Connecting Relay Loads

LittKttptr® 8

 

Standard Relay Module Wiring

The standard relay is a simple contact closure, breaking the 

line and load wires of a normal circuit. To wire the relay into 

the control circuit:
1.  Connect a 120 or 277 volt, 20 amp max, de-energized 

branch circuit breaker to the relay terminal block.

2.  Connect the load wiring to the output terminal block.

otte:

N

Terminal blocks are not polarity sensitive although it 

is recommended that line and load be brought into 

terminal blocks in the same manner for consistency.

3.  Tighten down relay terminal screws. Manufacturer’s 

recommended torque rating is 7 lbs-in.  

(0.59 lbs-foot) (0.8 Nm).

4.  Document relay to circuit information for  

future reference.

Latching Relay Module

1.  The Latching Relay Module is rated for single-pole 

load use only. Connection of 2 pole circuits/loads to 

the Latching Relay Module will void the equipment 

warranty and may result in severe injury or death,  

and/or damage to the equipment.

2.  Relay ratings are 120/ 277/347 volt, 20 amp maximum.
3.  Relay terminal blocks have a maximum limit of  

6AWG wire.

4.  During initial power-up, the relay on the Latching Relay 

Module will remain in its current latched state for a 

period of 30 seconds. After 30 seconds, the relay will 

assume its programmed state.

5.  During a power outage, the LRM relay will remain in 

the state it was in prior to the power outage. Once 

power returns, the relay will stay in its state for  

30 seconds then assume its programmed state.

6.  There is a manual switch on each relay that indicates 

relay status and allows for a temporary override of the 

lighting load. If the switch is moved towards the center 

of the Modular Relay Card, the relay is ON. If the 

relay switch is moved towards the outside of the relay 

card, the relay is OFF. If this switch is used to override 

lighting, the relay will stay in the overridden state until 

the next command to that relay is given by the  

logic board.

C

PCI 2003

R4

RP1

U1

TB1

MOV1

K1

J1

Latching Relay Module

Latching Relay Module Wiring

The latching relay is a simple closure, breaking the line and 

load wires of a normal circuit. To wire the relay into the 

control circuit:
1.  Connect a 120, 277 or 347 volt, 20 amp maximum, 

de-energized branch circuit breaker to the relay  

terminal block.

2.  Connect the load wiring to the output terminal block.

otte:

N

Terminal blocks are not polarity sensitive although it 

is recommended that line and load be brought into 

terminal blocks in the same manner for consistency.

3.  Tighten down relay terminal screws. Manufacturer’s 

recommended torque rating is 18lb-in.  

(1.475 foot-lbs) (2.0 Nm).

4.  Document relay to circuit information for  

future reference.

Two Pole Relay Module

1.  Two Pole Relay ratings are 208/240/480 volt,  

20 amp maximum.

2.  Relay terminal blocks have a maximum limit of  

6 AWG wire.

3.  Two Pole Relays take up two relay slots in the enclosure.
4.  Two Pole Relays come in a normally open configuration.
5.  There is an LED that will light up when the relay is 

commanded to be in the closed position.

Relay Status 

Indicator LED

Wiring Terminal 

Block

Relay Slot Pin Connector: 

Please note relay number 

location for programming 

purposes.

Summary of Contents for Greengate LiteKeeper 8

Page 1: ...esult in severe injury or death and or damage to the equipment 8 Document all wiring that is terminated to the relays so that the lighting control equipment can be properly configured and programmed f...

Page 2: ...Relay Card Notes 1 The Standard Relay Card is rated for single pole load use only Connection of 2 pole circuits loads to the Standard Relay Card will void the equipment warranty and may result in seve...

Page 3: ...urrent available relay module types include a Two Pole Relay Module TPRM Normally Open the Latching Relay Module LRM and the Standard Relay Module SRM K1 MOV1 TB1 U1 RP1 R4 R4 RP1 U1 TB1 MOV1 K1 MOV1...

Page 4: ...tate 6 There is a manual switch on each relay that indicates relay status and allows for a temporary override of the lighting load If the switch is moved towards the center of the Modular Relay Card t...

Page 5: ...ement of the relays The Two Pole Relay Card will hold eight 208V two pole relays one in each mounting clip The 480V Two Pole Relay Card uses two mounting clips thus only four relays will fit per card...

Page 6: ...board when doing initial switch input wiring Contact Input Switch Wiring This section describes the wiring for dry contact closure devices There are eight switch input wiring terminals on the left sid...

Page 7: ...iteKeeper 8 remote power connector GND terminal 5 Tape back or cap the blue and white wires and shield wire for the cable They will not be used for connection between the GDS I and lighting controller...

Page 8: ...it is now cleared to factory default programming Programming the LiteKeeper 8 The LiteKeeper 8 is programmed either through the keypad onboard interface or through the optional Keeper Enterprise Softw...

Page 9: ...nt le processus de c blage Montage l int rieur du bo tier 1 Choisissez un emplacement sec qui convient au panneau lectrique 2 Montez le panneau sur une surface stable l aide des trous pr perc s 3 Bran...

Page 10: ...de d rivation de 120 ou 277 V 20 A maximum hors tension au bornier du relais 2 Branchez le c blage de charge au bornier de sortie otte N Les borniers ne sont pas sensibles la polarit bien qu il soit...

Page 11: ...anchez un disjoncteur de d rivation de 120 ou 277 V 20 A maximum hors tension au bornier du relais 2 Branchez le c blage de charge au bornier de sortie otte N Les borniers ne sont pas sensibles la pol...

Page 12: ...s bipolaires occupent les deux fentes relais dans le bo tier 4 Les relais bipolaires sont normalement en configuration ouverte 5 Un voyant DEL s allume lorsque le relais est contr l par le panneau de...

Page 13: ...ogique Veuillez v rifier qu il n y a pas de court circuit au c ble de mise la terre c a avant de proc der au branchement des dispositifs d entr e Sans gard au type d entr e les remarques suivantes s a...

Page 14: ...e c ble sp cifi n est pas utilis et si vous prouvez des probl mes de communications qui exigent de l aide du service de d pannage des frais suppl mentaires peuvent tre applicables Les commutateurs num...

Page 15: ...alisation une r initialisation logicielle et une r initialisation de suppression La commande de r initialisation logicielle La commande de r initialisation logicielle red marre le microprocesseur Il n...

Page 16: ...5 8 LIGHTING CONTROL 12 OO O1 O1 0 8 2 4 7 OUTPUTS RELAY 6 5 4 3 8 7 1 6 B 9 C 3 A OFF 24 H 1 ON C OFF 24 H 1 ON C OFF 24 H 1 ON C OFF 24 H 1 ON C OFF 24 H 1 ON C OFF 24 H 1 ON C Sch ma de r f rence...

Page 17: ...gica para proteger los componentes contra posibles cortocircuitos durante el proceso de cableado Montaje en el recinto 1 Elija una ubicaci n seca que sea conveniente para el panel del disyuntor 2 Mont...

Page 18: ...os y 20 amperios como m ximo desconecte el disyuntor en el bloque de terminales del rel 2 Conecte los cables de carga en el bloque de terminales de salida otte N Los bloques de terminales no son sensi...

Page 19: ...l nea de un circuito normal Para realizar el cableado del rel en el circuito de control 1 Conecte un cable de 120 o 277 voltios y 20 amperios como m ximo desconecte el disyuntor en el bloque de termin...

Page 20: ...20 amperios como m ximo 2 Los bloques de terminales del rel tienen un l mite m ximo de cable 6 AWG 3 Los rel s de dos polos ocupan dos ranuras del rel en el recinto 4 Los rel s de dos poleas vienen en...

Page 21: ...lizar todo el cableado de entrada antes de aplicar energ a a la tarjeta l gica Verifique que no existan cortocircuitos a la conexi n a tierra de CA antes de conectar los dispositivos de entrada Sin im...

Page 22: ...comunicaci n que requieran asistencia mediante el proceso de resoluci n de problemas podr haber cargos adicionales por el servicio de soporte Los interruptores digitales se deben conectar entre s con...

Page 23: ...es de reconfiguraci n disponibles en el sistema LiteKeeper 8 un control de reconfiguraci n simple y uno de eliminaci n Control de reconfiguraci n simple El control de reconfiguraci n simple reinicia e...

Page 24: ...OFF H 1 ON C 0 D 5 8 LIGHTING CONTROL 12 OO O1 O1 0 8 2 4 7 OUTPUTS RELAY 6 5 4 3 8 7 1 6 B 9 C 3 A OFF 24 H 1 ON C OFF 24 H 1 ON C OFF 24 H 1 ON C OFF 24 H 1 ON C OFF 24 H 1 ON C OFF 24 H 1 ON C Dia...

Reviews: