Digital Switch Wiring

LittKttptr® 8

 

Digital Switch Wiring

Each LiteKeeper 8® unit is capable of supporting the 

Greengate Digital Switch (GDS) station. The GDS do not 

wire directly to the LiteKeeper 8® logic board, but are wired 

using a CAN Bus network that connects to the LiteKeeper 

8® through a gateway called the GDS-I. GDS stations are 

wired using the Eaton’s Cooper Controls LCCP or LCCNP 

cable, or Belden 1502P or 1502R equivallents. 
For best network performance, one of the suggested 

cables should be used. If the specified cable is not 

used and communications problems occur that require 

troubleshooting assistance, additional charges for support 

may be assessed.
Digital Switch devices should be networked together in a 

daisy chain configuration. No T-Taps/Stars should be used. 

The GDS-I device should reside somewhere within the 

daisy chain switch network. Total daisy chain network length 

should not exceed 1000 feet.
The following instructions describe the GDS-I device 

connection to the LiteKeeper 8®. Please refer to the 

Greengate Digital Switch installation instructions for 

information on wiring the Digital Switch Network to the 

Digital Switch Gateway.

1.  Mount the GDS-I next to the LiteKeeper®-8 panel. 

A six foot phone style cable has been provided for 

connection to the LiteKeeper-8® panel.

2.  Run a length of the Digital Switch LC or Belden cabling 

from the GDS-I location to the low voltage section of 

the LiteKeeper 8®.

3.  Connect the RED wire in the cable to the +V terminal 

on the back of the GDS-I and to the LiteKeeper 8® at 

one of the switch input +24 VDC terminals.

4.  Connect the BLACK wire in the cable to the GND 

terminal on the back of the GDS-I and to the LiteKeeper 

8® remote power connector GND terminal.

5.  Tape back or cap the blue and white wires and shield 

wire for the cable. They will not be used for connection 

between the GDS-I and lighting controller.

6.  Locate the 6 foot phone style cable included in the 

GDS-I box. Run this from the GDS-I into the low voltage 

section of the LiteKeeper 8® enclosure plugging the 

end with 9 pin head into the GDS-I. Plug the end the 

RJ11 phone style plug into the LiteKeeper 8®.

7.  It is recommended that power be removed from the 

logic board when doing initial switch input wiring.

GDS-I Wiring

Applying Power

1.  Once the wiring is complete, make certain that the 

enclosure is clean of any wire clippings and that no 

fragments are lodged in the relay circuit boards.

2.  Ensure that there are no loose wires or exposed wires 

that could short to other wires or components.

3.  Power-up the unit from the circuit breaker.
4.  Once power is applied to the unit, lighting loads may be 

operated via the ALL ON/ AUTO/ ALL OFF switch  

as necessary.

Manually Controlling Relays

The relays in the enclosure may be controlled before the 

logic board is programmed by using the on-board, ALL OFF, 

AUTO, ALL ON switch. In the ALL ON position the relay 

coils will be energized. In the ALL OFF position, the relay 

coils will be de-energized. The middle, AUTO, position allows 

the relays to be controlled by the individual relay switches or 

from the logic controller.

System Reset and Clear Commands

Under certain circumstances, you may want to reset the 

LiteKeeper 8®. There are two different types of reset 

commands available in the LiteKeeper 8® system: a soft 

reset command and a clear reset command.

Panel must be Set 

to Communicate to 

the GDS Switch BUS 

Through Menu Option 8

Communication 

Cable

Red Wire From 

GDS-1 +24 to 

LK +24

Black Wire From GDS-1 

0V to LK GND

Cabling is Cooper LC Cable, 

Belden 1502R, or Belden 1502P

GDS-I

Summary of Contents for Greengate LiteKeeper 8

Page 1: ...esult in severe injury or death and or damage to the equipment 8 Document all wiring that is terminated to the relays so that the lighting control equipment can be properly configured and programmed f...

Page 2: ...Relay Card Notes 1 The Standard Relay Card is rated for single pole load use only Connection of 2 pole circuits loads to the Standard Relay Card will void the equipment warranty and may result in seve...

Page 3: ...urrent available relay module types include a Two Pole Relay Module TPRM Normally Open the Latching Relay Module LRM and the Standard Relay Module SRM K1 MOV1 TB1 U1 RP1 R4 R4 RP1 U1 TB1 MOV1 K1 MOV1...

Page 4: ...tate 6 There is a manual switch on each relay that indicates relay status and allows for a temporary override of the lighting load If the switch is moved towards the center of the Modular Relay Card t...

Page 5: ...ement of the relays The Two Pole Relay Card will hold eight 208V two pole relays one in each mounting clip The 480V Two Pole Relay Card uses two mounting clips thus only four relays will fit per card...

