6
Operation
EPCT FirE sEriEs FirE PumP ConTrollEr
MN124016EN August 2019 www.eaton.com
4.0 Operation
4.1 General
This section specifically describes the operation and
functional use of the EPCT controller. The practical use
of and operation within each category will be discussed.
In this section, it is assumed that prior sections of this
manual were reviewed, and that the operator has a basic
understanding of the hardware
4.2 Welcome screen
When the EPCT controller is first energized, the Welcome
Screen will be displayed (refer to 4.2.1.1.
While on the Welcome Screen, the controller will not start
the pump regardless of any present starting conditions; this
screen will show all present starting conditions. The screen
comes equipped with a five (5) minute countdown timer
where, when it expires, the controller will exit the Welcome
Screen to the Home tab and resume normal operation.
The three (3) buttons on this screen are CLOSE AND
DISABLE WELCOME SCREEN, CLOSE WELCOME
SCREEN AND RUN ON NEXT STARTUP, and QUICK SETUP.
The operation is as follows:
•
Close and Disable Welcome Screen will bring the
controller to the Home tab and, upon re-energizing the
controller, the controller will not show the Welcome
Screen.
•
Close Welcome Screen and Run on Next Startup will
bring the user to the Home tab but, upon re-energizing
the controller, the controller will show the Welcome
Screen.
•
Quick Setup bring the user to directly to the Quick
Setup menu where the Time, Date, Start Pressure, Stop
Pressure, Enable or Disable Automatic Shutdown, and
Minimum Run Timer can be programmed. By accepting
or disregarding the programming from this menu, the
user will be brought back to the Welcome Screen.
4.2.1 Welcome screen and home screen graphics
4.2.1.1. Welcome screen