Technical specification
Power specification
Mains Fuse
: 1 .6A Slow Blow
Nominal Voltage : 230 Vac + 10%, -15%
Nominal Current : 75mA
The Panel is protected by an internal thermal device, this requires no maintenance .
Batteries
Number of Batteries
: 2
Manufacturer:
: YSP12-7
Capacity
: 7 Ah
Battery Fuse
: 4A Quick Blow (F4)
Maximum battery current; : 3 .5 Amps
Inputs
Addressable Loops
Max Number
: 1 or 2 (Panel depending)
Max Loop Load per loop : 350 mA
Max Number of Addressable
: 200
Devices per loop
Class Change
: Operated by external volt free contact
Outputs
Conventional sounder circuits
Number of sounder circuits
: 2
Total sounder Load
: 1 .5 Amp
Sounder Circuit Fuses (F1/2)
: 1 .6 Amp (Quick Blow)
End of line device
: 210Ω + Diode
AUX 1
Max Load
: 1 Amp
Fused (PTC2)
: 1 .1A polyswitch