background image

23

INSTALLATION AND OPERATION MANUAL

  25-16328-B   November 2020   www.eaton.com

Section 1: System installation and design

Networked Can be connected as loops or radial .
Networked panels can be used as active repeaters, alternatively a low cost passive 

repeater is available .
This can either be connected a loop of an individual panel or it can be connected to 

the network .
The recommended network cable for the network connection between panels is 

an enhanced Firetuf cable Manufactured by Draka cables (part number 910234 .) 

Screen continuity must be maintained throughout the entire network circuit including 

at each junction point . The screen should only be earthed at the connection point 

provided at the first panel and not at any other point . The screen or drain wire of the 

network cable should not be considered as a safety earth and therefore should not 

be connected to terminals marked with the earth symbol, except at the panel, and 

should not be insulated with green and yellow sleeving .

Where the network cable passes between buildings, screen continuity should 

not be maintained from building to building . A booster device must however be 

used irrespective of cable length and should be fitted at a suitable point in the link 

between buildings . The cable screen should be connected to the earth of one panel 

in each building . 102 S terminator should be fitted at the beginning and the end of 

the network . If the distance in the network exceeds 1KM the booster should be 

used . The booster requires 24V local supply, which can be connected to nearest 

Addressable Panel .

Input/outputs

Panel inputs

Class Change: (OPTION NOT REQUIRED BY EN54) .
A pair of terminals are provided for class change . By shorting these terminals 

together (e .g . Switch, Time clock) the alarm will sound (Panel so loop 

sounders only) . The Panel will not indicate a Fire . The alarm will cancel when the 

short circuit is removed . If the short circuit is not removed the alarms will not cancel .

WARNING

No voltage should be applied to this input .

-

+

Switch/Contactor

timer etc.

(Apply NO voltage)

Class Change

Summary of Contents for DF6100

Page 1: ...1002 Installation and Operation Manual VdS G211013 DoP0228 16 EN54 2 1997 A1 2006 EN54 4 1997 A1 2002 A2 2006 General Fault FIRE General Disable Power ON TEST Sounder Disable Fault System Fault Power...

Page 2: ...ns as per EN54 P2 4 17 Installation 19 External connections 21 Networking 22 Input outputs 23 Maintainance 25 SECTION 2 COMMISSIONING 26 Commissioning mode 26 Configuration 26 Panel fault finding 28 P...

Page 3: ...alk test 54 Commission Load CDR from laptop 55 Commission Download CDR to laptop 56 Commission Auto learn 57 Erase log 58 System details 59 Load logo from PC 60 Analogue level 61 Change panel number 6...

Page 4: ...CASB383 91 IP66 wall sounder wiring CAS381WP CASB383 WP 92 Base Sounder VAD CASBB394 93 Wall Sounder VAD CASB393 94 IP66 Wall Sounder VAD CASB393WP 95 3 way input output unit CIO351 CIO351S CIO351SST...

Page 5: ...e product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser THERE ARE NO UND...

Page 6: ...w You should contact your local distributor for product pricing availability ordering expediting and repairs Website Use the Eaton website to find product information You can also find information on...

Page 7: ...zardous situation which if not avoided can result in minor to moderate injury or serious damage to the product General Safety Precautions NOTICE The operating system of the control panel may be revise...

Page 8: ...n specifically designed to operate as part of a Panel system this provides an assurance that the panel the detectors the interfaces and the ancillaries are all fully compatible with each other and tha...

Page 9: ...e far terminals on Panel Motherboard PCB There is no minimum limit to loop length Any wiring spurs off the loop must be included within the 2 km limit On long loop runs the lengths of wiring rises and...

Page 10: ...o Detector 87H x 87W x 30D CIR301WP Conventional Weatherproof Remote Indicator Connects to Detector 87H x 87W x 30D MRIAD Addressable Remote Indicator 87H x 87W x 49D MBG813 Addressable Callpoint 87H...

Page 11: ...x 35W x 18 5D MAR724 Heavy Duty Relay 88H x 147W x 57D ZPCB2252 MML Addressable Master LED MIMIC 190H x 350W x 75D ZPCB2252 MSL Addressable Slave LED MIMIC 190H x 350W x 75D ZPCB2223 Loop Splitter op...

Page 12: ...appendix to suppress any reverse EMF on the release of the relay which might cause the panel to malfunction 2 A 24V DC output is provided at the panel to make it easy to connect ancillary equipment Al...

Page 13: ...pecial PC configuration software is available enabling Eaton Lighting and Security personnel to do this more efficiently than can be achieved using the system screen Exiting configurations can be uplo...

Page 14: ...integrity A single short circuit will not disable any loop mounted devices the isolators in the devices each side of the short circuit will operate and the control panel will drive communication from...

Page 15: ...es Number of Batteries 2 Manufacturer YSP12 7 Capacity 7 Ah Battery Fuse 4A Quick Blow F4 Maximum battery current 3 5 Amps Inputs Addressable Loops Max Number 1 or 2 Panel depending Max Loop Load per...

Page 16: ...output is not to be used for Fire protecting equipment or Fire alarm routing Equipment Any power taken from the alarm system will effect the standby duration Mechanical specification Weight including...

Page 17: ...al condition it operates by providing 12vdc which can be connected directly to a 12v auxiliary device relay It is current limited to 30 mA Under fault conditions or even if the Panel is powered down t...

Page 18: ...iring Only the cable types listed below are allowable for loop connections 1 Enhanced Fire TUF 2 Fire TUF 3 FP200 4 MICC When choosing your preferred cable type you must take note of the following cab...

Page 19: ...conductors should be permanently identified 6 Screen continuity must be maintained throughout the entire loop circuit including at each junction point and at each device terminals are provided on each...

Page 20: ...and with BS5839 part 1 2002 The electronic components within the fire panel are Static Sensitive Do not touch the electronics directly Mounting the Backbox The Panel can be surface mounted and recess...

Page 21: ...current edition of the IEE wiring regulations Connection to the mains supply must be via an isolating device e g an isolating fuse reserved solely for the fire alarm system The cover should be coloure...

Page 22: ...ove also applies to any distributed power supply i e mains connections for Repeater Panels Sounders Controller Units etc Cable segregation All cables for the fire alarm system should be segregated fro...

Page 23: ...d should not be insulated with green and yellow sleeving Where the network cable passes between buildings screen continuity should not be maintained from building to building A booster device must how...

Page 24: ...sistor and it current limited to 30 mA Under normal conditions it operates by providing 12vdc which can be connected directly to a 24v auxiliary device relay It is current limited to 30 mA Under fault...

Page 25: ...a detailed a building plan highlighting devices and locations to aid testing The panel will reset automatically once the 5mins have elapsed If no devices are triggered during the weekly test the panel...

Page 26: ...the panel is in Walk Test Mode the control panel inserts a different code into the log and also onto the print out This is to distinguish between when a device has been tested in Walk Test Mode and wh...

Page 27: ...nels The software can download to all 126 networkable Panels The PC is connected to each Panel on the network in turn All data for the Panel is downloaded For networked systems panels are identified b...

Page 28: ...mming See Scope Plots for Monitoring Conditions O C Normal S C Fire O C Normal S C Fire S C Normal O C Fire S C Normal O C Fire 12V No Fault 0V short CCT Fault O 6V No Fire 24V Fire REPEAT FOR LOOP 2...

Page 29: ...ce Evacuate Panel will send all alarm Fire extinguisher activate Fire extinguisher output will operate Fre activate Fre operates None fire Event will be logged but not displayed cause and effect will...

Page 30: ...n isolated as the triggered device returns to normal operation a call point keyswitch is an example for this application Device outputs Delay configuration The output of a device when triggered can be...

Page 31: ...l output can be assigned a unique list of zones derived from the zones available on the loop to activate this output two unique zones from this list have to be be in fire or alternatively any zone out...

Page 32: ...rs Report to system supervisor 4 General disable Monitors fire panel for faults Report fault to service dept 5 Power fault Monitor internal battery charger Report fault to service dept 6 System fault...

Page 33: ...lling fire conditions faults pre alarms or disabled devices independently or for displaying a reduced menu when in fire condition When an event occurs the Touch Screen backlighting comes on unless the...

Page 34: ...ield will highlight it and forward to the next screen as shown below Supervisor FRE Off Fires 0 Pre Alarms 0 Faults 0 Disabled Test 0 System Healthy XX Zones Active Tuesday dd mm yyyy 16 25 25 BST On...

Page 35: ...p 1 Ad 1 Z 1 Opto thermal 0 002 03 Jun 03 12 51 Warning Device2 Lp 1 Ad 2 Z 1 Opto thermal 69 002 12 32 59 Fault Device2 Lp 1 Ad 2 Z 1 Opto thermal 69 003 03 Jun 03 12 51 Warning Device3 Lp 1 Ad 3 Z 1...

Page 36: ...tes To enter the supervisor mode touch the supervisor button and enter the passcode Enter the Supervisor Mode Passcode and select Evacuate on the menu at the top of the screen Select Yes to evacuate t...

Page 37: ...er the supervisor mode touch the supervisor button and enter the passcode Enter the Supervisor Mode Passcode and select Silence Alarms button as the top of the screen Select yes to silence Alarm Super...

Page 38: ...d Select Reset from the top Menu Select Yes to reset the panel Supervisor FRE Off Evacuate Fires AC 0 Enable Disable Print Lamp test Send analogue values to PC View Log Check Config Weekly Test Send L...

Page 39: ...sabled devices Enter the Supervisor mode and Select the Disabled tab The individual buttons show which devices and the number of devices which have been disabled Press one of the buttons to display de...

Page 40: ...sor button and enter the passcode Enter the Supervisor Mode passcode and select the Others tab Supervisor FRE Off Evacuate Silence Alarms Mute Buzzer Reset Fires AC 0 View Pre Alarms View Disabled Vie...

Page 41: ...1 Zone 1 Type Opto thermal 003 Device 3 Zone 1 Loop 1 Zone 1 Type Opto thermal 004 Device 4 Zone 1 Loop 1 Zone 1 Type Opto thermal 005 Device 5 Zone 1 Loop 1 Zone 1 Type Opto thermal Evacuate Silence...

Page 42: ...Select the Others Tab Press Print Select the Information You wish to Print from the Buttons Listed Supervisor FRE Off Evacuate Silence Alarms Mute Buzzer Reset Fires AC 0 View Pre Alarms View Disable...

Page 43: ...Supervisor FRE Off Evacuate Silence Alarms Mute Buzzer Reset Fires AC 0 View Pre Alarms View Disabled View Faults Others Weekly Test Send Log to PC Enable Disable View Log Lamp Test LED s will light i...

Page 44: ...wn below Press Weekly test Weekly test is now in progress The panel will automatically return to the system healthy screen once the weekly test has been completed Supervisor FRE Off Evacuate Silence A...

Page 45: ...e interface is required See control panel operation for details This needs to be programmed as a call point on site installed PC software Standard connections ote N 1 Only connect cable screen to its...

Page 46: ...mm x 18 5mm Weight 0 1gm Ingress protection IP40 Short circuit isolator This addressable device contains an integral short circuit isolator which operates between the IN terminal and the OUT terminal...

Page 47: ...he oldest event every time a new event is stored The event log can only be reset by an approved service engineer Supervisor FRE Off Evacuate Silence Alarms Mute Buzzer Reset Fires AC 0 View Pre Alarms...

Page 48: ...feature will scan the loop and pinpoint the exact location of any break in the loop wiring and will also identify any changes in the loop configuration e g New devices added or changed device types Su...

Page 49: ...eplace device menu to allocate an existing address to the new device 1 1 0 0 2 2 3 3 4 4 5 5 6 6 7 7 8 8 9 9 Supervisor FRE Off Fires AC 0 Evacuate View Pre Alarms Enable Disable Print Lamp test Super...

Page 50: ...t 001 Lobby Build 1 1st floor Loop 1 Zone 2 Type Optical 002 Main Reception Building 1 1st floor Loop 1 Zone 2 Type Optical 003 Storage archive Building 1 1st floor Loop 1 Zone 2 Type Optical 004 Meet...

Page 51: ...ice passcode Enter the Service Mode Select Test and on the Screen Shown Below Press Test Zone Mute Buzzer Reset Service FRE Off Exit Global Flashing LED on off Test Zone Sounder Level Test Mode One Ma...

Page 52: ...ounder Level Test Mode Service FRE Off Mute Buzzer Reset Configure Enable Disable Address Commission Test Mute Buzzer Reset Service FRE Off Exit Global Flashing LED on off Test Zone Sound Level Test M...

Page 53: ...and enter the service passcode Enter the Service Mode and Select Test If global LED flashing is set to on all device LED s will pulse intermittently to confirm correct communication Select Global Fla...

Page 54: ...ervisor button and enter the service passcode Enter the Service Mode and Select Test Service FRE Off Mute Buzzer Reset Configure Enable Disable Address Commission Test Mute Buzzer Reset Service FRE Of...

Page 55: ...Number of Panels in Network Italian Mode System Detail Screen Cover Service FRE Off Mute Buzzer Reset Configure Enable Disable Address Commission Test Mute Buzzer Reset Service FRE Off Exit Load CDR f...

Page 56: ...Address Commission Test Mute Buzzer Reset Service FRE Off Exit Download CDR to Laptop Start PC program Press OK to continue or Cancel to exit OK Cancel Load logo from PC Load CDR from Laptop Download...

Page 57: ...ress Commission Test Supervisor FRE Off Exit Auto Learn No Pre addressed auto learn Yes autolearn all loops Do you want to continue Load logo from PC Load CDR from Laptop Download CDR to Laptop Auto L...

Page 58: ...nfigure Enable Disable Address Commission Test Yes No This will delete all log entries Do you want to continue Load logo from PC Load CDR from Laptop Download CDR to Laptop Auto Learn Erase Log Analog...

Page 59: ...der Control Unit Voice Annunciator Repeater ZMU SUM Beam Detector Technical Timer Non fire input Emerg Light Module Carbon Monoxide Opto sounder Opto heat sounder Heat A1R sounder Heat BS sounder Heat...

Page 60: ...d enter the service passcode Enter the Service Mode and Select Commission Load logo from PC Load CDR from Laptop Download CDR to Laptop Auto Learn Erase Log and Reset Analogue Level Printer Settings C...

Page 61: ...d CDR to Laptop Auto Learn Erase Log and Reset Analogue Level Printer Settings Change Panel Number Number of Panels in Network Italian Mode System Detail Screen Cover Mute Buzzer Reset Service FRE Off...

Page 62: ...To enter the supervisor mode touch the supervisor button and enter the service passcode Enter the Service Mode and Select Commission then press Change Panel Number Service FRE Off Mute Buzzer Reset C...

Page 63: ...er the service passcode Enter the Service Mode and Select Commission then press Number of Panels in Network Service FRE Off Mute Buzzer Reset Configure Enable Disable Address Commission Test Load logo...

Page 64: ...d enter the service passcode Enter the Service Mode and Select Commission then press Screen Cover Service FRE Off Mute Buzzer Reset Configure Enable Disable Address Commission Test Service FRE Off Res...

Page 65: ...r the Service Mode and Select Commission then press Italian Mode Service FRE Off Mute Buzzer Reset Configure Enable Disable Address Commission Test Service FRE off Reset Italian Mode T1 Call Point Del...

Page 66: ...ecs 140 secs 80 secs 20 secs 130 secs 70 secs 10 secs Off Service FRE Off Mute Buzzer Reset Configure Enable Disable Address Commission Test Mute Buzzer Reset Service FRE off Exit Day Night Network Pr...

Page 67: ...ecs 140 secs 80 secs 20 secs 130 secs 70 secs 10 secs Off Service FRE Off Mute Buzzer Reset Configure Enable Disable Address Commission Test Mute Buzzer Reset Service FRE off Exit Day Night Network Pr...

Page 68: ...left corner of the screen until the screen illuminates To enter the supervisor mode touch the supervisor button and enter the service passcode Enter the Service Mode and Select Configure Mute Buzzer R...

Page 69: ...re Configure Mute Buzzer Exit Add Delete Change Date Time Change Text Configure Zones Change Pascode Network Protocal Extinguisher Fire Bridgsde Australian Swedish Mode Day Night Language Network Conf...

Page 70: ...t Configure Service FRE Off Service FRE off Service FRE off Service FRE off Alarm Verification Feature Programming I O and Sounders Exit Commission Test Enable Disable Address Mute Buzzer Mute Buzzer...

