5 Parameters
5.3 “Extended” parameter group
DC1…E1 Variable Frequency Drives
11/16 MN040022EN
www.eaton.com
45
P-53
Action@Communication
Loss
0
4
Device reaction after occuring of “Communication
Loss”. Possibilities device dependent
Drive reaction after SWD master communication
loss. Master communication loss delay time is set
by ”Modbus RTU0 COM Timeout” (P-36)
0: No reaction, continue work
1: Set warning, continue work
2: stop (if ramp enabled)
3: quick stop
4: coast stop
0
P-54
RO1 Hysteresis
0.00 %
100.00 %
Hysteresis for relay output 1
This parameter defines a lower reaction threshold
level in case P-18 is set to 4, …, 7.
Threshold level = limit (P-19) - hysteresis (P-54)
P-18 = 4 or 5: output will be logic 1 if the value
≧
limit , output will be logic 0 if value < level
P-18 = 6 or 7: output will be logic 0 if the value
≧
limit, output will be logic 1 if value < level
0.00 %
P-55
RO1 Switch-On Delay
0.0 s
250.0 s
Delay time before the Relay switches from logic 0
to logic 1.
0.0 s
P-56
Reserved Parameter
0.0 s
250.0 s
Reserved Parameter
0.0 s
P-57
Reserved Parameter
0.0 s
250.0 s
Reserved Parameter
0.0 s
P-58
Reserved Parameter
0.0 s
250.0 s
Reserved Parameter
0.0 s
P-59
Reserved Parameter
0.0 s
250.0 s
Reserved Parameter
0.0 s
Parameter
Designation
Min. value
Max. value
Description
DS