Instruction Leaflet
IL17559 Rev. D
Instructions for the DeviceNet
®
Product
Effective August 2009
Operated Network Interface (DPONI)
EATON CORPORATION
www.eaton.com
22
Table D-11. Format of Assembly Instance #159 (9Fh) – Power.
Word #
Member
Parameter
Inst #
Data Bytes
0
Status 32 2
1
StatusByte
33
2
2
RealPwr3Ph 162 4
3
ReactPwr3Ph
163
4
4
ApparPwr3Ph 164 4
5
PwrFactorAppr
166
2
6
Frequency 167 2
7
RealPwrPhA
170
4
8
RealPwrPhB 171 4
9
RealPwrPhC
172
4
10
ReactPwrPhA 173 4
11
ReactPwrPhB
174
4
12
ReactPwrPhC 175 4
13
ApparPwrPhA
176
4
14
ApparPwrPhB 177 4
15
ApparPwrPhC
178
4
16
PwrFactorApprPhA 182
2
17
PwrFactorApprPhB
183
2
18
PwrFactorApprPhC 184
2
19
20
21
22
23
24
Table D-12. Format of Assembly Instance #160 – Energy.
Word #
Member
Parameter
Inst #
Data Bytes
0
Status 32 2
1
StatusByte
33
2
2
NetEnergyWattHr 187
4
3
NetEnergyVarHr
190
4
4
EnergyVAHr 191 4
5
EnergyUnitsId
192
2
6
EnLastResetDateM 193
2
7
EnLastResetDateD
194
2
8
EnLastResetDateY 195
2
9
EnLastResetTimeH
196
2
10
EnLastResetTimeM 197
2
11
EnLastResetTimeS
198
2