Battery specification
Battery type
VRLA, 12 VDC
Battery quantity
32 blocks, 192 cells per battery string
Note! Do not connect battery strings
with different battery quantity and
voltage in parallel!
Battery voltage
384 V (32 blocks)
5.3
Environmental specifications
Recommended storage temperature
range
From -25 °C to +25 °C in the protective
package
Ambient operating temperature range
From 0 °C to +40 °C
Recommended operating temperature
range
From +20 °C to +25 °C
Relative humidity range
5 to 95%, no condensation allowed