DS
P-01
f-max
Sets the upper limit for the speed of the motor.
This can be set to any value between “f-min” and 5x the “motor nom frequency”.
When “Motor Nom Frequency” (P-09) is changed, P-01 is set to the value of P-09.
”Motor Nom Speed” (P-10) = 0, the maximum speed limit will be displayed in Hz.
”Motor Nom Speed” (P-10) > 0, the maximum speed limit will be displayed in rpm.
50.0 Hz
P-02
f-min
Sets the lower limit for the speed of the motor
This can be set to any value between 0 and “f-max” (P-01). When “Motor Nom
Frequency” (P-09) is changed, P-01 is set to zero.
0.0 Hz
…