Effective 11/2003
Page 50
I.L. 66A7535H02
Appendix D Page D-4a
LONG
DELAY
TRIP
1st & 2nd
Meter Screens
Note 1
Data and Time Stamp
logged for each event.
Possible Events
TRIP
(Continued from D-3)
SHORT
DELAY
TRIP
1st & 2nd
Meter Screens
INST
TRIP
1st & 2nd
Meter Screens
Note 2
GROUND
FAULT
TRIP
1st & 2nd
Meter Screens
Note 4
OverVOLT
TRIP
L-L Voltage and
FREQ screens
displayed.
See Note 3
PHASE
LOSS
TRIP
1st & 2nd
Meter Screens
OVER
TEMP
TRIP
No Data
Displayed
UndrFREQ
TRIP
L-L Voltage and
FREQ screens
displayed.
See Note 3
OverFREQ
TRIP
L-L Voltage and
FREQ screens
displayed.
See Note 3
OPEN BY
COMM
No Data
Displayed
ACC BUS
TRIP
No Data
Displayed
AMPERES
OUT OF
BALANCE
1st Meter
Screens
VOLT UN-
BALANCE
TRIP
L-L Voltage and
FREQ screens
displayed.
See Note 3
PlugTRIP
No Data
Displayed
4. If IEC style,
"EARTH" will replace
"GROUND"
Note: "Meter screens" refer to those on D-2
UndrVOLT
TRIP
L-L Voltage and
FREQ screens
displayed.
See Note 3
RevPower
TRIP
Power kW screen
displayed
See Note 3
2. INST TRIP values displayed
could be less than actual fault
levels due to fast response of this
element.
1. LONG DELAY TRIP term is
used by LSIG, IEEE and IEC
curve type indicating an
overload trip.
3. Real Time data is
shown for Voltage and
Frequency. View
EventLog screen for
TRIP data.