8
GridAdvisor™ Series II smart sensor installation instructions
IL915001EN
April 2019
Eaton.com
Installation procedures
Figure 7. Smart Sensor LED designations.
Installation of smart sensor – overhead
application
Install the sensor a minimum of ten (10) feet away from any
structure on the conductor, including any poles.
1.
Arm the FCI clamping mechanism by carefully grasping
both clamping arms, pulling them apart until the trigger
mechanism drops into place. Stops have been built into
the clamping arms such that they can only be opened to
the point where the trigger will latch (Figure 5 on page 7).
2.
For applications where the cable diameter is less than
1 inch, leave the clamp pads attached to the clamp arms.
On installations where the cable diameter exceeds
1 inch, remove the pads that are attached to each
clamping arm. Removing the pads will allow the clamping
mechanism to properly attach to larger diameter cables
(Figure 4 on page 7, Figure 6 on page 7).
3.
Attach the sensor to a hotstick using the pulling eye.
4.
Push the sensor onto the cable conductor. Ensure that
the CT is around the conductor and good contact is made
between the ends of the CT. The triggering mechanism
will release the clamping arms from the latched position,
to securely attach the device to the cable.
Sensor display operation
The GridAdvisor Series II smart sensor has two multicolor
light emitting diodes (LEDs) used for annunciating functional
tasks and the status of the smart sensor. Each LED will be
referred to as Source and Load LED in the context of the
labels found on sensor per Figure 7.
Note:
The fault LEDs can be disabled in the sensor
configuration.
Device activation
The LEDs provided on the GridAdvisor Series II smart sensor
provide annunciation during the activation process of the
sensor onto the cellular or Bluetooth SCADA network at time
the battery is installed; see Table 2 and Table 3.
LED installation indication
The LEDs provided on the GridAdvisor Series II smart sensor
provide annunciation during the installation of device to verify
proper load current is present.
Programming sensor
Refer to the
GridAdvisor Series II Smart Sensor ProView NXG
software programming manual (MN915003EN)
for
instructions on connecting to the sensor with the Bluetooth
®
module and/or programming device with ProView NXG
software.
Load LED
Source LED
Table 1. GridAdvisor Series II Smart Sensor LEDs Provided
Sequence Steps
(in order)
Source LED
Load LED
Current present
below 10 Amps
RED Moving Bar
Sequence for Direction
RED Moving Bar
Sequence for Direction
Current present
below 50 Amps
AMBER Moving Bar
Sequence for Direction
AMBER Moving Bar
Sequence for Direction
Current present
above 50 Amps
Green Moving Bar
Sequence for Direction
Green Moving Bar
Sequence for Direction
Table 2. LED annunciation during cellular activation
Sequence steps (in order)
Source LED
Load LED
Initialization
A single pulse green LED.
Bluetooth
®
and cellular modules are unavailable and device
will not respond to reed switch.
A single pulse green LED.
Bluetooth
®
and cellular modules are unavailable and device
will not respond to reed switch.
Initialization Failure
LED will blink red continuously.
Contact Factory for assistance after attempting to force an
OTASP or inserting a new SIM card.
LED will blink red continuously.
Contact Factory for assistance after attempting to force an
OTASP or inserting a new SIM card.
Initialization Complete
A double pulse green LED.
Bluetooth
®
module is available for programming sensor by
reed switching device.
A double pulse green LED.
Bluetooth
®
module is available for programming sensor by
reed switching device.
Successful Cellular Activation
Three yellow LED flashes in succession ten times.
Indicates sensor has received IP address from network.
Three yellow LED flashes in succession ten times.
Indicates sensor has received IP address from network.
Failed Cellular Activation
Three (3) red LED flashes in succession ten (10) times.
Contact utility network administrator to verify proper
configuration of cellular account.
Three (3) red LED flashes in succession ten (10) times.
Contact utility network administrator to verify proper
configuration of cellular account.