background image

6

LED Beacon LD15

English

Assessment of functional safety – LD15 DC

This Beacon is intended for use in a safety system 

conforming to the requirements of IEC61508. Sira Test & 

certification Ltd has conducted a Failure Modes Effect and 

Diagnostic Analysis (FMEDA) of the LD15 LED Beacon 

against the requirements of IEC 61508-2 using a Proof 

Test Interval of 8760hrs.
The results are shown below and are based on Route 1

H

.

The Beacon is classed as a Type B device.

Safety function:

‘To provide an intermittent or permanent spherical visual warning light upon demand’.

LD15 DC Beacon

Summary of 

Clauses

2/7.4.2 and 2/7.4.4

LD15 LED Beacon 

Single Mode  

(1oo1)

LD15 LED Beacon 

Redundant Mode 

(1oo2)

Verdict

Architectural 

constraints Safe 

Failure Fraction (SFF)

HFT=0

HFT=1

Type B

60%

60%

SIL 1 

(1oo1) 

SIL 2 

(1oo2)

Random 

hardware 

failures: [h

-1

 ]

λ

DD

λ

DU

0.00E+00

3.44E-08

0.00E+00

3.45E-09

Random 

hardware 

failures: [h

-1

 ]

λ

SD

λ

SU

0.00E+00

5.16E-08

0.00E+00

5.19E-09

Diagnostic coverage 

(DC)

0.00%

0.00%

PFD @ PTI = 8760Hrs, 

MTTR = 8 Hrs

1.51E-04

1.51E-05

SIL 3 

(1oo1)

Average freq. of 

dangerous failure 

(high demand-PFH)[h

-1

]

3.44E-08

3.45E-09

Hardware safety 

integrity compliance

Route 1

H

Systematic safety 

integrity compliance

See report R56A31253B

Systematic Capability

(SC1, SC2, SC3, SC4)

SC2

 (R56A31253B)

Hardware safety 

integrity achieved

Limited to: SIL 1 (1oo1) & SIL 2 (1oo2) due to 

SFF value.

LED BEacon LD15

   

TM334 Issue A

   

October

 2018   www.eaton.com

Summary of Contents for LD15

Page 1: ...LED Beacon LD15 Technical manual...

Page 2: ...AR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT S...

Page 3: ...ch 2 4 0 OPERATION 3 Wiring detail standard unit 3 Wiring detail telephone relay initiate unit 3 General arrangement 4 5 0 MAINTENANCE 4 6 0 SPECIAL CONDITIONS FOR SAFE USE 5 7 0 CERTIFICATION APPROVA...

Page 4: ...iv LED BEacon LD15 TM334 Issue A October 2018 www eaton com...

Page 5: ...rements may also apply VII Cable termination should be in accordance with specification applying to the required application MEDC recommends that all cables and cores should be correctly identified Pl...

Page 6: ...witch Ensure the cover seal is correctly seated in its groove during re assembly There should be a maximum gap of 0 2mm between the faces of the cover and enclosure to ensure O ring compression LED BE...

Page 7: ...nal if requested when ordered When installed as a direct switching device the operating mode can be set by means of a 3 way DIL switch mounted on the underside of the electronics assembly The switch s...

Page 8: ...damage or accident etc then visual inspection is recommended If the unit requires cleaning then only clean exterior with a damp cloth to avoid electro static charge build up If a unit fault should occ...

Page 9: ...bility for use in a zone 1 area G Signifies suitability for use in the presence of gases D Signifies suitability for use in the presence of dust These units also have the following approvals Radiated...

Page 10: ...and 2 7 4 4 LD15 LED Beacon Single Mode 1oo1 LD15 LED Beacon Redundant Mode 1oo2 Verdict Architectural constraints Safe Failure Fraction SFF HFT 0 HFT 1 Type B 60 60 SIL 1 1oo1 SIL 2 1oo2 Random hardw...

Page 11: ...4 4 LD15 LED Beacon Single Mode 1oo1 LD15 LED Beacon Redundant Mode 1oo2 Verdict Architectural constraints Safe Failure Fraction SFF HFT 0 HFT 1 Type B 67 67 SIL 1 1oo1 SIL 2 1oo2 Random hardware fail...

Page 12: ...rongly recommended to test the product at least once a year 3 Selection of this equipment for use in safety functions and the installation configuration overall validation maintenance and repair shall...

Page 13: ...2 Detalhes da fia o unidade de iniciar o rel 12 Disposi o geral 13 5 0 MANUTEN O 13 6 0 CONDI ES ESPECIAIS PARA O USO SEGURO 14 7 0 CERTIFICA O APROVA ES 14 Unidades lECEx 14 Unidades ATEX 14 Essas un...

Page 14: ...ano Tamb m podem ser aplic veis outros requisitos nacionais e ou locais VII A termina o dos cabos deve estar em conformidade com as especifica es referentes aplica o em quest o A MEDC recomenda que to...

Page 15: ...ssegure se de que a veda o da tampa tenha sido corretamente assentada em sua ranhura durante a remontagem Deve existir um espa o m ximo de 0 2 mm entre as superf cies do gabinete e da tampa para garan...

Page 16: ...indicadas por ocasi o da emiss o do pedido Quando for instalado como um dispositivo de ativa o direta o modo de funcionamento pode ser ajustado mediante um interruptor DIL de 3 vias presente na parte...

Page 17: ...te am condi es ambientais anormais ou incomuns decorrentes de danos na instala o ou acidentes etc Se a unidade necessitar de limpeza limpe apenas a parte externa utilizando um pano mido para evitar o...

Page 18: ...equado para uso na presen a de gases D Significa adequado para uso na presen a de poeira Essas unidades tamb m disp em das seguintes aprova es Emiss es radiadas segundo EN 61000 6 4 2007 A1 2011 Desca...

Page 19: ...7 4 2 e 2 7 4 4 Sinalizador luminoso LD15 LED Modo simples 1oo1 Sinalizador luminoso LD15 LED Modo redundante 1oo2 Veredicto Limita es arquitet nicas Fra o de Falha de Seguran a SFF HFT 0 HFT 1 Tipo...

Page 20: ...2 7 4 2 e 2 7 4 4 Sinalizador luminoso LD15 LED Modo simples 1oo1 Sinalizador luminoso LD15 LED Modo redundante 1oo2 Veredicto Limita es arquitet nicas Fra o de Falha de Seguran a SFF HFT 0 HFT 1 Tipo...

Page 21: ...utras aplica es recomenda se fortemente testar o produto pelo menos uma vez ao ano 3 A sele o deste equipamento para uso em fun es de seguran a e a instala o configura o valida o geral manuten o e rep...

Page 22: ...ion contained in this document and to prices are reserved so are errors and omissions Only order confirmations and technical documentation by Eaton is binding Photos and pictures also do not warrant a...

Reviews: