2

Wiring the Transformer

LittKttptr® 8

 

Wiring the Transformer

The transformer is multi-tapped and voltages are  

color-coded. The transformer is available in 120/277 

VAC and 120/347 VAC models. It is recommended that 

a dedicated branch circuit with circuit protection be 

provided for the transformer. 

1.  Connect neutral wire to the wire with the appropriate 

color-coding for the voltage being used: White/

Black=120 VAC, White/Orange=277 VAC, Brown=347 

VAC.

2.  Connect the solid black wire to the dedicated branch 

circuit that is powering the transformer.

Transformer Wiring Information

Connecting Relay Loads

The relay cards will be pre-mounted by the manufacturer 

in the enclosure per the order specifications. There are 

currently four available relay types for the enclosure. This 

includes the Standard Relay Card, the Modular Relay Card, 

the Latching Relay Card and the Two Pole Relay Card. If a 

Modular Relay Card or Two Pole Relay Card is ordered, a 

deeper enclosure will be provided to allow for clearance 

of the transformer with the larger relay types. Refer to the 

specific section for your relay card type that you are wiring. 

For all relay types:
1.  Verify that all wire cuttings are removed from  

the enclosure.

2.  Take the protective shrink-wrap off of the relay cards 

AFTER the wire cuttings are removed from the 

enclosure.

3.  Test branch circuits for short circuits prior to landing 

wiring on relays.

otte:

N

Neutrals terminate within the adjoining lighting panel.

Standard Relay Card Notes

1.  The Standard Relay Card is rated for single-pole load 

use only. Connection of 2 pole circuits/loads to the 

Standard Relay Card will void the equipment warranty 

and may result in severe injury or death, and/or damage 

to the equipment.

2.  Relay ratings are 120 or 277 volt, 20 amp maximum.
3.  Relay terminal blocks have a maximum limit of  

10AWG wire.

Standard Relay Card Wiring

The standard relay is a simple contact closure, breaking the 

line and load wires of a normal circuit. To wire the relay into 

the control circuit:

1.  Connect a 120 or 277 volt, 20 amp max, de-energized 

branch circuit breaker to the relay terminal block.

2.  Connect the load wiring to the output terminal block.

otte:

N

Terminal blocks are not polarity sensitive although it 

is recommended that line and load be brought into 

terminal blocks in the same manner for consistency.

3.  Tighten down relay terminal screws. Manufacturer’s 

recommended torque rating is 7 lbs-in.  

(0.59 lbs-foot) (0.8 Nm).

4.  Document relay to circuit information for  

future reference.

 

TB8

TB6

TB4

TB2

Standard Relay Card Wiring

Latching Relay Card Notes

1.  The Latching Relay Card is rated for single-pole load use 

only. Connection of 2 pole circuits/loads to the Latching 

Relay Card will void the equipment warranty and may 

result in severe injury or death, and/or damage to  

the equipment.

2.  Relay ratings are 120/277/347 volt, 20 amp maximum.
3.  Relay terminal blocks have a maximum limit of  

6AWG wire.

System Power Supply

Line Voltage = Black
Neutral: 

120VAC = white/black 

277VAC = white/orange 

347VAC = brown
Ground = green

Relay Wiring 

Wire: 10 AWG Max. 

Relay Rating: 20amps, 277V

54-015030
54-015030

From Branch Circuit

To Lighting Load

Summary of Contents for Greengate LiteKeeper 8

Page 1: ...esult in severe injury or death and or damage to the equipment 8 Document all wiring that is terminated to the relays so that the lighting control equipment can be properly configured and programmed f...

Page 2: ...Relay Card Notes 1 The Standard Relay Card is rated for single pole load use only Connection of 2 pole circuits loads to the Standard Relay Card will void the equipment warranty and may result in seve...

Page 3: ...urrent available relay module types include a Two Pole Relay Module TPRM Normally Open the Latching Relay Module LRM and the Standard Relay Module SRM K1 MOV1 TB1 U1 RP1 R4 R4 RP1 U1 TB1 MOV1 K1 MOV1...

Page 4: ...tate 6 There is a manual switch on each relay that indicates relay status and allows for a temporary override of the lighting load If the switch is moved towards the center of the Modular Relay Card t...

Page 5: ...ement of the relays The Two Pole Relay Card will hold eight 208V two pole relays one in each mounting clip The 480V Two Pole Relay Card uses two mounting clips thus only four relays will fit per card...

