and Belleville washer 

positioned to the rear .
Repeat the process until all holes in the horizontal bus are connected 

with bolts and nuts for each shipping split . Inspect connections to 

ensure that there is no foreign material at the connection point and 

that all connections are properly aligned and bolts are seated .
Torque all connections to torque requirements on labels affixed to 

each Recombiner and as shown in 

Appendix A,

 

Table 1

 .

Grounding

 WARNING

THE DC INPUT AND DC OUTPUT CIRCUITS ARE ISOLATED FROM THE 

ENCLOSURE AND SYSTEM GROUNDING, IF REQUIRED BY SECTION 250 OF 

THE NATIONAL ELECTRICAL CODE, ANSI/NFPA 70, IS THE RESPONSIBILITY 

OF THE INSTALLER.

 WARNING

THE PHOTOVOLTAIC SYSTEM GROUNDING SHALL BE INSTALLED PER  

THE REQUIREMENTS OF SECTIONS 690.41 THROUGH 690.47 OF THE 

NATIONAL ELECTRICAL CODE, ANSI/NFPA 70 AND IS THE RESPONSIBILITY 

OF THE INSTALLER.

Torque both line and load connections to values indicated on the 

labeling on the Recombiner . Refer to 

Appendix A, Table  2

 for  

torque values .

Installation of incoming Recombiner connections

 DANGER

DE-ENERGIZE RECOMBINER—HAZARDOUS VOLTAGE WILL CAUSE SEVERE 

INJURY OR DEATH.

DO NOT work on electrical equipment while it is energized . Verify 

that power entering the equipment is de-energized at the source . 
Power is brought into a Recombiner by cable .
Remove structure covers as needed to access Recombiner chassis 

and components . Retain all cover mounting hardware and covers for 

reassembly . Protect hardware and parts from moisture, debris, and 

damage

otee:

N

As a minimum, all Recombiner connections are rated for use with  

90 °C or higher rated conductors . When wire is used with temperature ratings 

above 90 °C, it shall be sized based on the ampacity of wire rated 75 °C .

View "A"

Typical view when more

than one bar per phase

Summary of Contents for Power Xpert

Page 1: ...biner Contents Description Page Safety measures 2 Pre installation receiving handling and storage 3 Pre installation preparation 5 Considerations for seismic qualified installations 5 Electrical conne...

Page 2: ...D WITHOUT THE SAFETY ALERT SYMBOL INDICATES A POTENTIALLY HAZARDOUS SITUATION THAT IF NOT AVOIDED CAN RESULT IN PROPERTY DAMAGE Eaton s liability for any errors or omissions in this document is limite...

Page 3: ...t from dust dirt moisture and damage until ready for installation The Recombiner should remain attached to its shipping skid until it has been moved into its final installation position Handling WARNI...

Page 4: ...which are top heavy equipment The forks or blades of the forklift must run through the entire Recombiner shipping length and be extended to the outermost sides of the wooden shipping skids see Figure...

Page 5: ...ional requirements The entire area around the Recombiner should be thoroughly cleaned of all debris Considerations for seismic qualified installations Recombiners are seismic qualified and in seismica...

Page 6: ...talled cables wire used to connect components between sections from damage when moving Recombiner sections into place An outdoor multi section Recombiner will ship with uninstalled intermediate roof c...

Page 7: ...type washer see Figure 11 Holes are provided on the side of each Recombiner section for this purpose Three holes are located on the side of each section toward the front and back see Figure 12 Figure...

Page 8: ...BUS OR COMPONENTS To accommodate future serviceability the manufacturer recommends that the head of the carriage bolt be mounted from the rear of the Recombiner for FRONT ACCESSIBLE Recombiners with t...

Page 9: ...r of the crimp tool Once the lug is affixed to the conductor reinstall the lug on the lug pad using the existing hardware Torque hardware using information provided on Recombiner labeling Refer to App...

Page 10: ...s on the Recombiner using hardware supplied by the manufacturer Take caution that conductors are not pinched between parts when installing the deadfront cover plates side sheets and filler plates All...

Page 11: ...T AC DIELECTRIC MEGGER TESTING DAMAGE TO COMPONENTS WILL OCCUR A test resulting in readings at or above 1 mega ohm is satisfactory Compare these test readings with prior readings and retain with previ...

Page 12: ...ts such as short circuits and overloads until the cause of the event has been identified and corrected After the event has been rectified test equipment per the maintenance process described in this p...

Page 13: ...the part Drawing numbers Rating of part s Electrical equipment has a limited life span As such the manufacturer cannot guarantee the availability of obsolete equipment or parts Equipment replacement m...

Page 14: ...VE POSITIVE Ground NEGATIVE Ground Date All overcurrent devices closed Phase to phase connections Phase to ground connections POSITIVE NEGATIVE POSITIVE Ground NEGATIVE Ground Notes Date All overcurre...

Page 15: ...s Secondary control wiring Clean ventilation Date Checklist 3 Notes and actions taken Cleaning Bus and cable connections Insulation inspection Overcurrent device inspection Controllers Other protectiv...

Page 16: ...eir respective owners Instruction Booklet IB015001EN Effective June 2015 Power Xpert Solar DC breaker recombiner Eaton 1000 Eaton Boulevard Cleveland OH 44122 United States Eaton com 2015 Eaton All Ri...

Reviews: