Instructions for the DeviceNet
®
Product
Instruction Leaflet
IL17559 Rev. D
Operated Network Interface (DPONI)
Effective August 2009
EATON CORPORATION
www.eaton.com
23
Consumed Assembly Instances
There is one consuming assembly supported for the MP-4000 as shown in the following table.
Table D-13. Consumed Assembly Instances.
Inst #
Assembly Name
Number of
Data Bytes
Access
100
SlaveActions 2 Set
101
Reserved
-
Set
102
Reserved - Set
103
Reserved
-
Set
Table D-14. Format of Assembly Instance #100 – Slave Actions.
Word #
Member
Parameter
Inst #
Data Bytes
0
SlaveActions 39
2
Table D-15. Data Bit Definitions – Slave Actions.
Bit #
Slave Action Requested
0 ResetTripAlm
1 ResetMotrMax
2 ResetMotrTrp
3 ResetMotrAlm
4 StopTrip
5 EmrgOvrdTrip
6 RelsMajrEvnt
7 ResetHistory
8 RelsMinrEvnt
9 RelsStrtProf
10 ResetEnergy
11 ResetMtrTrp2
12 ResetMtrAlm2
13 ResetMtrMnMx
14 Reserved
15 Reserved