TD03309002E
For more information visit:
www.EatonElectrical.com
Technical Data
Effective: January 2005
Page
5
Storage, Handling,
Installation and
Maintenance of Controllers
Troubleshooting
Table 3. Contactor Troubleshooting Chart
Defect
Cause
Remedy
Contactor
Overheating
Load current too high
Reduce load. Use larger contactor.
Loose connections
Clean discolored or dirty connections and retighten. Replace poorly crimped
lugs.
Overtravel and/or contact force too low
Adjust overtravel, replace contacts, and replace contact springs as required to
correct defect.
Collection of copper oxide or foreign matter
on copper contact faces
Clean with fine file. Use Type 12 enclosure for dirty atmosphere.
Load is on in excess of 8 hours on copper
contacts
Change operating procedure. Check factory for more suitable contacts.
Ambient temperature is too high
Reduce load. Provide better ventilation. Relocate starter. Use larger contactor.
Line and/or load cables are too small
Install terminal block and run larger conductors between contactor and terminal
block.
Poor Arc Interruption
Arc box not in place
Install arc box.
Arc box damaged
Replace broken or eroded insulating parts, arc horns, and grid plates. Clean or
replace insulating parts having a heavy coating of foreign conducting material.
Dirt or paint on arc horns or steel-grid plates
Remove contaminating materials which may have accumulated on arc horns
and steel-grid plates.
Magnetic hardware substituted for non-
magnetic hardware in arc box and blowout
assemblies
Replace with correct hardware; brass or stainless steel as available.
Blowout coil reversed or shorted
Replace with new blowout coil or correct defect by reversing coil.
Oil level is low or oil is contaminated (in oil-
immersed contactor)
Fill tank to proper level with fresh oil. Test at 28 kV.
Welding of Contacts
Overtravel and/or contact force is too low
Adjust overtravel, replace contacts, and replace contact springs as required to
correct defect.
Magnet armature stalls or hesitates at contact
touch point
Correct low voltage at coil terminals as coil draws inrush current.
Contactor drops open to contact-touch
position because of voltage dip
Maintain voltage at coil terminals. Install low voltage protective device,
sometimes called “Brownout Protector.”
Excessive contact bounce on closing
Correct coil overvoltage condition.
Contacts rebound to contact-touch position
when opening
Correct mechanical defect in stop assembly. Correct mechanical defect in latch if
one is used.
Poor contact alignment
Adjust contacts to touch simultaneously within 1/32 inch.
Jogging duty is too severe
Reducing jogging cycle. Check factory for more weld-resistant contact material.
Use larger contactor.
Excessive inrush current
Motor has locked rotor code letter greater than G. Most contactors are designed
for motors with code letters A through G. Therefore, use larger contactor. Check
factory for more weld-resistant contact material.
Vibration in starter mounting
Move starter to location having less shock and vibration. Insulate starter form
shock and vibration. Provide more rigid support for starter.
Contacts
Contact Chatter
Low voltage
Check supply voltage, especially during starting. Check coil voltage rating.
Increase voltage or change coil rating as required.
Poor contact in control circuit
Replace the contact or use holding-circuit interlock (3-wire control).
Broken shading coil
Replace magnet and armature assemblies.
Welding
Abnormal inrush current
Use next larger size contactor or check for grounds, shorts, or excessive motor
load current.
Rapid jogging
Install larger device rated for jogging service.
Insufficient contact pressure
Replace contacts and springs, check contacts for abnormal wear or damage.
Low voltage preventing magnet from sealing
Check supply voltage to coil, especially for momentary voltage dip during
starting.
Foreign matter preventing contacts from
closing
Clean contacts with freon. Contacts used at low current and voltage levels
should be cleaned with freon.
Vibration in starter mounting
Insulate starter from shock and vibration.
Short circuit
Remove fault and check to be sure fuse or breaker size is correct.
Summary of Contents for Pow-R-Line SPX0361126
Page 2: ......
Page 4: ......
Page 6: ......
Page 7: ...TAB 1 Switchboards ...
Page 8: ......
Page 10: ......
Page 11: ...Instruction Data ...
Page 12: ......
Page 37: ...Component Data ...
Page 38: ......
Page 43: ......
Page 44: ......
Page 48: ......
Page 66: ...3 6 IM02601001E www eaton com Mechanical Installation ...
Page 114: ...14 IM02601001E www eaton com Using the I O Option Cards ...
Page 134: ...9 14 IM02601001E www eaton com Functions on the Web Server Pages Events Page ...
Page 156: ...10 22 IM02601001E www eaton com Setup on the Web Server Pages ...
Page 166: ...A 2 IM02601001E www eaton com Navigation Maps Main Menu Screens Sheet 1 ...
Page 167: ...www eaton com IM02601001E A 3 Navigation Maps Operating Mode Screens Sheet 2 ...
Page 168: ...A 4 IM02601001E www eaton com Navigation Maps Reset Mode Screens Sheet 3 ...
Page 169: ...www eaton com IM02601001E A 5 Navigation Maps Configuration Mode Screens Sheet ...
Page 170: ...A 6 IM02601001E www eaton com Navigation Maps ...
Page 172: ...B 2 IM02601001E www eaton com DIP Switch Description ...
Page 240: ...C 68 IM02601001E www eaton com Modbus Register Maps ...
Page 241: ......
Page 242: ......
Page 259: ...Shop Drawings ...
Page 260: ......
Page 262: ......
Page 264: ......
Page 266: ......
Page 268: ......
Page 270: ......
Page 272: ......
Page 274: ......
Page 275: ...Date PDF Generated 10 19 2012 Page 1 of 1 ...
Page 276: ......
Page 278: ......
Page 280: ......
Page 282: ......
Page 284: ......
Page 286: ......
Page 288: ......
Page 289: ...TAB 2 Panelboards ...
Page 290: ......
Page 292: ......
Page 293: ...Instruction Data ...
Page 294: ......
Page 296: ......
Page 325: ...Spare Parts ...
Page 326: ......
Page 371: ...Drawings ...
Page 372: ......
Page 374: ......
Page 376: ......
Page 378: ......
Page 380: ......
Page 382: ......
Page 384: ......
Page 386: ......
Page 387: ...TAB 3 Dry Type Transformers ...
Page 388: ......
Page 390: ......
Page 391: ...Instruction Data ...
Page 392: ......
Page 401: ...Drawings ...
Page 402: ......
Page 404: ......
Page 405: ...TAB 4 Molded Case Circuit Breakers ...
Page 406: ......
Page 408: ......
Page 409: ...Instruction Data ...
Page 410: ......
Page 417: ...TAB 5 Safety Switches ...
Page 418: ......
Page 420: ......
Page 421: ...Instruction Data ...
Page 422: ......
Page 424: ......
Page 452: ......
Page 453: ...Spare Parts ...
Page 454: ......
Page 467: ...Drawings ...
Page 468: ......
Page 470: ......
Page 471: ...Item 001 Cat DH261FGK ...
Page 472: ......
Page 474: ......
Page 475: ...Item 002 Cat DH261FGK ...
Page 476: ......
Page 478: ......
Page 479: ...Item 003 Cat DH261FGK ...
Page 480: ......
Page 482: ......
Page 483: ...Item 004 Cat DH261FGK ...
Page 484: ......
Page 486: ......
Page 487: ...Item 09 Cat DH364NRK ...
Page 488: ......
Page 490: ......
Page 491: ...Item 011 Cat DH324NGK ...
Page 492: ......
Page 494: ......
Page 495: ...Item 013 Cat DH362FRK ...
Page 496: ......
Page 498: ......
Page 499: ...Item 015 Cat DH321NRK ...
Page 500: ......
Page 502: ......
Page 503: ...Item 017 Cat DH362FRK ...
Page 504: ......
Page 506: ......
Page 507: ...Itm 019 Cat DH221NGK ...
Page 508: ......
Page 510: ......
Page 511: ...Item 021 Cat DH361UGK ...
Page 512: ......
Page 513: ...TAB 6 Enclosed Control NEMA ...
Page 514: ......
Page 516: ......
Page 517: ...Instruction Data ...
Page 518: ......
Page 550: ......
Page 551: ......
Page 552: ......
Page 561: ......
Page 562: ......
Page 578: ......
Page 579: ...Drawings ...
Page 580: ......
Page 582: ......
Page 584: ......