background image

Effective.June.2007

 

 

Page

RS-485 PONI

66A2070 Rev. B

Introduction

The RS-485 

P

roduct.

O

perated.

N

etwork.

I

nterface (RS-485 

PONI) is a communications device that allows Eaton’s 

Cutler-Hammer IQ Meters, IQ and MP Protective relays, and 

IQ Transfer switches to communicate over a Modbus RTU 

Network .

These host devices interface to the RS-485 PONI through 

their DB9 PONI interface connector. The host device 

provides a 24V DC voltage through the DB9 connector.

A 5-pin connector is provided for wiring to the RS-485 

network. The RS-485 PONI mounts on the rear panel of the 

host product.

Figure 1: RS-485 PONI

Product Compatibility

The following products are supported by the RS-485 PONI. 

To ensure proper operation, the firmware of the host devices 

must.be.considered .

Table 1: Firmware Compatibility

IQ Host

RS-485 V1.00 RS-485 V1.01 RS-485 V1.02

IQ Analyzer

Ver ..2 .02

Ver ..2 .02

Ver.2 .02

IQ DP-4000

Ver ..1 .04

Ver ..1 .04

Ver.1 .04

IQ Data Plus II Rev. 8B 

6/26/95

Rev. 8B 

6/26/95

Rev. 8B 

6/26/95

MP-3000

Ver ..1 .08

Ver ..1 .08

Ver ..1 .08

ATC-400

Ver ..1 .40

Ver ..1 .40

Ver ..1 .40

IQ Transfer II

Ver ..4 .5

Ver ..4 .5

Ver ..4 .5

MP4000

Not.Supported Not.Supported Ver ..1 .06

Features

The RS-485 PONI provides the following features:

• 

A means of communicating using the standard Modbus 

RTU Protocol.

• 

Various baud rates are selectable for networking flexibility.

• 

Addresses 0-99 are selectable by way of two rotary 

switches.

• 

Status light provides indication of proper operation and 

also functions as an error indicator light.

• 

Data in IEEE Floating Point and fixed-point formats.

• 

Host interface communications indicator light.

• 

RS-485 TX/RX indicator lights.

• 

Termination resistor is DIP switch-selectable.

Hardware Installation

The RS-485 PONI is designed to be installed, operated 

and.maintained.by.adequately.trained.personnel ..

These instructions do not cover all details, variations 

or combinations of the equipment, its storage, delivery, 

installation, checkout, safe operation or maintenance.

NOTE: De-energize the device to which the RS-485 

PONI will be attached or wired; otherwise, erroneous 

operation or damage to equipment could occur.

The installer must comply with the National Electric Code 

and local codes or regulations, as well as safety practices, 

for this class of equipment.

.  Ensure that mounting screws and adapter bracket for the 

RS-485 PONI have been included.

2.  Consult the Instruction Leaflet (IL) mounting instructions 

for each RS-485 PONI-compatible host device.

The following sections – 3a through 3f – explain common 

examples of mounting instructions.

3a. Mounting to an IQ Analyzer

Disconnect power to the IQ Device. Many applications will 

have a separately mounted power module. In this case, 

mount the RS-485 PONI to the IQ Device using the stacking 

screws.provided .

Summary of Contents for Cutler-Hammer

Page 1: ...66A2070 Rev B For more information visit www eaton com Effective June 2007 Instruction Leaflet 66A2070 INSTRUCTIONS FORTHE RS 485 PONI Cutler Hammer...

Page 2: ...ommunications Protocol 5 Function Codes 5 Control of Host Product 5 Register Access Configurations 6 Energy Format 6 Exception Codes 6 INCOM Protocols 6 Supported Diagnostic Sub Functions 6 Troublesho...

Page 3: ...ud rates are selectable for networking flexibility Addresses 0 99 are selectable by way of two rotary switches Status light provides indication of proper operation and also functions as an error indic...

Page 4: ...00 s style s 66D2040Gxx do not have external power supply fuses These new style meters do not require the Amp fuse included 3b Mounting to the IQ DP 4000 or IQ Data Plus II Mounting to the IQ DP 4000...

Page 5: ...the ATC 400 Attach the ribbon cable from the RS 485 PONI to the receptacle of the IQ device as shown in Figure 3 on Page 2 and firmly tighten the screws on the plug lock assembly 3f Mounting to an IQ...

Page 6: ...485 PONI to host devices where the mounting surfaces are tied to the chassis ground the Chassis ground connection on the RS 485 PONI should not be connected Using the metal screws provided will ensur...

Page 7: ...NI to an host product is listed in Figure 11 on Page 6 The Modbus master reads the INCOM product response to a pass through query using either function code 03 or 04 beginning at register 424833 61001...

Page 8: ...ction in the query is not supported by the RS 485 PONI exception code 01 is returned in the response If the data object register is illegal exception code 02 is returned in the response If the data va...

Page 9: ...PONI address Error Detection Using Status LED If the status light blinks twice in rapid ON OFF cycles followed by a 1 5 second OFF period this is an indication that the product is not being recognize...

Page 10: ...011 1998 Radiated and Conducted Emissions System Ratings Operating Temperature 20 C to 60 C Storage Temperature 20 C to 70 C Altitude 3 048 m 10 000 ft Operating Humidity 5 to 90 max non condensing En...

Page 11: ...6177 1220 1820 10 peak IB demand A 404643 406179 1222 1822 10 peak IC demand A 404645 406181 1224 1824 10 peak IG demand A 404647 406183 1226 1826 10 peak IN demand A 404649 406185 1228 1828 10 power...

Page 12: ...727 406263 1276 1876 1 x x lead KVARh 404729 406265 1278 1878 1 x x lag KVARh 404731 406267 127A 187A 1 x x net KVARh 404733 406269 127C 187C 1 x x x Energy 32 bit apparent KVAh 404735 406271 127E 187...

Page 13: ...4 Device Alarmed 21 Phase C Alarm 5 Device On 22 Neutral Alarm 6 Device Off 23 Ground Earth Alarm 7 Device Ready 24 Phase AB Alarm 8 Device Starting 25 Phase BC Alarm 9 Device Running 26 Phase CA Alar...

Page 14: ...0 Secondary status unknown Reserved 9 27 1 Secondary status is not applicable 2 Device in program mode 3 Device in test mode 4 Device disabled 5 Device disarmed 28 Product Specific Code 28 6 Controlle...

Page 15: ...izing 92 Multiple External Conditions 131 Starts Per Hour 93 Motor Bearing Temperature 132 Preferred Source 94 Load Bearing Temperature 133 Plant Exerciser 95 Auxiliary Temperature 134 Neutral Ground...

Page 16: ...y Moon Township PA 15108 4312 USA www eaton com 2005 2007 Eaton Corporation All Rights Reserved Publication No 66A2070 Rev B June 2007 Cutler Hammer Contact Information Power Quality Technical Support...