background image

4

Instructional Leaflet 

IL0131093EN

Effective January 2019

Instructions for secondary terminal blocks 

  

  

EATON

 www.eaton.com

14

13

Figure 10. Step 6.

Step 7: 

To remove a fixed secondary terminal block, lift up 

on the small flexible mounting tab at the top of fixed terminal 

block mounting plate, and rotate the terminal block out in the 

opposite direction shown in Step 6.

IMPORTANT

KEEP IN MIND THAT TO REMOVE AN ACCESSORY PLUG ON A FIXED 

CIRCUIT BREAKER, THE APPROPRIATE FIXED SECONDARY TERMINAL 

BLOCK MUST FIRST BE REMOVED.  ONCE THE TERMINAL BLOCK IS 

REMOVED, THE ACCESSORY CONNECTOR PLUG CAN BE UNPLUGGED 

FROM THE BOTTOM OF THE TERMINAL BLOCK. REFER TO FIGURE 4 IN 

SECTION 1 FOR ASSISTANCE WITH THE REMOVAL. 

Step 8:

 Once all terminal blocks are securely mounted, replace 

the front cover and secure it in place with the four mounting 

screws previously removed in Step 1. 

Section 3: Installation and Removal of 

Drawout Terminal  Blocks 

IMPORTANT

KEEP IN MIND THAT THE SECONDARY TERMINAL BLOCKS ASSOCI-

ATED WITH DRAWOUT CIRCUIT BREAKERS ARE MOUNTED ON THE 

BREAKER’S DRAWOUT CASSETTE (FIGURE 11).  ACCESSORY SECOND-

ARY PLUGS PLUG INTO A SECONDARY PLUG HOUSING MOUNTED 

ON THE TOP FRONT OF THE CIRCUIT BREAKER (FIGURE 12).  AS SUCH, 

SECONDARY CONNECTIONS ARE AUTOMATICALLY MADE OR DIS-

CONNECTED DURING THE LEVERING (RACKING) PROCESS AS THE 

SECONDARY PLUG HOUSING ON THE BREAKER ENGAGES OR DIS-

ENGAGES THE SECONDARY TERMINAL BLOCKS MOUNTED ON THE 

DRAWOUT CASSETTE.  FOR THIS REASON, ACCESSORY SECONDARY 

PLUGS DO NOT HAVE TO BE UNPLUGGED TO ADD OR REMOVE TER-

MINAL BLOCKS. REFER TO FIGURES 3 AND 4 OF SECTION 1 AND THE 

ASSOCIATED COPY FOR ASSISTANCE WITH CONNECTING OR DISCON-

NECTING ACCESSORY SECONDARY PLUGS.

ote:

N

Many illustrations use the NF Frame cassette for illustrative purposes 

only. The RF Frame cassette is handled in a similar fashion.

Figure 11. Cassette-Mounted Terminal Blocks NF Frame.

Figure 11A. Cassette-Mounted Terminal Blocks RF Frame.

Full Complement of 

Secondary Terminal 

Blocks Shown Installed

Full Complement of 

Secondary Terminal 

Blocks Shown Installed

Summary of Contents for Power Defense PD-NF

Page 1: ...FOLLOW THESE STEPS FOR ALL PROCEDURES DESCRIBED IN THIS INSTRUCTION LEAFLET COULD RESULT IN DEATH BODILY INJURY OR PROPERTY DAMAGE WARNING THE INSTRUCTIONS CONTAINED IN THIS IL AND ON PRODUCT LABELS...

Page 2: ...rs secondary terminal blocks Figure 1 are mounted onto an insulated support frame on the top front portion of the drawout cassette Figure 1 Drawout Terminal Block For fixed mounted circuit breakers se...

Page 3: ...Step 3 Become familiar with the fixed terminal block mount ing plate where secondary connections are made Note N Secondary connection points have numerical and descriptive laser etched identifications...

Page 4: ...IMPORTANT KEEP IN MIND THAT THE SECONDARY TERMINAL BLOCKS ASSOCI ATED WITH DRAWOUT CIRCUIT BREAKERS ARE MOUNTED ON THE BREAKER S DRAWOUT CASSETTE FIGURE 11 ACCESSORY SECOND ARY PLUGS PLUG INTO A SECO...

Page 5: ...aker s secondary plug housing to ensure accurate terminal block placement In addition a terminal block alignment bracket is assembled to provide proper alignment and separation of each individual term...

Page 6: ...etween any mounted terminal blocks and put it aside for re installment after new terminal blocks are connected to the mounting bracket Figure 16 Step 3 Grasp Here Step 4 Connect the bottom part of the...

Page 7: ...Step 8 Step 9 Once the terminal block alignment bracket is in place inspect it from the bottom to ensure that the teeth on the bracket separate each individual terminal block Only one installed termin...

Page 8: ...tual agreement between the parties This literature is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipm...

Reviews: