background image

5

Instruction leaflet 

IL05407002E

Effective October 2010

E5-648-C242x

electronic preset counter 

with two presets

eaton corporation

 www.eaton.com

7.4 Selecting the menu items

The Prog/Mode key is used to select  

a menu item within the sub-menu

7.5 Setting the menu items

The T2 key is used to select the individual 

settings for the menu items

When setting count values, each decade 

has a key assigned to it. Each time the key 

is pressed, the value increments by one

7.6 Accepting the setting

Pressing the Prog/Mode key causes 

the current setting to be accepted. 

Programming then switches to the next 

menu item

7.7 Ending the programming

During programming, it is possible to exit the programming  

at each menu item by pressing the reset key.

Press the Reset key

The security prompt appears in the display

Pressing the Prog/Mode key acknowledges 

this prompt and causes the programming 

menu to start again from the beginning. 

The previously programmed values are 

preserved. These can now be changed  

or checked again
Pressing the decade key T2 selects the 

termination of the programming

The security prompt appears in the display

Pressing the  Prog/Mode key  

acknowledges this prompt and  

terminates the programming; the modified 

settings are saved in the EEPROM.
The text SAVE is displayed for 2s

7.8 Programming menu
7.8.1 Default parameters

Three default parameter sets have been permanently stored; 

these can be adapted as required. With each acknowledgment 

of the parameter sets, all parameters will be reset to the values 

listed in the table. 

The dEFAuL P.USEr can be freely programmed.

Menu Parameter sets

Default setting 

Parameter set 1

Default setting 

Parameter set 2

Default setting 

Parameter set 3

Freely programmable 

user settings

7.8.2 Parameter sets

Factory setting are highlighted in grey.

Display

p.Set 1

p.Set 2

p.Set 3

Func

Count

Count

Count

InP.PoL

PnP

PnP

PnP

FiLtEr

on

oFF

oFF

Count

Cnt.dir

uP.dn

Quad

MPi

LAtch

LAtch

Set

Loc.InP

ProG

ProG

ProG

ModE

Add

Sub

TrAiL

FActor

01.0000

01.0000

01.0000

diViSo

01.0000

01.0000

01.0000

dP

0

0

0.00

SEtPt

000000

000000

0000.00

rESmd

Man.EL

Man.EL

Man.EL

PrES 1

on

on

on

Pr.Out 1
t.Out

00.10

Pr.Out 2
t.Out 2

00.10

00.10

Downloaded from 

Elcodis.com

 

electronic components distributor

 

Summary of Contents for E5-648-C242 Series

Page 1: ...Effective October 2010 Instruction leaflet IL05407002E E5 648 C242x electronic preset counter with two presets Downloaded from Elcodis com electronic components distributor ...

Page 2: ...6 7 8 4 Pulse counter 6 7 8 5 Tacho frequency meter 8 7 8 6 Timer 9 7 9 Setting the presets 12 7 9 1 Setting via decade keys 13 7 9 2 Setting with Teach In function 13 7 9 3 Setting the tracking presets 13 7 10 Set function 13 8 Error message 13 9 Connections 13 9 1 Signal and control inputs 14 9 2 Supply voltage and outputs 14 10 Technical data 14 10 1 General data 14 10 2 Pulse counter 14 10 3 T...

Page 3: ...ip from the rear onto the housing until the spring clamps are under tension and the upper and lower latching lugs have snapped into place 2 3 Electrical installation DANGER The device must be disconnected from the power supply before any installation or maintenance work is carried out AC powered devices must only be connected to the low voltage network via a switch or circuit breaker Installation ...

Page 4: ...no counting while active Timer no time measurement while active Gate hi no time measurement while not active Gate Lo 5 4 Lock Input Static keypad lock input for presets or programming Lock out level can be set in the programming menu 5 5 MPI Input Programmable as Display Latch Set or Teach In input 6 Outputs 6 1 Output 1 Relay with potential free make NO contact 6 2 Output 2 Relay with potential f...

Page 5: ...sing the decade key T2 selects the termination of the programming The security prompt appears in the display Pressing the Prog Mode key acknowledges this prompt and terminates the programming the modified settings are saved in the EEPROM The text SAVE is displayed for 2s 7 8 Programming menu 7 8 1 Default parameters Three default parameter sets have been permanently stored these can be adapted as ...

