Section 1: System installation and design
System overview
Simple user interface
The main element of the user interface with is a large (120mm x 90mm visible area)
touch screen display, which provides comprehensive user information and also acts
as a multifunctional keypad .
Comprehensive context sensitive help information is provided throughout the menus
to assist unfamiliar users with system operation .
The Panel touch screen display automatically reconfigures to suit the selected
function, for example, if the change device text menu option is selected, the touch
screen is automatically formatted as a full QWERTY keyboard to enable fast and
simple text entry .
The use of the touch screen display enables a wide range of user and engineering
facilities to be incorporated into the panel whilst still offering simple operation .
User configuration and maintenance facilities
The Panel has comprehensive facilities for on site system configuration, whereby
the user can add or remove simple devices or change device text directly via the
panel, without the need for a service engineer to visit site . For initial configuration or
major system changes special PC configuration software is available enabling Eaton
Lighting and Security personnel to do this more efficiently than can be achieved
using the system screen . Exiting configurations can be uploaded to the PC so that
changes can be made to the existing system rather than having to revert to
initial files .
Sophisticated sounder control facilities
The Panel has the ability to support highly complex ringing pattern requirements .
Multistage cause and effect programming is possible whereby each addressable
sounder or output interface can be programmed independently if required and can be
set to respond to specific addresses, specific detection zones, specific panels on a
networked system or standard global ringing .
The panel supports three separate sets of programming per sounder and each
stage can be triggered differently For example, if a single detector is triggered the
panel can be programmed such that the sounder nearest to the detector operates
immediately and continuously, the remaining sounders in the affected zone operate
in pulsed mode and the other sounders delay for a selectable period to allow the
cause of the alarm to be investigated before global ringing commences .
Spur tolerant soft addressing
The Panel utilises intelligent soft addressing technology to greatly simplify the
installation and commissioning processes .
Once the system has been installed and the autolearn menu selected, the