Eaton Power Xpert 9395C UPS Installation and Operation Manual 164000821—Rev 06
55..44
IInnssttaalllliinngg aann O
Oppttiioonnaall R
Reellaayy IInntteerrffaaccee M
Moodduullee IIII
To install RIM II wiring:
1.
Verify the UPS system is turned off and all power sources are removed. See
for shutdown instructions.
2.
Perform the procedure listed in paragraph
Installing an Optional Powerware Hot Sync CAN Bridge Card
.
NOTE
If mounting to a hollow wall, secure the enclosure to a wood or metal stud within the
wall. Do not use hollow wall anchors.
3.
Securely mount the RIM II at the desired location. See
for mounting hole locations.
NOTE
When installing signal wiring for CAN card J3 terminals, conduit must be installed
between the device and the UPS cabinet.
4.
Remove the UPS cabinet top interface conduit landing plates to drill or punch conduit holes (see
).
5.
Reinstall the conduit landing plate.
6.
Install conduit between the UPS and RIM II. See
for RIM II knockout hole location.
7.
Install wiring between the UPS and RIM II. See
and
for the Powerware Hot Sync CAN
Bridge Card terminal location and wiring information, and
,
, and
for the RIM II
terminal location and wiring information.
NOTE
120 Vac for the RIM II should be supplied from the critical bus by facility planners or the
customer.
8.
Install 120 Vac power wiring from the critical bus to the RIM II. See
, and
for
the terminal location and wiring information.
9.
Close the front door and secure the latch.
10. Restart the UPS. See
for startup instructions.
NOTE
Setup of the Powerware Hot Sync CAN Bridge Card must be performed by an
authorized Eaton Customer Service Engineer. Contact an Eaton service representative
to schedule a date.
11. Contact an Eaton service representative for verification and testing of the RIM II and its connections prior
to making connections with J1 through J4 (see
and
You can order interface cables separately for connecting to the 15–Pin D–Sub Connectors.
Table 22. J1 through J4 Interface Connectors
Status
J1 through J4
Description
UPS AVAILABLE
Pins 1 and 12
Contacts are closed when the UPS is
operating in Online mode or ready to
supply the load.
UPS OFFLINE
Pins 3 and 13
Contacts are open when the UPS is
offline. Contacts are closed when the
UPS is operating in Online mode.