![Eaton DF6100 Installation And Operation Manual Download Page 26](http://html1.mh-extra.com/html/eaton/df6100/df6100_installation-and-operation-manual_3762112026.webp)
26
INSTALLATION AND OPERATION MANUAL
25-16328-B November 2020 www.eaton.com
Section 2: Commissioning
Section 2: Commissioning
Commissioning mode
Walk test mode allows a single engineer to test the various detectors and call points
on a system without always having to return to the panel either to reset the system
or silence the alarms . When in COMMISSIONING MODE, the system operates as
normal except that when a detector or call point goes into alarm, the alarms only
operate for a few seconds and then will silence . The panel then tries to reset the
device automatically and, if successful, the alarms are operated again for a few
seconds and the installation engineer can move on to the next detector . After a full
test has been carried out the engineer can check the order in which the detectors/
call points were operated using the DISPLAY LOG mode . This information can also
be printed on the optional printer .
For details of how to access commissioning mode, please refer to page 62
When the panel is in “Walk Test Mode” the control panel inserts a different code
into the log and also onto the print-out . This is to distinguish between when a device
has been tested in “Walk Test Mode” and when a device has been triggered while in
normal operation .
The following differences will occur:
a.
When in the LOG mode, “One man walk test” will appear on the display
followed by the address text and device type .
b.
On the printout a “One man walk test” message will appear will appear
followed by the address text and device type .
c.
During a real fire “FIRE !” Will appear on the display followed by the address
text and device type .
Configuration
Db level check
Panel includes the facility to test and set the system sounders with the minimum
amount of disturbance . In sounder test mode, the sounders will sound for
30 seconds on then 30 seconds off . This facility can be accessed via the
engineering menu .
Detector LED flashing
The Panel Sensor flashing function is used to allow a visual inspection and
confirmation that the fire panel is in communication with the installed system
devices . This facility can be accessed via the engineering menu and can be switched
on or off at any time as required .