Page 71: ...s Panel Outputs Service FRE off Programming I O and Sounders Mute Buzzer Exit Exit Auxillary Board HMO Sounder tone Alarm Verification Feature Reset Exit Reset Exit Add Delete Change Date Time Configu...

Page 72: ...ing the Buttons Shown Below Service FRE Off Reset Change Password Exit Mute Buzzer Programming I O and Sounders Change Date Time Change Text Configure Zones Add Zone Add Device Delete Zone Delete Devi...

Page 73: ...ete Device Exit Change address text Change Panel Text Change zone text Mute Buzzer Mute Buzzer Day Night Service FRE Off Reset Exit Service FRE Off Reset Change Password Programming I O and Sounders C...

Page 74: ...Device Exit Mute Buzzer Change Password Day Night Service FRE Off Change address text Change Panel Text Change zone text Reset Mute Buzzer Exit 001 Device 1 Zone 1 Loop 1 Zone 1 Type Opto thermal 002...

Page 75: ...dd Device Delete Zone Delete Device Exit Exit 1 Q A Z X C V B S D F G CAPS OTHER CF1100 Correct Panel Text SPACE W E R T Y 2 3 4 5 6 U I O P 7 8 9 0 N M H J K L OK CANCEL Mute Buzzer Change Password D...

Page 76: ...Password Day Night Configure Zones Touch the dash to move the device into the selected zone 001 Device 1 Zone 1 Loop 1 Zone 1 Type Opto thermal 002 Device 2 Zone 1 Loop 1 Zone 1 Type Opto thermal 003...

Page 77: ...Code Please enter Passcode New Code Verify New Code 1 4 5 6 7 8 9 ok 0 2 3 Passcode is not correct No change made Ok Verification is incorrect No change made Ok New Password accepted Saved Ok Cancel E...

Page 78: ...Service Mode and Select Configure Select Add Zone Add Zone Exit Add Delete Change Date Time Change Text Configure Zones Change Password Day Night Language Network Configure Heat Detectors Mute Buzzer...

Page 79: ...lete Exit Reset Delete Zone 2 Yes No Service FRE Off Service FRE Off Reset Add Zone Add Device Delete Zone Delete Device Exit Zone 001 Zone 1 Zone 002 Zone 2 Zone 003 Zone 3 Zone 004 Zone 4 Touch row...

Page 80: ...m New Device and Loop Loop 2 Exit Exit Scanning Loop Loop 2 Service FRE Off Reset Exit Add Zone Delete Zone Delete Device Service FRE Off Reset Loop 1 Add Device Loop 2 Exit Exit Scanning Loop Loop 2...

Page 81: ...Touch row to delete Goto Delete Device 3 Device 3 Loop1 Address 3 Device Type Opto thermal Yes No Service FRE Off Reset Exit Service FRE Off Reset Exit Add Zone Add Device Delete Zone 001 Device 1 Zo...

Page 82: ...ord Day Night Language Network Mute Buzzer Reset Service FRE Off Programming I O and Sounders Touch row to configure Service FRE Off Reset Exit 001 Device 1 Zone 1 Loop 1 Zone 1 Type Opto thermal 005...

Page 83: ...ssage over network Evacuate Silence Fire Pre Alarm Fault Select Group of Panels or Panel on the same network Reset Evacuate Exit Network filter Receive message over Netrwork Mute Buzzer Silence Alarms...

Page 84: ...This menu defines whether messages are broadcast across the network or remain local Reset Evacuate Exit Receive message over Netrwork Mute Buzzer Silence Alarms Exit Add Delete Change Date Time Chang...

Page 85: ...and Select Configure Select Programming I O and Sounders from the Configure Menu Screen Then press Language Select required Language English Fran ais Deutsch Nederlands Italiano Portugu s Nederlands...

Page 86: ...st Configure Reset Exit Mute Buzzer Service FRE off Reset Exit Day Night Programming I O and Sounders Change Date Time Change Text Configure Zones Add Delete Network Configure Heat Detectors Language...

Page 87: ...Menu and to TEST COMMISSIONING MODE The password is a four digit code and the default number is 2214 The password entry screen is accessed via the supervisor mode button Press supervisor mode and the...

