10/10 MN05003003Z-EN
Technical data
101
Relay switching frequency
Mechanical switch operations
Switch
operations
10 mill. (107)
Mechanical switching frequency
Hz
10
Resistive lamp load
Hz
2
Inductive load
Hz
0.5
Transistor outputs
Number of outputs
8
Rated voltage
U
e
V DC
24
Permissible range
V DC
20.4 bis 28.8
Residual ripple
%
F
5
Supply current
On 0 state, typical/maximum
mA
18/32
On 1 state, typical/maximum
mA
24/44
Reverse polarity protection
h
Caution!
Connecting the outputs to a power supply with a reverse polarity will result
in a short-circuit.
Yes
Potential isolation
Yes
Rated current
I
e
at state 1, maximum
A
0.5
Lamp load without
R
V
W
5
Residual current on signal 0 per channel
mA
< 0.1
Maximum output voltage
On “0” signal with external load, 10 M
O
V
2.5
On „1“, signal,
I
e
= 0.5 A
U
=
U
e – 1 V
Short-circuit protection (thermal) Group Q1 to Q4 /Group
Q5 to Q8. Evaluation with
Diagnostics input I16 (Q1 to Q4), I17 (Q5 to Q8)
h
Caution!
Set the output group in the program to a “0” signal
in order to prevent the output from overloading
Yes
Short-circuit tripping current for
R
a
F
10 m
O
(depending on number of active channels and their
load)
A
0.7
F
I
e
F
2
Maximum total short-circuit current
A
16
Peak short-circuit current
A
32
Thermal cutout
Yes
Maximum switching frequency with constant resistive
load
R
L
= 100 k
O
(depends on program and load)
Switch
operations/h
40000
Summary of Contents for easyControl EC4-200
Page 4: ...II...
Page 10: ...10 10 MN05003003Z EN 6...
Page 14: ...10 10 MN05003003Z EN 10...
Page 22: ...10 10 MN05003003Z EN 18...
Page 38: ...10 10 MN05003003Z EN 34...
Page 62: ...10 10 MN05003003Z EN 58...
Page 78: ...10 10 MN05003003Z EN 74...
Page 96: ...10 10 MN05003003Z EN 92...