Step 2 

1.  Remove 225 mm of the insulation screen.
2.  Remove 77 mm of core insulation.
3.  Cut a 45° chamfer onto the end of the cable 

insulation.

Step 3

1.  Thoroughly clean the core insulation, using a suitable 

cleaner and a lint-free cloth.

2.  Wrap several layers of electrical tape over the end of 

the conductor.

3.  Apply a thin layer of lubricant to the core insulation 

and the inside diameter of the cable adapter. 

4.  Slide the cable adapter onto the cable, black end 

first, until the grey end is 85 mm from the end of the 

cable. Remove the electrical tape from the conductor.

Step 4

1.  If the conductor is aluminum, thoroughly wire brush 

the exposed conductor.

2.  Immediately insert the conductor into the crimp 

barrel as far as it will go. Ensure that the flat of the 

copper face is parallel to the face of the bushing.

3.  Crimp the connector starting at the shoulder, as 

shown. Rotate the crimping tool 90° for each 

successive crimp.

4.  Remove any inhibitor that may come out of the crimp 

connector.

Step 5

1.  Clean the outer surface of the cable adapter and the 

interior of the cable end of the tee connector with a 

lint-free cloth. Apply a thin layer of lubricant to both 

surfaces.

2.  Push the tee connector over the cable adapter as far 

as it will go. Ensure that the hole in the top of the 

crimp connector is visible through the interface end 

of the tee.

3.  Connect one of the screen wires to an earthing eye 

on the tee connector.

Figure 3.  Removal of insulation.

INSULATION

CONDUCTOR

225 mm

77 mm

50 mm

CHAMFER

Figure 4.  Cable adapter insulation.

Tape (Remove 

before next step)

85 mm

4   3   2  1

Figure 5.  Insertion of conductor into crimp barrel.

3

DT400/436 tee connector installation instructions

   MN650001EN   September 2014   www.cooperpower.com

Summary of Contents for DT400

Page 1: ...Lorem ipsum dolor sit Amat Connectors and Splices MN650001EN Effective September 2014 Supersedes IS550 30 1 March 2011 DT400 436 Tee Connector Installation Instructions...

Page 2: ...TING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES In no event...

Page 3: ...DUCT INFORMATION Introduction 1 Acceptance and Initial Inspection 1 Handling and Storage 1 Standards 1 INSTALLATION PROCEDURE Installation Instructions 2 iii DT400 436 tee connector installation instr...

Page 4: ...Safety information DANGER Hazardous voltage Contact with hazardous voltage will cause death or severe personal injury Follow all locally approved safety procedures when working around high and low vol...

Page 5: ...rocedures or process described nor provide directions for meeting every possible contingency during installation operation or maintenance For additional information contact your representative Accepta...

Page 6: ...re long enough to reach the earthing eye on the tee connector The cable will be cut to its final length in a later step 3 Remove 435 mm of the cable sheath 4 Fold the screen wires back over the sheath...

Page 7: ...per face is parallel to the face of the bushing 3 Crimp the connector starting at the shoulder as shown Rotate the crimping tool 90 for each successive crimp 4 Remove any inhibitor that may come out o...

Page 8: ...mm socket wrench Step 8 1 Clean and apply lubricant to the insulating plug and the tee connector interface 2 Insert the insulating plug into the connector and engage the threads of the clamping screw...

Page 9: ...24 kV Figure 9 Installation of cap CAUTION The apparatus bushing and tee connector should not support the weight of the cable Clamp the cable immediately below the cable screen adapter Failure to com...

Page 10: ...This page is intentionally left blank 6 DT400 436 tee connector installation instructions MN650001EN September 2014 www cooperpower com...

Page 11: ...This page is intentionally left blank 7 DT400 436 tee connector installation instructions MN650001EN September 2014 www cooperpower com...

Page 12: ...use these trademarks without the prior written consent of Eaton Eaton 1000 Eaton Boulevard Cleveland OH 44122 United States Eaton com Eaton s Cooper Power Systems Business 2300 Badger Drive Waukesha...

Reviews: