Instruction Leaflet
IL17559 Rev. D
Instructions for the DeviceNet
®
Product
Effective August 2009
Operated Network Interface (DPONI)
EATON CORPORATION
www.eaton.com
10
Table B-2. Format of Assembly Instance #150 (96h) – Status.
Word #
Member
Parameter
Inst #
Data Bytes
0 1
Status StatusByte
32
33
2 2
Table B-3. Format of Assembly Instance #151 (97h) – Temperatures.
Word #
Member
Parameter
Inst #
Data Bytes
0
Status
32
2
1
StatusByte
33
2
2
WindingTemp1 40 2
3
WindingTemp2
41
2
4
WindingTemp3 42 2
5
WindingTemp4
43
2
6
WindingTemp5 44 2
7
WindingTemp6
45
2
8
MotorBrngTemp1 46 2
9
MotorBrngTemp2
47
2
10
LoadBrngTemp1 48 2
11
LoadBrngTemp2
49
2
12
AuxiliaryTemp 50 2
Table B-4. Format of Assembly Instance #152 (98h) – Currents.
Word #
Member
Parameter
Inst #
Data Bytes
0
Status
32
2
1
StatusByte
33
2
2
CurrentPhA 51 2
3
CurrentPhB
52
2
4
CurrentPhC 53
2
5
CurrentGnd
54
2
6
CurrentAvg3Ph 55 2
Table B-5. Format of Assembly Instance #153 (99h) – MotorData.
Word #
Member
Parameter
Inst#
Data Bytes
0
Status
32
2
1
StatusByte
33
2
2
CurrentPhAPcntFl 56 2
3
CurrentPhBPcntFl
57
2
4
CurrentPhCPcntFl 58 2
5
PcntPhaseUnbal
59
2
6
PcntThermCapcty 60 2
7
TimeToNextStart
61
2
8
RemainStartsCnt
62
2
9
TimeOldestStart 63 2