Figure 4.8 INCOM Network with Remote Master Computer BIM
II
4.2.8 Setting TIME and DATE
In the Digitrip 1150V, dates are displayed in DD-MmmYY
format (for example, 12 Mar 98) and time is displayed in
military-style format with hours from 0 to 23. The first
screen in PGM SET\TIME is a view-only screen showing
the current time setting for the unit. The View Down button
changes screens to the DAY programming screen where
the two digit date can be adjusted with the Edit Up or Edit
Down pushbuttons. View Down then moves through the
programmable three-character MONTH abbreviation, two
digit YEAR selection, two digit HOURS, and two digit
MINUTES which are all programmed with the Edit Up and/
or Edit Down pushbuttons. Seconds are not programmable
and begin at 00 when time settings are saved. Using View
Up in the menu will move the user through the settings in
reverse order as described above
(Refer to Appendix D-18).
4.2.9 Selecting DISPLAYS
Display programming options control the screens dis-
played in the Meter Menu. Program Display is located in
the PGM SET\DISPLAY submenu. This submenu lists
twenty-two programmable screens. The first screen sets
metering for A, B, and C phase currents to AUTO or
MANUAL. The remaining twenty-one screens of various
perameters and can be set to on or off, depending on user
preference. Any settings turned to OFF will not be dis-
played when METER is selected from the Main Menu
(Refer to Appendix D-14)
.
4.2.10 System
4.2.10.1 Frequency
This setting is to reflect the power system’s operating
frequency of 50 or 60 Hertz. The factory default is 60Hz.
1
1
2
3
3
1
2
3
0 0 1
0 0 2
Cut-off Shield or connect to
unused customer
terminal -- Do not Ground.
Twisted Pair.
No. 18 AWG.
Breaker
Interface
Monitor
(BIM )
ΙΙ
Typical Mini Vac
Circuit Breaker
with Digitrip Trip Unit
3 Digit
INCOM
Address
Baud Rate
1200 or 9600
See View A
Typical IBM
Compatible
Computer
View A
(Y)
(BL)
Refer to Master Circuit Breaker Connection Diagrams in Appendix C.
Modular telephone connector, Type RJ11, supplied by user.
Ground shielding at computer BIM as shown. Where devices
are daisy-chained, interconnect shielding, but do not ground the connection.
100 ohm, ½ watt, carbon resistor required at last breaker. See T.D. 17-513.
Also insert 100 ohm resistor to terminator at CONI card (via switch on CONI).
See Appendix D-11 for programming INCOM function.
BIM version 3.20 or greater is compatible with Digitrip 1150V.
ΙΙ
ΙΙ
NOTICE
100 OHM 1/2W terminating
resistor required on network
even if network is unused
4