Pow-R-Line X Retrofit Panelboards

Instruction Manual 

MN014011EN

Effective January 2020

P1RX 240Vac Max & P2RX 347/600Vac Max

Summary of Contents for P1RX 240Vac Max

Page 1: ...Pow R Line X Retrofit Panelboards Instruction Manual MN014011EN Effective January 2020 P1RX 240Vac Max P2RX 347 600Vac Max...

Page 2: ......

Page 3: ...1EN January 2020 eatoncanada ca Table of Content Installation Criteria 2 Safety Measures 3 Pre Installation Receiving Handling and Storage 4 Removal of Existing Panelboard Interior 4 Installation of R...

Page 4: ...2 1067 Lug 24 400 48 1219 20 0 508 5 75 127 30 42 Table 2 P2RXL P2RXB Panelboards Main Device Circuits Current Amperes Minimum Height in mm Minimum Width in mm Minimum Depth in mm Lug 18 100 19 5 495...

Page 5: ...ade all reasonable efforts to ensure that the instructions in this document are adequate and free of material errors and omissions Eaton will if necessary explain issues which may not be covered by th...

Page 6: ...TALL AND OR SERVICE THIS EQUIPMENT Removal of Existing Panelboard Interior DO NOT work on electrical equipment while energized Verify power entering the equipment is de energized at the source Follow...

Page 7: ...maintained per NECTM CECTM Care must be taken to ensure that the trim will completely cover openings in the enclosure If not using existing mounting hardware mark minimum of 8 mounting locations on th...

Page 8: ...conductor into lug so the bare conductor fills the full length of the lug body Tighten lug then torque to levels indicated on the panelboard label If compression lugs are utilized and supplied with th...

Page 9: ...uire ground fault protection for this installation Other GFP applications may be used including multi level ground fault protection Refer to the panelboard drawings and electrical construction drawing...

Page 10: ...trim parts on the panelboard using hardware supplied by the manufacturer Take caution that conductors are not pinched between parts when installing the dead front cover and trim All parts should be al...

Page 11: ...e all control power fusing and connections to products which will be damaged in this test This includes all components with control wire fusing Transient Voltage Surge Suppression Surge Protective Dev...

Page 12: ...o maintain the equipment in satisfactory condition Maintain a permanent record of all maintenance activities and testing for future reference The condition of each panelboard should be recorded as a g...

Page 13: ...RE ENERGIZE PANELBOARD After the panelboard has completely dried remove all materials and tools from the equipment Inspect all connections for damage and torque Re install all covers fillers dead fro...

Page 14: ...le 4 Wire Bending Space Requirements for Cable Sizes Bolt Size Torque inch pounds Torque foot pounds Torque Newton Meters 10 30 2 5 3 4 65 5 4 7 3 5 16 130 10 8 14 7 3 8 240 20 27 1 600 50 67 8 Nation...

Page 15: ...11 Pow R Line X Retrofit Panelboards Pow R Line X Retrofit Panelboards MN014011EN January 2020 eatoncanada ca Notes...

Page 16: ...evard Cleveland OH 44122 United States Eaton com 2020 Eaton All Rights Reserved Printed in USA Publication No MN014011EN January 2020 Eaton is a registered trademark All trademarks are property of the...