Page 6: ...P B count input sub Totalizing A B INP A count input add INP B count input add Quadrature input INP A count input 0 INP B count input 90 Quadrature with pulse doubling INP A count input 0 INP B count input 90 Each pulse edge of INP A will be counted Quadrature x4 INP A count input 0 INP B count input 90 Each pulse edge of INP A and INP B will be counted Ratio measurement A B Inp A count input A In...

Page 7: ...ro Batch counter counts the number of automatic repetitions of preset 2 Output 1 active when Batch counter preset 1 Manual reset sets main counter to preset value 2 batch counter to zero Electrical reset only sets the main counter to preset value 2 Count mode ADDING with automatic reset and Total counter Output 2 timed signal active when main counter preset value 2 Automatic reset to zero when mai...

Page 8: ...or programming the signal and control inputs Input polarity PNP switching to Plus for all inputs in common NPN switching to 0V for all inputs in common Filter for signal inputs Inp A and Inp B Maximum count frequency Damped to approx 30 Hz for control with mechanical contacts Input mode frequency measurement Simple frequency measurement Inp A Frequency input Inp B No function Differential measurem...

Page 9: ...cimal point determines the resolution 0 no decimal place 0 0 1 decimal place 0 00 2 decimal places 0 000 3 decimal places Moving average Moving average calculated AVG 2 over 2 measurements AVG 5 over 5 measurements AVG 10 over 10 measurements AVG 20 over 20 measurements Start delay Programmable from 00 0 to 99 9s At the start of a measurement the measurement results within this time period are ign...

Page 10: ...also 7 10 Lock input When the Lock input is activated the programming is inhibited When the Lock input is activated the setting of the preset values is inhibited When the Lock input is activated the setting of the preset values and the programming are both inhibited 7 8 6 2 Main menu for output operations Main menu for determining the operation of the outputs Count mode ADD Outputs active when cou...

Page 11: ...t sets only main counter to preset value 2 Tracking preset mode When preset 2 is changed then preset 1 automatically tracks it Reset to zero Preset 1 relative to preset 2 see also section 17 Output operations Tracking Preset mode with automatic reset When preset 2 is changed then preset 1 automatically tracks it Reset to zero Automatic reset to zero when main counter preset value 2 Preset 1 relati...

Page 12: ...irection and when count preset 1 Duration of timed signal of output 1 programmable from 00 01 to 99 99s Timed signal is post triggered 7 8 6 6 Main menu for preset 2 Main menu for preset 2 ADD mode output operations permanent signal at output 2 becomes active when count preset 2 SUB mode output operations permanent signal at output 2 becomes active when count zero ADD mode output operations perman...

Page 13: ... to be changed using the Prog Mode key Briefly activate the MPI NPN or PNP input logic The current count value will be adopted as the new preset value The preset value can subsequently be further modified via the decade keypad 7 9 3 Setting the tracking presets trail If a tracking preset has been programmed the value for preset 2 can be set either via the decade keypad or via the Teach In function...

Page 14: ...egative backlit 2 x 6 digit Digit height Upper line 9 mm Lower line 7 mm Special characters 2 mm Overload Blinking 1s Underload Counter loses up to 1 decade no pulses Data retention 10 years EEPROM Operation 8 keys 10 2 Pulse counter Count frequency max 55 kHz see section 13 Frequencies Response time of the outputs Relays Add Sub Trail 13 ms With automatic repeat 13 ms A B A B A 34 ms 10 3 Tacho f...

Page 15: ...age AC supply 90 260 Vac max 8 VA 50 60 Hz Ext fuse protection T 0 1A DC supply 10 30 Vdc max 1 5W reverse polarity protection Ext fuse protection T 0 2A 10 8 Sensor supply voltage AC supply 24 Vdc 15 80 mA DC supply max 80 mA external voltage supply is connected through 10 9 Climatic conditions Operating temperature 20 C to 65 C Storage temperature 25 C to 75 C Relative humidity RH 93 at 40 C non...

Page 16: ... A B A 29 kHz 29 kHz 29 kHz 5V level Typ Low 1 0V Typ High 4 0V Display Add Sub Trail AddAr SubAr AddBat SubBat TrailAr AddTot SubTot Cnt Dir 9 kHz 2 7 kHz 2 4 kHz Up Dn Up Up 9 kHz 2 7 kHz 2 4 kHz Quad Quad 2 9 kHz 1 2 kHz 1 2 kHz Quad 4 9 kHz 1 2 kHz 0 9 kHz A B A B A 9 kHz 9 kHz 9 kHz 13 2 Frequency meter HTL level AC supply Typ Low 2 5V Typ High 22V DC supply 12V Typ Low 2V Typ High 10V DC sup...

Page 17: ...1 0 Inp A Count input add Inp B Count input sub Add Display 0 Preset Sub Display Preset 0 Up Up INP A INP B ADD 0 4 1 2 7 3 6 Inp A Count input 1 add Inp B Count input 2 add Add Display 0 Preset Quad INP A INP B ADD 0 4 1 2 7 3 6 SUB P P P 1 P 1 P 3 P 2 P 2 A 90 B Inp A Count input Count on one edge Inp B Reverse direction Add Display 0 Preset Sub Display Preset 0 Quad 2 INP A INP B ADD 0 4 1 2 2 ...

Page 18: ... Inp A Count input Count on rising and on falling edges Inp B Count input Count on rising and on falling edges Reverse direction Add Display 0 Preset Sub Display Preset 0 A B INP A INP B Counts A Counts B Display 0 4 4 1 2 3 3 0 1 0 75 1 0 5 0 66 0 33 0 4 1 1 1 2 3 Inp A Count input 1 Inp B Count input 2 Formula A B A B A INP A INP B Counts A Counts B Display 0 4 4 1 2 3 3 0 0 33 1 100 50 200 0 4 ...

Page 19: ... P T1 T2 0 T1 T2 on off off T1 T1 T2 Inp A no function Inp B Start Stop Add Display 0 Preset Sub Display Preset 0 FrRrun GATE ADD SUB P P T2 P T1 T2 0 on off off T1 T1 T2 T1 T2 Inp A no function Inp B no function Control of the timing only via the GATE input Add Display 0 Preset Sub Display Preset 0 Auto GATE RESET PRESET ADD SUB P P T2 P T1 P T2 T3 0 P 0 P 0 P 0 on off off T1 T2 T2 T3 T1 T2 T3 T4...

Page 20: ...quency input 2 Formula A B AaddB INP B INP A Display 0 0 FA0 FA1 FA2 X 0 0 FB0 FB1 FB2 X 0 0 FA0 FA0 FB0 FA1 FB1 FB2 Inp A Frequency input 1 Inp B Frequency input 2 Formula A B Quad INP B INP A Display 0 0 FA0 fA0 fA1 fA2 fA3 fA4 fA5 FA1 FA2 FA3 FA4 A 90 B Inp A Frequency input 1 Inp B Reverse direction A B INP B INP A Display 0 0 0 FA0 FA1 X 0 0 FB0 FB1 FB2 X 0 0 0 FA0 FB0 FA1 FB1 0 Inp A Frequen...

Page 21: ... P1 OUT P2 RESET t t AddBat t t PR2 PR1 COUNTER OUT P1 BATCH OUT P2 RESET t t t SubBat t t PR2 PR1 COUNTER OUT P1 BATCH OUT P2 RESET t t t AddTot t t PR2 PR1 COUNTER OUT P1 TOTAL OUT P2 RESET t t SubTot t t PR2 PR1 COUNTER OUT P1 TOTAL OUT P2 RESET t t Mode Diagram Mode Diagram Trail t t tt t t PR2 PR1 PR1 COUNTER n 0 1 2 3 4 5 6 7 8 9 10111213 14 1312 1110 9 8 7 6 5 OUT P1 PR1 PR1 PR1 OUT P1 PR1 ...

Page 22: ...648 C242x electronic preset counter with two presets eaton corporation www eaton com 18 Dimensional drawings mm Figure 2 Dimensions Figure 3 Panel cut out 48 48 45 15 5 91 7 4 25 max 10 5 45 0 6 45 0 6 Downloaded from Elcodis com electronic components distributor ...

Page 23: ...truction leaflet IL05407002E Effective October 2010 E5 648 C242x electronic preset counter with two presets eaton corporation www eaton com Notes Downloaded from Elcodis com electronic components distributor ...

Page 24: ...d Printed in USA Publication No IL05407002E Z9871 October 2010 PowerChain Management is a registered trademark of Eaton Corporation All other trademarks are property of their respective owners Instruction leaflet IL05407002E Effective October 2010 E5 648 C242x electronic preset counter with two presets Downloaded from Elcodis com electronic components distributor ...

Reviews: