Factory
Settings
LONG SLOPE
LONG PU
LONG TIME
LONG MEMORY ***
SHORT SLOPE ***
SHORT PU
SHORT TIME
INST PU
GROUND PU
GROUND SLOPE
GROUND TIME
EXT GND CT RATIO
AMP UNBALANCE
AMP UNBALANCE (time)
PHASE LOSS
I2T
1.00
4.0 s
ON
FLAT
3.0
0.30 s
4.0
0.40
FLAT
0.30 s
none
OFF
10 s
OFF
MOD INV
1.00
2.0
3.0
0.30 s
4.0
0.40
FLAT
0.30 s
none
OFF
10 s
OFF
PHASE SLOPE
Pickup
PHASE TimeDial
SHORT PU
SHORT TIME
INST PU
EARTH PU
EARTH SLOPE
EARTH TIME
EXT EARTH CT RATIO
AMP UNBALANCE
AMP UNBALANCE (time)
PHASE LOSS
IEC - A
1.00
0.20
3.0
0.30 s
4.0
0.40
FLAT
0.30 s
none
OFF
10 s
OFF
LSIG ON
LSIG Current Curve
IEEE Curve
IEC Curve
DISPLAY
(6 active)
IA IB IC
AUTO
IN IG
ON
L-L VOLTAGE
ON
FwdPower
ON
PF HZ
ON
ENERGY FWD & REV
ON
(all others)
OFF
AuxReLaYs
All relays DISABLED
ALARMS
All alarms OFF
ACC BUS
Address1 Relay1 is Aux.-Aux Switch
All other addresses and relays OFF
SYSTEM
FIXED DEMAND 15 Min window
WAVEFORM CAPTURE OFF
FREQ 60Hz
Relay B,C MANUAL
INCOM
INCOM ADDRESS
100 hex
INCOM BAUD RATE
9600
EXT COMM OpenTrip
ENABLED
EXT COMM
TRIP
EXT COMM CLOSE
ENABLED
DT 910 COMM
DISABLED
*** Only available on LSIG Current Curve. On IEEE curve and IEC
curve, LONG MEMORY and SHORT I2T SLOPE settings are not available.
CURRENT Protection
VOLTAGE Protection
DISABLED
VT Primary
4800V
VT Secondary
120V
TEST
PH TEST
0.4x In
GND TEST
0.1x In
PHASE SLOPE
Pickup
PHASE TimeDial
SHORT PU
SHORT TIME
INST PU
GROUND PU
GROUND SLOPE
GROUND TIME
EXT GND CT RATIO
AMP UNBALANCE
AMP UNBALANCE (time)
PHASE LOSS