Page 6: ...board when doing initial switch input wiring Contact Input Switch Wiring This section describes the wiring for dry contact closure devices There are eight switch input wiring terminals on the left sid...

Page 7: ...iteKeeper 8 remote power connector GND terminal 5 Tape back or cap the blue and white wires and shield wire for the cable They will not be used for connection between the GDS I and lighting controller...

Page 8: ...it is now cleared to factory default programming Programming the LiteKeeper 8 The LiteKeeper 8 is programmed either through the keypad onboard interface or through the optional Keeper Enterprise Softw...

Page 9: ...nt le processus de c blage Montage l int rieur du bo tier 1 Choisissez un emplacement sec qui convient au panneau lectrique 2 Montez le panneau sur une surface stable l aide des trous pr perc s 3 Bran...

Page 10: ...de d rivation de 120 ou 277 V 20 A maximum hors tension au bornier du relais 2 Branchez le c blage de charge au bornier de sortie otte N Les borniers ne sont pas sensibles la polarit bien qu il soit...

Page 11: ...anchez un disjoncteur de d rivation de 120 ou 277 V 20 A maximum hors tension au bornier du relais 2 Branchez le c blage de charge au bornier de sortie otte N Les borniers ne sont pas sensibles la pol...

Page 12: ...s bipolaires occupent les deux fentes relais dans le bo tier 4 Les relais bipolaires sont normalement en configuration ouverte 5 Un voyant DEL s allume lorsque le relais est contr l par le panneau de...

Page 13: ...ogique Veuillez v rifier qu il n y a pas de court circuit au c ble de mise la terre c a avant de proc der au branchement des dispositifs d entr e Sans gard au type d entr e les remarques suivantes s a...

Page 14: ...e c ble sp cifi n est pas utilis et si vous prouvez des probl mes de communications qui exigent de l aide du service de d pannage des frais suppl mentaires peuvent tre applicables Les commutateurs num...

Page 15: ...alisation une r initialisation logicielle et une r initialisation de suppression La commande de r initialisation logicielle La commande de r initialisation logicielle red marre le microprocesseur Il n...

Page 16: ...5 8 LIGHTING CONTROL 12 OO O1 O1 0 8 2 4 7 OUTPUTS RELAY 6 5 4 3 8 7 1 6 B 9 C 3 A OFF 24 H 1 ON C OFF 24 H 1 ON C OFF 24 H 1 ON C OFF 24 H 1 ON C OFF 24 H 1 ON C OFF 24 H 1 ON C Sch ma de r f rence...

Page 17: ...gica para proteger los componentes contra posibles cortocircuitos durante el proceso de cableado Montaje en el recinto 1 Elija una ubicaci n seca que sea conveniente para el panel del disyuntor 2 Mont...

Page 18: ...os y 20 amperios como m ximo desconecte el disyuntor en el bloque de terminales del rel 2 Conecte los cables de carga en el bloque de terminales de salida otte N Los bloques de terminales no son sensi...

Page 19: ...l nea de un circuito normal Para realizar el cableado del rel en el circuito de control 1 Conecte un cable de 120 o 277 voltios y 20 amperios como m ximo desconecte el disyuntor en el bloque de termin...

Page 20: ...20 amperios como m ximo 2 Los bloques de terminales del rel tienen un l mite m ximo de cable 6 AWG 3 Los rel s de dos polos ocupan dos ranuras del rel en el recinto 4 Los rel s de dos poleas vienen en...

Page 21: ...lizar todo el cableado de entrada antes de aplicar energ a a la tarjeta l gica Verifique que no existan cortocircuitos a la conexi n a tierra de CA antes de conectar los dispositivos de entrada Sin im...

Page 22: ...comunicaci n que requieran asistencia mediante el proceso de resoluci n de problemas podr haber cargos adicionales por el servicio de soporte Los interruptores digitales se deben conectar entre s con...

Page 23: ...es de reconfiguraci n disponibles en el sistema LiteKeeper 8 un control de reconfiguraci n simple y uno de eliminaci n Control de reconfiguraci n simple El control de reconfiguraci n simple reinicia e...

Page 24: ...OFF H 1 ON C 0 D 5 8 LIGHTING CONTROL 12 OO O1 O1 0 8 2 4 7 OUTPUTS RELAY 6 5 4 3 8 7 1 6 B 9 C 3 A OFF 24 H 1 ON C OFF 24 H 1 ON C OFF 24 H 1 ON C OFF 24 H 1 ON C OFF 24 H 1 ON C OFF 24 H 1 ON C Dia...

Reviews: