Instruction Leaflet 

IL17559 Rev. D

 

Instructions for the DeviceNet

®

 Product

 

Effective August 2009

 

Operated Network Interface (DPONI)

 

EATON CORPORATION

 

www.eaton.com

 

4

 CAUTION 

1. 

DO NOT INSTALL THE DPONI IN LOCATIONS WHERE THE 
TEMPERATURE AT THE UNIT FALLS OUTSIDE THE RANGE OF –
20 C TO 70 C (-4 F TO 158 F).  COOLING EQUIPMENT, SUCH AS 
A FAN, SHOULD BE USED TO LOWER THE TEMPERATURE IF 
THE 70 C (158 F) LIMIT IS EXCEEDED.  HEATING EQUIPMENT 
SHOULD BE PROVIDED IF THE –20 C (-4 F) LIMIT IS 
EXCEEDED. 

2. 

DO NOT INSTALL THE UNIT WHERE THE RELATIVE HUMIDITY 
EXCEEDS 90% OR WHERE CONDENSATION FORMS DUE TO 
RAPID TEMPERATURE CHANGES.  A HEATER SHOULD BE 
PROVIDED TO PREVENT THE FORMATION OF CONDENSATION. 

3. 

DO NOT INSTALL THE UNIT WHERE DUST, SALT, OR IRON 
PARTICLE DENSITIES ARE HIGH. 

4. 

DO NOT INSTALL THE UNIT WHERE IT MAY BE SUBJECTED TO 
DIRECT IMPACT OR VIBRATION. 

 

Networking 

Master Device 

The control station for the DeviceNet network must be a unit, 
such as a PC or PLC, which acts as a DeviceNet master. 

EDS files for the MP-4000 (MP-4000.EDS) and MP-3000 
(MP3000.EDS) are on the disc shipped with the DPONI.  The 
latest version of each of these files is also available on the Eaton 
Corporation Website (www.eaton.com). 

Slave Device 

A DPONI must be used as a slave device with a DeviceNet 
network to provide communications with the MP-3000 or MP-
4000. 

Simplified Wiring Rules 

For complete wiring rules, refer to the DeviceNet Specification.  
The DeviceNet configuration must comply with the rules for 
trunk and drop cable configuration and length.  The following list 
provides the basic wiring rules. 

• 

Terminating resistors are required on each end of the trunk 
line. 

• 

The trunk must be configured as a linear bus. 

• 

Drop lines may be as long as 6 m (20 ft) and may contain 
branches.  The cumulative drop length for thin or thick cable 
is limited to 156 m (512 ft) for 125 Kbps, 78 m (256 ft) for 
250 Kbps, and 39 m (128 ft) for 500Kbps. 

• 

The maximum total cable distance at all baud rates is 100 m 
(328 ft) for thin trunk cable. 

• 

The maximum total cable distance at 125 Kbps is 500 m 
(1640 ft) for thick trunk cable. 

• 

The maximum total cable distance at 250 Kbps is 250 m 
(820 ft) for thick trunk cable. 

• 

The maximum total cable distance at 500 Kbps is 100 m 
(328 ft) for thick trunk cable. 

• 

The maximum length of mixed cables may be found by 
solving the following equation: 
L

Thick

 + 5*L

Thin

 = 500 m (1640 ft). 

L

Thin

 must not exceed 156 m (511 ft). 

The most common power configuration is shown in Figure 4.  
The 5-point plug connector should be wired with cable approved 
for DeviceNet applications.  The colors of the wires should be 
matched to the DPONI label. 

 

 

 

Figure 4. Typical DeviceNet Power Configuration. 

The DeviceNet cable insulation should be stripped back 
approximately 1 in. (25.4 mm) from the end. Each of the wires 
should be stripped approximately ¼ in. (6.5 mm).  The terminals 
of the DeviceNet connector should be tightened to 5 to 7 in-lbs 
(0.57 to 0.79 N-m).  The drop cable can be daisy chained by 
terminating two wires under one screw. 

Operational Check 

After the DeviceNet system has been installed, check the 
operation of the DPONI by applying power to the host device and 
to the DeviceNet network.  When under power from both 
sources, the bicolor LED should: 

• 

Turn green for approximately 0.25 second; 

• 

Turn red for approximately 0.25 second; then 

• 

Turn off. 

Note that a minimum of two nodes (a master and a slave) must 
be under power for the Duplicate MAC ID check to complete 
successfully. 

The DPONI does not support network-settable addressing.  The 
DPONI address is entirely switch- dependent.  Each DPONI is 
shipped with its address switches set to 63. 

The DPONI’s bicolor combined network/status LED functions as 
defined in the DeviceNet Specification.  In brief, after DPONI 
initialization, the status LEDs perform as described in the 
following section of this instruction leaflet. 

LED Definitions and Diagnostics 

During the power-up initialization sequence, all three bicolor LEDs 
should blink green, then red, then off.  This indicates that all three 
LEDs are functioning correctly.  After initialization, these LEDs 
function according to the following descriptions. 

Combined Module/Network Status (NS) LED 

The Combined Module/Network Status (NS) LED provides an 
indication of the status of the DeviceNet Network as listed in 
Table 1. 

Summary of Contents for DeviceNet Product Operated Network Interface

Page 1: ...implified Wiring Rules 4 Operational Check 4 LED Definitions and Diagnostics 4 Combined Module Network Status NS LED 4 5 WIRE TX 5 Troubleshooting 5 Specifications 5 DeviceNet Cable Specifications 5 Maintenance and Care 5 Appendix A Parameter Object Instances for MP 3000 6 Appendix B Assembly Object Instances for MP 3000 9 Appendix C Parameter Object Instances for MP 4000 14 Appendix D Assembly Ob...

Page 2: ...rience and judgment and may not cover all contingencies If further information is required an Eaton sales office should be consulted Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser THERE ARE NO UNDERSTANDINGS AGREEMENTS WARRANTIES EXPRESSED OR IMPLIED IN...

Page 3: ... DPONI supports explicit mode and polled I O connections Volume 3 of the CIP Networks Library provides details of these communications modes The DPONI must be reset following an address change via the address switches by removing power from the DPONI host connection This can be accomplished by cycling power to the host device The DPONI allows monitoring and control only Changing setpoints is not s...

Page 4: ...s 500 m 1640 ft for thick trunk cable The maximum total cable distance at 250 Kbps is 250 m 820 ft for thick trunk cable The maximum total cable distance at 500 Kbps is 100 m 328 ft for thick trunk cable The maximum length of mixed cables may be found by solving the following equation LThick 5 LThin 500 m 1640 ft LThin must not exceed 156 m 511 ft The most common power configuration is shown in Fi...

Page 5: ... 6 If suggestions 1 through 5 do not remedy the problem the DPONI may need to be replaced CAUTION DO NOT ATTEMPT TO SERVICE THIS EQUIPMENT OTHERWISE SERIOUS INJURY OR DEATH AND OR EQUIPMENT DAMAGE MAY RESULT Specifications Table 2 DeviceNet Connector Ratings Connector Rating V 11 Vdc to 27 Vdc inrush 300 mA steady state 40 mA maximum 3 VA V DeviceNet common CANH Reverse wiring protected to 27 Vdc ...

Page 6: ...UINT 2 Get 0 15 1 0 300 37 FlagsStatus UINT 2 Get 0 6 1 0 3C8 38 FlagsReason UINT 2 Get 0 40 1 0 3C8 39 SlaveActions WORD 2 Set Get 0 65535 1 0 3D0 40 WindingTemp1 DegC INT 2 Get 1 255 1 0 30F N 1 41 WindingTemp2 DegC INT 2 Get 1 255 1 0 30F N 1 42 WindingTemp3 DegC INT 2 Get 1 255 1 0 30F N 1 43 WindingTemp4 DegC INT 2 Get 1 255 1 0 30F N 1 44 WindingTemp5 DegC INT 2 Get 1 255 1 0 30F N 1 45 Wind...

Page 7: ...INT 2 Get 0 65535 1 0 30F N 25 86 TotalRunTime Hour UINT 2 Get 0 65535 1 0 30F N 25 87 TotalTripsCnt UINT 2 Get 0 65535 1 0 30F N 25 88 GndFaultTripsCnt UINT 2 Get 0 255 1 0 30F N 26 89 I2TtripsCnt UINT 2 Get 0 255 1 0 30F N 26 90 InstOCurTripsCnt UINT 2 Get 0 255 1 0 30F N 26 91 JamTripsCnt UINT 2 Get 0 255 1 0 30F N 26 92 UndrLdTripsCnt UINT 2 Get 0 255 1 0 30F N 26 93 PhsUnbalTripsCnt UINT 2 Ge...

Page 8: ...teM Mnth UINT 2 Get 1 12 1 0 30F N 27 126 AcLastResetDateD Day UINT 2 Get 1 31 1 0 30F N 27 127 AcLastResetDateY Year UINT 2 Get 2001 2099 1 0 30F N 27 128 AcLastResetTimeH Hour UINT 2 Get 0 23 1 0 30F N 27 129 AcLastResetTimeM Min UINT 2 Get 0 59 1 0 30F N 27 130 AcLastResetTimeS Sec UINT 2 Get 0 59 1 0 30F N 27 131 FlagsBitsB15B00 WORD 2 Get 0 65535 1 0 3C8 132 FlagsBitsB31B16 WORD 2 Get 0 65535...

Page 9: ...ts assembly instance 151 temperatures Use the hex value of the desired instance to select the appropriate assembly Next send the explicit message to the DPONI to change the polled assembly instance Produced Assembly Instances There are eight producing assemblies supported for the MP 3000 as indicated in the following table Table B 1 Produced Assembly Instances Inst Assembly Name Number of Data Byt...

Page 10: ...mp4 43 2 6 WindingTemp5 44 2 7 WindingTemp6 45 2 8 MotorBrngTemp1 46 2 9 MotorBrngTemp2 47 2 10 LoadBrngTemp1 48 2 11 LoadBrngTemp2 49 2 12 AuxiliaryTemp 50 2 Table B 4 Format of Assembly Instance 152 98h Currents Word Member Parameter Inst Data Bytes 0 Status 32 2 1 StatusByte 33 2 2 CurrentPhA 51 2 3 CurrentPhB 52 2 4 CurrentPhC 53 2 5 CurrentGnd 54 2 6 CurrentAvg3Ph 55 2 Table B 5 Format of Ass...

Page 11: ...astResetDateY 81 2 20 MoLastResetTimeH 82 2 21 MoLastResetTimeM 83 2 22 MoLastResetTimeS 84 2 23 TotalStartsCnt 85 2 24 TotalRunTime 86 2 25 TotalTripsCnt 87 2 Table B 7 Format of Assembly Instance 155 Motor Trip Counts Word Member Parameter Inst Data Bytes 0 Status 32 2 1 StatusByte 33 2 2 GndFaultTripsCnt 88 2 3 I2TtripsCnt 89 2 4 InstOCurTripsCnt 90 2 5 JamTripsCnt 91 2 6 UndrLdTripsCnt 92 2 7 ...

Page 12: ...ResetDateM 125 2 15 AcLastResetDateD 126 2 16 AcLastResetDateY 127 2 17 AcLastResetTimeH 128 2 18 AcLastResetTimeM 129 2 19 AcLastResetTimeS 130 2 Table B 9 Format of Assembly Instance 157 Flags Word Member Parameter Inst Data Bytes 0 Status 32 2 1 StatusByte 33 2 2 FlagsStatus 37 2 3 FlagsReason 38 2 4 FlagsBitsB15B00 131 2 5 FlagsBitsB31B16 132 2 6 FlagsBitsB47B32 133 2 7 FlagsBitsB63B48 134 2 C...

Page 13: ...9 EATON CORPORATION www eaton com 13 Table B 12 Data Bit Definitions Slave Actions Bit Slave Action Requested 0 ResetTripAlm 1 ResetMotrMax 2 ResetMotrTrp 3 ResetMotrAlm 4 StopTrip 5 EmrgOvrdTrip 6 RelsMajrEvnt 7 ResetHistory 8 RelsMinrEvnt 9 RelsStrtProf 10 Reserved 11 Reserved 12 Reserved 13 Reserved 14 Reserved 15 Reserved ...

Page 14: ...INT 2 Get 0 15 1 0 300 37 FlagsStatus UINT 2 Get 0 42 1 0 3C8 38 FlagsReason UINT 2 Get 0 329 1 0 3C8 39 SlaveActions WORD 2 Set Get 0 65535 1 0 3D0 40 WindingTemp1 DegC INT 2 Get 1 255 1 0 30F N 1 41 WindingTemp2 DegC INT 2 Get 1 255 1 0 30F N 1 42 WindingTemp3 DegC INT 2 Get 1 255 1 0 30F N 1 43 WindingTemp4 DegC INT 2 Get 1 255 1 0 30F N 1 44 WindingTemp5 DegC INT 2 Get 1 255 1 0 30F N 1 45 Win...

Page 15: ...INT 2 Get 0 23 1 0 30F N 25 86 MoLastResetTimeM Min UINT 2 Get 0 59 1 0 30F N 25 87 MoLastResetTimeS Sec UINT 2 Get 0 59 1 0 30F N 25 88 TotalStartsCnt UINT 2 Get 0 65535 1 0 30F N 25 89 TotalRunTime Hour UINT 2 Get 0 65535 1 0 30F N 25 90 TotalTripsCnt UINT 2 Get 0 65535 1 0 30F N 25 91 GndFaultTripsCnt UINT 2 Get 0 255 1 0 30F N 26 92 I2TtripsCnt UINT 2 Get 0 255 1 0 30F N 26 93 InstOCurTripsCnt...

Page 16: ...Hour UINT 2 Get 0 23 1 0 30F N 27 145 AcLastResetTimeM Min UINT 2 Get 0 59 1 0 30F N 27 146 AcLastResetTimeS Sec UINT 2 Get 0 59 1 0 30F N 27 147 FlagsBitsB15B00 WORD 2 Get 0 65535 1 0 3C8 148 FlagsBitsB31B16 WORD 2 Get 0 65535 1 0 3C8 149 FlagsBitsB47B32 WORD 2 Get 0 65535 1 0 3C8 150 FlagsBitsB63B48 WORD 2 Get 0 65535 1 0 3C8 151 FlagsBitsB79B64 WORD 2 Get 0 65535 1 0 3C8 152 DiscreteInputs WORD...

Page 17: ...88 Reserved 189 Reserved 190 NetEnergyVarHr VH 1 DINT 4 Get 2 31 2 31 1 1 0 30F N 8 191 EnergyVAHr Vah 1 UDINT 4 Get 0 2 32 1 1 0 30F N 8 192 EnergyUnitsId 1 UINT 2 Get 3 6 1 0 30F N 8 193 EnLastResetDateM Mnth UINT 2 Get 1 12 1 0 30F N 8 194 EnLastResetDateD Day UINT 2 Get 1 31 1 0 30F N 8 195 EnLastResetDateY Year UINT 2 Get 2001 2099 1 0 30F N 8 196 EnLastResetTimeH Hour UINT 2 Get 0 23 1 0 30F...

Page 18: ...s 22 Get 159 Power 62 Get 160 Energy 30 Get 161 Reserved Get 162 Reserved Get 163 Reserved Get 164 Reserved Get Table D 2 Format of Assembly Instance 150 96h Status Word Member Parameter Inst Data Bytes 0 Status 32 2 1 StatusByte 33 2 Table D 3 Format of Assembly Instance 151 97h Temperatures Word Member Parameter Inst Data Bytes 0 Status 32 2 1 StatusByte 33 2 2 WindingTemp1 40 2 3 WindingTemp2 4...

Page 19: ...9Ah Motor Maximums Word Member Parameter Inst Data Bytes 0 Status 32 2 1 StatusByte 33 2 2 MaxStartCurrent 64 2 3 MaxRunCurrent 65 2 4 MaxPhaseUnbal 66 2 5 MaxWindingTemp 67 2 6 MaxMotBrngTemp 68 2 7 MaxLoadBrngTemp 69 2 8 MinLGVoltage 70 2 9 MaxLGVoltage 71 2 10 MaxVltPhaseUnbal 72 2 11 MxLastResetDateM 73 2 12 MxLastResetDateD 74 2 13 MxLastResetDateY 75 2 14 MxLastResetTimeH 76 2 15 MxLastReset...

Page 20: ...nt 97 2 9 MotrBrngTripsCnt 98 2 10 LoadBrngTripsCnt 99 2 11 AuxTempTripsCnt 100 2 12 PhsRvrsTripsCnt 101 2 13 IncmSeqTripsCnt 102 2 14 RemoteTripsCnt 103 2 15 DiffrntlTripsCnt 104 2 16 StrtPerTTripsCnt 105 2 17 TBtnStrtTripsCnt 106 2 18 XsitionTripsCnt 107 2 19 TripBypsTripsCnt 108 2 20 ZeroSpdSTripsCnt 109 2 21 VltUnbalTripsCnt 110 2 22 UndrFreqTripsCnt 111 2 23 OverFreqTripsCnt 112 2 24 OverVolt...

Page 21: ...OverFreqAlrmsCnt 137 2 17 OverVoltAlrmsCnt 138 2 18 UndrVoltAlrmsCnt 139 2 19 UndrPwrAlrmsCnt 140 2 20 AcLastResetDateM 141 2 21 AcLastResetDateD 142 2 22 AcLastResetDateY 143 2 23 AcLastResetTimeH 144 2 24 AcLastResetTimeM 145 2 25 AcLastResetTimeS 146 2 Table D 9 Format of Assembly Instance 157 9Dh Flags Word Member Parameter Inst Data Bytes 0 Status 32 2 1 StatusByte 33 2 2 FlagsStatus 37 2 3 F...

Page 22: ...wrPhB 171 4 9 RealPwrPhC 172 4 10 ReactPwrPhA 173 4 11 ReactPwrPhB 174 4 12 ReactPwrPhC 175 4 13 ApparPwrPhA 176 4 14 ApparPwrPhB 177 4 15 ApparPwrPhC 178 4 16 PwrFactorApprPhA 182 2 17 PwrFactorApprPhB 183 2 18 PwrFactorApprPhC 184 2 19 20 21 22 23 24 Table D 12 Format of Assembly Instance 160 Energy Word Member Parameter Inst Data Bytes 0 Status 32 2 1 StatusByte 33 2 2 NetEnergyWattHr 187 4 3 N...

Page 23: ...bly Name Number of Data Bytes Access 100 SlaveActions 2 Set 101 Reserved Set 102 Reserved Set 103 Reserved Set Table D 14 Format of Assembly Instance 100 Slave Actions Word Member Parameter Inst Data Bytes 0 SlaveActions 39 2 Table D 15 Data Bit Definitions Slave Actions Bit Slave Action Requested 0 ResetTripAlm 1 ResetMotrMax 2 ResetMotrTrp 3 ResetMotrAlm 4 StopTrip 5 EmrgOvrdTrip 6 RelsMajrEvnt ...

Page 24: ...eaton com Internet www eaton com Eaton Corporation Electrical Group 1000 Cherrington Parkway Moon Township PA 15108 United States 877 ETN CARE 877 386 2273 eaton com 2009 Eaton Corporation All Rights Reserved Printed in USA Publication No IL17559 Rev D TBG 000257 August 2009 PowerChain Management is a registered trademark of Eaton Corporation All Other trademarks are property of their respective o...

Reviews: