INS #
iLumin Plus
Installation Quick Guide
ILS-0010
ILS-1100
ILS-0020
ILS-2000
ILM-2201
ILM-2200
ILM-2111
ILM-2110
ILM-0040
ILM-0041
ILM-3000
ILM-3001
ILM-4000
ILM-4001
ILL-3300
ILL-3301
ILL-4400
ILL-4401
Applies to Model #s:
Risk of Fire, Electrical Shock, Cuts or other Casualty Hazards- Installation and maintenance of this
product must be performed by a qualified electrician. This product must be installed in accordance
with the applicable installation code by a person familiar with the construction and operation of
the product and hazards involved. For continued protection against shock hazard replace all covers
and guards after field wiring is completed.
Before installing or performing any service, the power MUST be turned OFF at the branch circuit breaker.
According to NEC 240-83(d), if the branch is used as the main switch for a fluorescent lighting circuit,
the circuit breaker should be marked with “SWD”. All installations should be in compliance with the
National Electric Code and all state and local codes.
Risk of Fire and Electric Shock- Make certain power is OFF before starting installation or attempting
any maintenance. Disconnect power at fuse or circuit breaker. iLumin Plus models may contain
circuits from more than one power source.
Risk of Burn- Disconnect power and allow fixture to cool before handling or servicing.
Risk of Personal Injury- Due to sharp edges, handle with care. Always use at least two people when
lifting and mounting heavy or large units
Failure to comply with these instructions may result in serious injury (including death) and property
damage.
WARNING
DISCLAIMER OF LIABILITY: Eaton assumes no liability for damages or losses of any kind that may arise from the
improper, careless, or negligent installation, handling or use of this product.
IMPORTANT:
Read carefully before installing fixture. Retain for future reference.
NOTICE:
Fixture may become damaged and/or unstable if not installed properly.
Note:
Specifications and dimensions subject to change without notice.
ATTENTION Receiving Department:
Note actual fixture description of any shortage or noticeable damage on
delivery receipt. File claim for common carrier (LTL) directly with carrier. Claims for concealed damage must be
filed within 15 days of delivery. All damaged material, complete with original packing must be retained.
iLumin Plus
NOTICE:
If a room is wired for two circuits using two separate hot leads, it is very important to connect only one
circuit per relay. Both circuits must be fed from the same phase.
NOTICE:
Ensure that all modules are firmly seated on the DIN rails before beginning field wiring.
NOTICE:
The high voltage supply should be fed to the cabinet via an external isolation breaker with sufficient
capacity for the planned installation.
NOTICE:
Ensure that the supply is fully isolated at an external breaker before opening doors. Test that power has
been removed before starting to handle conductors.
NOTICE:
Ensure that high voltage and low voltage wiring remains separate.
NOTICE:
All new wiring must be fully verified before applying power.
NOTICE:
Designed for indoor installation and use only. Dry location rated.