Installation
10/10 MN05003003Z-EN
24
Connecting outputs
The relay or transistor outputs are used to switch loads such as
fluorescent tubes, filament bulbs, contactors, relays or motors.
Check the technical thresholds and output data before installing
such devices (
Connect relay outputs
EC4P-221/222-MR…, EASY6..-DC-RE
Unlike the inputs, you can connect the EC4P-221/222-MR…,
EASY6..-..RE relay outputs to different phase conductors.
Figure 24: Relay outputs EC4P-221/222-MR…
+ 24 V
H
0 V
H
, N
F
8 A/B 16
L1, L2, L3 (115/230 V
h
)
25 000
R
L
24 V
H
8 A
115 V
h
8 A
230 V
h
8 A
2 A
2 A
2 A
1000 W
10
x
58 W
1 2
2
2
2
2
2
1
1
1
1
1
10 000 000
Q6
Q5
Q4
Q3
Q2
Q1
i
Caution!
Do not exceed the maximum voltage of 250 V AC on a
relay contact. If the voltage exceeds this threshold,
flashover may occur at the contact, resulting in damage to
the device or a connected load.