Page 88: ...L L O O O O P P 4 4 A A U U X X R R E E L L A A Y Y L L O O O O P P C C I I R R C C U U I I T T S S 0 0 V V S S S S F F F F F F F F S S S S 2 2 6 6 V V R R x x C C T T S S R R T T S S O O V V T T x x...

Page 89: ...neven mounting surfaces a very uneven surface may cause the base to deform when the mounting screws are tightened down loosen screws to reduce this or slide base to a flat position WARNING DO NOT USE...

Page 90: ...el Continuous 910Hz Pulsed 910Hz 0Hz pulse 1Hz Two tone 610 910Hz 1Hz cycle Slow whoop 500 1200Hz in 3 5 seconds 0 5secs gap E E E E I IN N O O U U T T A An na al lo og gu ue e A Ad dd dr re es ss sa...

Page 91: ...surface using two suitable screws the rear gasket fits underneath the base and the sounder gasket fits inside the base Connection WARNING Do NOT use high voltage testers if ANY equipment is connected...

Page 92: ...s for the cable gland fixing 2 Drill out the required fixing holes 3 Fix to mounting surface using two suitable screws Connections WARNING Do NOT use high voltage testers if ANY equipment is connected...

Page 93: ...s pass through aperture in sounder body and terminate at the front 6 Connections are to connector block on front of main sounder body System functionality 1 Volume and tone are set by control panel no...

Page 94: ...ed into place on base main body locks into place when pressed into position 5 Cables pass through aperture in sounder body and terminate at the front 6 Connections are to connector block on main sound...

Page 95: ...olted into place on base 5 Cables pass through aperture in sounder body and terminate at the front Ensure cables are correctly sealed for IP66 integrity 6 Connections are to connector block on main so...

Page 96: ...operation for details Standard connections ote N No addressing of the interface is required See control panel operation for details 1 Only connect cable screen to its adjacent earth terminal 2 The en...

Page 97: ...pass the wires into it 4 Connect the unit according the diagram below ote N No addressing of the interface is required See control panel operation for details Standard connections ote N 1 Only connec...

Page 98: ...1 This unit can only be used with CDB300 I detector base and compatible detectors 2 Only connect cable screen to its adjacent earth terminal 3 The end of line resistor must always be fitted even if th...

Page 99: ...able Type FIRETUF FP200 MICC ote N No addressing of the interface is required See control panel operation for details There are no serviceable parts so no maintenance procedures apply Standard connect...

Page 100: ...f the spur is unused 4 Maximum spur length See BS5839 Pt1 2002 for Zone Coverage 5 Maximum number of call points allowed is unlimited 6 Detector zone end of line device is EOLM 1 7 Callpoint zone has...

Page 101: ...function correctly No addressing of the interface is required See control panel operation for details Standard connections ote N 1 Only connect cable screen to its adjacent earth terminal 2 For maximu...

Page 102: ...required See control panel operation for details This unit requires a permanent 230V AC supply Standard connections ote N 1 Only connect cable screen to its adjacent earth terminal 2 The end of line r...

Page 103: ...the wires into it 4 Connect the unit according to the diagram below 5 Set the required threshold levels via the DIL switches Standard connections ote N Recommended Loop Cable Type FIRETUF FP200 MICC N...

Page 104: ...peration for details There are no serviceable parts so no maintenance procedures apply Standard connections ote N 1 This unit can only be used with Eaton FXN520 detector base and compatible detectors...

Page 105: ...FIRETUF FP200 MICC ote N No addressing of the interface is required See control panel operation for details There are no serviceable parts so no maintenance procedures apply Standard connections ote N...

Page 106: ...o the diagram below 3 Recommended Loop Cable Type FIRETUF FP200 MICC ote N No addressing of the interface is required See control panel operation for details There are no serviceable parts so no maint...

Page 107: ...t the internal PCB 6 Install wiring through the pre drilled holes ensuring care is taken not to damage the circuit board 7 Connect the unit as per diagram below 8 Refit front cover 9 Recommended Loop...

Page 108: ...uth Yorkshire DN2 4NB Eaton EMEA Headquarters Route de la Longeraie 7 1110 Morges Switzerland Eaton eu 2019 Eaton All Rights Reserved Publication No 25 16328 B November 2020 Eaton is a registered trad...

Reviews: