13
Instruction Manual
IM01500001E
Effective July 2011
Pow-R-Line switchboards
eaton Corporation
www.eaton.com
Pre-energizing procedures and inspection
Before energizing any switchboard, perform a comprehensive
inspection to make certain that the switchboard is ready to be
energized . This includes the following steps:
1.
Verify that the switchboard is not energized .
2.
Visually inspect the switchboard and remove all foreign materials,
such as tools, scraps of wire, and other debris from all switch-
board sections .
3.
Remove and discard all packing materials and temporary shipping
braces from the switchboard .
4.
Any accumulation of dust and dirt should be removed with a
vacuum cleaner . Use a lint-free cloth to remove dust and dirt
on other surfaces . Never use compressed air as this may blow
contaminants into electrical and/or electronic components . Never
use solvents or other chemicals to clean surfaces or components .
5.
Visually inspect all ventilation points to ensure that there is no
blockage or debris . Remove any debris that is present .
6.
Verify that all field bus and wire connections have the proper
torque per instructions on the switchboard and on components .
7.
All factory connections are made using calibrated power tools .
However, vibrations do occur in transit and handling . Verify
factory connections by checking at least 10% of the total factory
connections for tightness . If this spot check reveals loose
connections, proceed to check all factory connections . These
connections include bus hardware connections, circuit breaker
and switch terminals, contactors, metering, and other connec-
tions, including the incoming terminals .
8.
Visually inspect switchboard insulators, busbar, and conductors
for damage . DO NOT ENERGIZE IF DAMAGE FOUND .
Contact Eaton .
9.
If fusible switch type overcurrent devices are used, verify that
proper fusing has been selected and installed . Eaton does not
typically supply switchboards with these fuses .
Overcurrent devices
Overcurrent devices are typically shipped in either the open (OFF)
or “tripped” position . Manually close, and then open these devices
to ensure that they are functioning properly . At the completion of
this process, be sure that the overcurrent device is in the OFF or
“tripped” position .
Inspect overcurrent devices for any visible damage . If damage is
found, DO NOT ENERGIZE the switchboard . Contact Eaton .
Circuit breakers
Some circuit breaker types provide the ability to adjust trip settings .
When shipped, settings are typically at the minimum rating . There
are two types of trip units included in this group: adjustable thermal
magnetic and electronic trip units .
Thermal magnetic trip units
may have an adjustable magnetic
setting . Use the engineering study recommendations, if available,
to adjust to the proper setting . Low magnetic settings feeding high
inrush loads, such as motors, could nuisance trip on startup . For
specifics on breaker types, consult the circuit breaker instruction
leaflets shipped with the switchboard .
Electronic trip units
have several settings depending on the breaker
ordered . Electronic trip units may include long-time (L), short-time
(S), instantaneous (I), and ground fault (G) settings . These trip units
are available in combinations LS, LSI, LSG, and LSIG . Check the
electrical drawings, engineering study, or the engineer’s recommen-
dations for these trip unit settings . For details on each type, refer to
the Eaton circuit breaker and electronic trip unit instruction leaflets
shipped with the switchboard .
For certain breakers with electronic trip units, a portable test kit is
available from Eaton . An auxiliary power module is included in the
test kit . This auxiliary power module powers the electronic trip unit
when the board is de-energized and allows testing . The kit includes
complete instructions and test times for testing long-time, short-
time/instantaneous operations, and optional ground fault operation
of the circuit breakers .
Figure 25. Circuit Breakers
Circuit Breaker with
Adjustable Magnetic
Trip Unit
Circuit Breaker with
Electronic Trip Unit
Summary of Contents for Pow-R-Line SPX0361126
Page 2: ......
Page 4: ......
Page 6: ......
Page 7: ...TAB 1 Switchboards ...
Page 8: ......
Page 10: ......
Page 11: ...Instruction Data ...
Page 12: ......
Page 37: ...Component Data ...
Page 38: ......
Page 43: ......
Page 44: ......
Page 48: ......
Page 66: ...3 6 IM02601001E www eaton com Mechanical Installation ...
Page 114: ...14 IM02601001E www eaton com Using the I O Option Cards ...
Page 134: ...9 14 IM02601001E www eaton com Functions on the Web Server Pages Events Page ...
Page 156: ...10 22 IM02601001E www eaton com Setup on the Web Server Pages ...
Page 166: ...A 2 IM02601001E www eaton com Navigation Maps Main Menu Screens Sheet 1 ...
Page 167: ...www eaton com IM02601001E A 3 Navigation Maps Operating Mode Screens Sheet 2 ...
Page 168: ...A 4 IM02601001E www eaton com Navigation Maps Reset Mode Screens Sheet 3 ...
Page 169: ...www eaton com IM02601001E A 5 Navigation Maps Configuration Mode Screens Sheet ...
Page 170: ...A 6 IM02601001E www eaton com Navigation Maps ...
Page 172: ...B 2 IM02601001E www eaton com DIP Switch Description ...
Page 240: ...C 68 IM02601001E www eaton com Modbus Register Maps ...
Page 241: ......
Page 242: ......
Page 259: ...Shop Drawings ...
Page 260: ......
Page 262: ......
Page 264: ......
Page 266: ......
Page 268: ......
Page 270: ......
Page 272: ......
Page 274: ......
Page 275: ...Date PDF Generated 10 19 2012 Page 1 of 1 ...
Page 276: ......
Page 278: ......
Page 280: ......
Page 282: ......
Page 284: ......
Page 286: ......
Page 288: ......
Page 289: ...TAB 2 Panelboards ...
Page 290: ......
Page 292: ......
Page 293: ...Instruction Data ...
Page 294: ......
Page 296: ......
Page 325: ...Spare Parts ...
Page 326: ......
Page 371: ...Drawings ...
Page 372: ......
Page 374: ......
Page 376: ......
Page 378: ......
Page 380: ......
Page 382: ......
Page 384: ......
Page 386: ......
Page 387: ...TAB 3 Dry Type Transformers ...
Page 388: ......
Page 390: ......
Page 391: ...Instruction Data ...
Page 392: ......
Page 401: ...Drawings ...
Page 402: ......
Page 404: ......
Page 405: ...TAB 4 Molded Case Circuit Breakers ...
Page 406: ......
Page 408: ......
Page 409: ...Instruction Data ...
Page 410: ......
Page 417: ...TAB 5 Safety Switches ...
Page 418: ......
Page 420: ......
Page 421: ...Instruction Data ...
Page 422: ......
Page 424: ......
Page 452: ......
Page 453: ...Spare Parts ...
Page 454: ......
Page 467: ...Drawings ...
Page 468: ......
Page 470: ......
Page 471: ...Item 001 Cat DH261FGK ...
Page 472: ......
Page 474: ......
Page 475: ...Item 002 Cat DH261FGK ...
Page 476: ......
Page 478: ......
Page 479: ...Item 003 Cat DH261FGK ...
Page 480: ......
Page 482: ......
Page 483: ...Item 004 Cat DH261FGK ...
Page 484: ......
Page 486: ......
Page 487: ...Item 09 Cat DH364NRK ...
Page 488: ......
Page 490: ......
Page 491: ...Item 011 Cat DH324NGK ...
Page 492: ......
Page 494: ......
Page 495: ...Item 013 Cat DH362FRK ...
Page 496: ......
Page 498: ......
Page 499: ...Item 015 Cat DH321NRK ...
Page 500: ......
Page 502: ......
Page 503: ...Item 017 Cat DH362FRK ...
Page 504: ......
Page 506: ......
Page 507: ...Itm 019 Cat DH221NGK ...
Page 508: ......
Page 510: ......
Page 511: ...Item 021 Cat DH361UGK ...
Page 512: ......
Page 513: ...TAB 6 Enclosed Control NEMA ...
Page 514: ......
Page 516: ......
Page 517: ...Instruction Data ...
Page 518: ......
Page 550: ......
Page 551: ......
Page 552: ......
Page 561: ......
Page 562: ......
Page 578: ......
Page 579: ...Drawings ...
Page 580: ......
Page 582: ......
Page 584: ......