Page 6: ...board when doing initial switch input wiring Contact Input Switch Wiring This section describes the wiring for dry contact closure devices There are eight switch input wiring terminals on the left sid...

Page 7: ...iteKeeper 8 remote power connector GND terminal 5 Tape back or cap the blue and white wires and shield wire for the cable They will not be used for connection between the GDS I and lighting controller...

Page 8: ...it is now cleared to factory default programming Programming the LiteKeeper 8 The LiteKeeper 8 is programmed either through the keypad onboard interface or through the optional Keeper Enterprise Softw...

Page 9: ...nt le processus de c blage Montage l int rieur du bo tier 1 Choisissez un emplacement sec qui convient au panneau lectrique 2 Montez le panneau sur une surface stable l aide des trous pr perc s 3 Bran...

Page 10: ...de d rivation de 120 ou 277 V 20 A maximum hors tension au bornier du relais 2 Branchez le c blage de charge au bornier de sortie otte N Les borniers ne sont pas sensibles la polarit bien qu il soit...

Page 11: ...anchez un disjoncteur de d rivation de 120 ou 277 V 20 A maximum hors tension au bornier du relais 2 Branchez le c blage de charge au bornier de sortie otte N Les borniers ne sont pas sensibles la pol...

Page 12: ...s bipolaires occupent les deux fentes relais dans le bo tier 4 Les relais bipolaires sont normalement en configuration ouverte 5 Un voyant DEL s allume lorsque le relais est contr l par le panneau de...

Page 13: ...ogique Veuillez v rifier qu il n y a pas de court circuit au c ble de mise la terre c a avant de proc der au branchement des dispositifs d entr e Sans gard au type d entr e les remarques suivantes s a...

Page 14: ...e c ble sp cifi n est pas utilis et si vous prouvez des probl mes de communications qui exigent de l aide du service de d pannage des frais suppl mentaires peuvent tre applicables Les commutateurs num...

Page 15: ...alisation une r initialisation logicielle et une r initialisation de suppression La commande de r initialisation logicielle La commande de r initialisation logicielle red marre le microprocesseur Il n...

Page 16: ...5 8 LIGHTING CONTROL 12 OO O1 O1 0 8 2 4 7 OUTPUTS RELAY 6 5 4 3 8 7 1 6 B 9 C 3 A OFF 24 H 1 ON C OFF 24 H 1 ON C OFF 24 H 1 ON C OFF 24 H 1 ON C OFF 24 H 1 ON C OFF 24 H 1 ON C Sch ma de r f rence...

Page 17: ...gica para proteger los componentes contra posibles cortocircuitos durante el proceso de cableado Montaje en el recinto 1 Elija una ubicaci n seca que sea conveniente para el panel del disyuntor 2 Mont...

Page 18: ...os y 20 amperios como m ximo desconecte el disyuntor en el bloque de terminales del rel 2 Conecte los cables de carga en el bloque de terminales de salida otte N Los bloques de terminales no son sensi...

Page 19: ...l nea de un circuito normal Para realizar el cableado del rel en el circuito de control 1 Conecte un cable de 120 o 277 voltios y 20 amperios como m ximo desconecte el disyuntor en el bloque de termin...

Page 20: ...20 amperios como m ximo 2 Los bloques de terminales del rel tienen un l mite m ximo de cable 6 AWG 3 Los rel s de dos polos ocupan dos ranuras del rel en el recinto 4 Los rel s de dos poleas vienen en...

Page 21: ...lizar todo el cableado de entrada antes de aplicar energ a a la tarjeta l gica Verifique que no existan cortocircuitos a la conexi n a tierra de CA antes de conectar los dispositivos de entrada Sin im...

Page 22: ...comunicaci n que requieran asistencia mediante el proceso de resoluci n de problemas podr haber cargos adicionales por el servicio de soporte Los interruptores digitales se deben conectar entre s con...

Page 23: ...es de reconfiguraci n disponibles en el sistema LiteKeeper 8 un control de reconfiguraci n simple y uno de eliminaci n Control de reconfiguraci n simple El control de reconfiguraci n simple reinicia e...

Page 24: ...OFF H 1 ON C 0 D 5 8 LIGHTING CONTROL 12 OO O1 O1 0 8 2 4 7 OUTPUTS RELAY 6 5 4 3 8 7 1 6 B 9 C 3 A OFF 24 H 1 ON C OFF 24 H 1 ON C OFF 24 H 1 ON C OFF 24 H 1 ON C OFF 24 H 1 ON C OFF 24 H 1 ON C Dia...

Reviews: