19
Programming
EPCT FirE sEriEs FirE PumP ConTrollEr
MN124016EN August 2019 www.eaton.com
Table 4
statistics
Total Powered Time
Total Motor Run Time
Last Motor Run Time
Calls to Start
Motor Starts
Maximum Starting Current A
Maximum Starting Current B
Maximum Starting Current C
Maximum Run Current A
Maximum Run Current B
Maximum Run Current C
Last LR Voltage A
Last LR Voltage B
Last LR Voltage C
Last LR Current A
Last LR Current B
Last LR Current C
Minimum System Pressure
Maximum System Pressure
Minimum S1 Voltage AB
Minimum S1 Voltage BC
Minimum S1 Voltage CA
Maximum S1 Voltage AB
Maximum S1 Voltage BC
Maximum S1 Voltage CA
Minimum S2 Voltage AB
Minimum S2 voltage BC
Minimum S2 Voltage CA
Maximum S2 Voltage AB
Maximum S2 Voltage BC
Maximum S2 Voltage CA
Minimum S1 Frequency
Maximum S1 Frequency
Minimum S2 Frequency
Maximum S2 Frequency
Last System Startup
Last Motor Start
Last Low Pressure Start
Last Locked Rotor Trip
Last S1 Phase Failure
Last S2 Phase Failure
Last S1 Phase Reversal
Last S2 Phase Reversal
Last S1 Overvoltage
Last S1 Under voltage
Last S2 Under voltage
Last S2 Overvoltage
Last S1 Under frequency
Last S2 Over frequency
Last S1 Under frequency
statistics
Last S2 Over frequency
Last Generator Start
Last Generator Stop
Last Transfer to S1
Last Transfer to S2
Last S2 Disconnect
5.10.3 Controller diagnostics
The EPCT controller will display a number of diagnostic
values that can be viewed on the main display or saved onto
a USB storage device.
The main diagnostic page will display the firmware version,
voltages, amperages, and transducer information.
The input status page will display the state of each input
contact. Pressing the input buttons, the controller will
override the state of that input for one minute. If the button
is depressed a second time, the input will resume normal
operation. If the screen is exited, the input will resume
normal operation.
The output status page will display the state of each
output relay on the I/O board or ATS board (if equipped),
solenoid valve, and alarm. Pressing the output buttons,
the controller will override the state of that output for
one minute. If the button is depressed a second time,
the output will resume normal operation. If the screen is
exited, the input will resume normal operation. The horn
can be silenced for a period of ten (10) minutes that will
not reset by leaving the screen.
The controller is equipped with on board communication
diagnostics. The last page in the Controller Diagnostic menu
allows the user to test the transfer and receive functions of
the display board. The screen will provide a prompt that the
test successfully passed or failed.
5.10.4 Startup information
The EPCT controller will log all tasks that are completed/
programmed through the STARTUP tab in a separate file.
This allows the user to specifically identify all completed
activities during the startup/commissioning process.
5.10.5 Save to USB
Data can be saved to an external USB memory device via
the USB port located on the controller door. When a valid
USB device is inserted, the button text will change from
“INSERT USB” to “PRESS TO SAVE”. Once the data has
been saved to the USB, the display will prompt the user to
remove the USB device.
Message history, statistics, diagnostics, configuration,
and the startup file will be saved onto the USB in comma
separated value (CSV) format.