2 Setup
Inputs
Table 1:
Type and number of inputs
Inputs I7, I8, I11, I12 can also be used as analog inputs. They are
selected in the user program by means of the appropriate syntax
used in the PLC configurator.
When programming the inputs as digital inputs in the user
program, the input voltage of 8 V forms the limit value for the
TRUE/FALSE signals.
Technical data:
Inputs I1, I2, I3, I4 can be used for:
• generating interrupts (inputs I1, I2, I3, I4)
• controlling high-speed counters such as:
– 16 or 32-bit counters, for counting pulses (I1, I2),
up/down counting
– Incremental counters, 32-bit, for processing the signals of an
incremental encoder (I1, I2, I3, I4).
The function is selected in the PLC configuration. However, several
functions cannot be used at the same time.
Figure 1:
Front of the EC4P-221-MRAD1,
Legend
Figure 2:
Front of the EC4P-221-MTAD1
a
24 V DC power supply
b
Inputs
c
Interface for connecting the CAN network
d
Analog output, 0 – 10 V (not active)
e
DEL button
f
ALT button
g
RUN/STOP/SF LED
h
CAN/NET LED
i
Field for device labelling
j
easyLink interface to expansion device
k
Programming interface for connection to a PC
l
Multi-function interface
m
Relay outputs
n
Transistor outputs
o
OK button
p
ESC button
q
LCD display (EC4P-22x-M…D1)
r
Cursor buttons P1…P4 (rocker button)
Q1
Q2
Q
3
Q4
Q5
Q6
RUN
STOP
SF
CAN/
NET
e
a
b
d
c
f
g
h
i
j
k
l
p
r
o
m
q
Q7 Q8
Q5 Q6
Q
3
Q4
Q1 Q2
+24V
0V
RUN
STOP
SF
CAN/
NET
e
a
b
d
f
g
h
i
j
k
l
p
r
o
n
q
c
Digital
12 (I1…I12)
24 V DC
of which can be used
as analog
4 (I7, I8, I11, I12)
24 V DC/0…10 V
Figure 3:
Selection between digital and analog input, e.g. I7
Voltage [V]
State
F
8
FALSE
> 8
TRUE
Summary of Contents for easyControl EC4-200
Page 4: ...II...
Page 10: ...10 10 MN05003003Z EN 6...
Page 14: ...10 10 MN05003003Z EN 10...
Page 22: ...10 10 MN05003003Z EN 18...
Page 38: ...10 10 MN05003003Z EN 34...
Page 62: ...10 10 MN05003003Z EN 58...
Page 78: ...10 10 MN05003003Z EN 74...
Page 96: ...10 10 MN05003003Z EN 92...