Name

Numeric

Units

IEEE-

754 

floating

 

point

Fixed 

point

IEEE-

754 

floating

 

(hex)

Fixed 

point 

(hex)

FP

 scale  factor

DP-4000

IQ 

Analyzer IQ Data 

Plus

IQ 

Transfer 

II

MP

 3000

ATC-400

MP

 4000

source1 

VAB

V

404699 406235

25A

85A

10

x

x

VBC

V

404701 406237

125C

185C 10

x

x

VCA

V

404703 406239

125E

185E

10

x

x

freq

Hz

404705 406241

1260

1860

10

x

x

source 2 

VAB

V

404707 406243

1262

1862

10

x

x

VBC

V

404709 406245

1264

1864

10

x

x

VCA

V

404711 406247

1266

1866

10

x

x

freq

Hz

404713 406249

1268

1868

10

x

x

x

power

power (real 3 ph)

W

404715 406251

26A

86A

1

x

x

x

power factor

pf

n/a

404717 406253

126C

186C 100 x

x

x

prod ID

prod.ID

n/a

404719 406255

126E

186E

1

x

x

x

x

x

x

x

frequency

freq

Hz

404721 406257

1270

1870

100 x

x

x

real energy

forward

KWh

404723 406259

1272

1872

1

x

x

reverse

KWh

404725 406261

1274

1874

1

x

x

reactive energy  

(32-bit)

net

KWh

404727 406263

1276

1876

1

x

x

lead

KVARh

404729 406265

1278

1878

1

x

x

lag

KVARh

404731 406267

27A

87A

1

x

x

net

KVARh

404733 406269

127C

187C 1

x

x

x

Energy  

(32-bit)

apparent

KVAh

404735 406271

127E

187E

1

x

x

x

Motor 

phase unbalance

%

404737 406273

1280

1880

100

x

x

thermal capacity

%

404739 406275

1282

1882

100

x

x

Temperature

winding 

°C

404741 406277

1284

1884

1

x

x

winding 2

°C

404743 406279

1286

1886

1

x

x

winding 3

°C

404745 406281

1288

1888

1

x

x

winding 4

°C

404747 406283

28A

88A

1

x

x

winding 5

°C

404749 406285

128C

188C 1

x

x

winding 6

°C

404751 406287

128E

188E

1

x

x

motor bearing 

°C

404753 406289

1290

1890

1

x

x

motor bearing 2

°C

404755 406291

1292

1892

1

x

x

load bearing 

°C

404757 406293

1294

1894

1

x

x

load bearing 2

°C

404759 406295

1296

1896

1

x

x

auxiliary

°C

404761 406297

1298

1898

1

x

x

real

energy  

(64-bit)

forward

Wh

406305

8A0

1

x

x

reverse

Wh

406309

8A4

1

x

x

net

Wh

406313

8A8

1

x

x

x

reactive energy  

(64-bit)

lead

VARh

406317

8AC

1

x

x

lag

VARh

406321

8B0

1

x

x

net

VARh

406325

8B4

1

x

x

x

Energy  

(64-bit)

apparent

VAh

406329

8B8

1

x

x

x

Table 3: Modbus Register Maps (Continued)

Summary of Contents for Cutler-Hammer

Page 1: ...66A2070 Rev B For more information visit www eaton com Effective June 2007 Instruction Leaflet 66A2070 INSTRUCTIONS FORTHE RS 485 PONI Cutler Hammer...

Page 2: ...ommunications Protocol 5 Function Codes 5 Control of Host Product 5 Register Access Configurations 6 Energy Format 6 Exception Codes 6 INCOM Protocols 6 Supported Diagnostic Sub Functions 6 Troublesho...

Page 3: ...ud rates are selectable for networking flexibility Addresses 0 99 are selectable by way of two rotary switches Status light provides indication of proper operation and also functions as an error indic...

Page 4: ...00 s style s 66D2040Gxx do not have external power supply fuses These new style meters do not require the Amp fuse included 3b Mounting to the IQ DP 4000 or IQ Data Plus II Mounting to the IQ DP 4000...

Page 5: ...the ATC 400 Attach the ribbon cable from the RS 485 PONI to the receptacle of the IQ device as shown in Figure 3 on Page 2 and firmly tighten the screws on the plug lock assembly 3f Mounting to an IQ...

Page 6: ...485 PONI to host devices where the mounting surfaces are tied to the chassis ground the Chassis ground connection on the RS 485 PONI should not be connected Using the metal screws provided will ensur...

Page 7: ...NI to an host product is listed in Figure 11 on Page 6 The Modbus master reads the INCOM product response to a pass through query using either function code 03 or 04 beginning at register 424833 61001...

Page 8: ...ction in the query is not supported by the RS 485 PONI exception code 01 is returned in the response If the data object register is illegal exception code 02 is returned in the response If the data va...

Page 9: ...PONI address Error Detection Using Status LED If the status light blinks twice in rapid ON OFF cycles followed by a 1 5 second OFF period this is an indication that the product is not being recognize...

Page 10: ...011 1998 Radiated and Conducted Emissions System Ratings Operating Temperature 20 C to 60 C Storage Temperature 20 C to 70 C Altitude 3 048 m 10 000 ft Operating Humidity 5 to 90 max non condensing En...

Page 11: ...6177 1220 1820 10 peak IB demand A 404643 406179 1222 1822 10 peak IC demand A 404645 406181 1224 1824 10 peak IG demand A 404647 406183 1226 1826 10 peak IN demand A 404649 406185 1228 1828 10 power...

Page 12: ...727 406263 1276 1876 1 x x lead KVARh 404729 406265 1278 1878 1 x x lag KVARh 404731 406267 127A 187A 1 x x net KVARh 404733 406269 127C 187C 1 x x x Energy 32 bit apparent KVAh 404735 406271 127E 187...

Page 13: ...4 Device Alarmed 21 Phase C Alarm 5 Device On 22 Neutral Alarm 6 Device Off 23 Ground Earth Alarm 7 Device Ready 24 Phase AB Alarm 8 Device Starting 25 Phase BC Alarm 9 Device Running 26 Phase CA Alar...

Page 14: ...0 Secondary status unknown Reserved 9 27 1 Secondary status is not applicable 2 Device in program mode 3 Device in test mode 4 Device disabled 5 Device disarmed 28 Product Specific Code 28 6 Controlle...

Page 15: ...izing 92 Multiple External Conditions 131 Starts Per Hour 93 Motor Bearing Temperature 132 Preferred Source 94 Load Bearing Temperature 133 Plant Exerciser 95 Auxiliary Temperature 134 Neutral Ground...