3 Control signal terminals
3.2 Configuration of the control signal terminals
16
DC1…E1 Variable Frequency Drives
11/16 MN040022EN
www.eaton.com
3.2 Configuration of the control signal terminals
3.2.1 P-12 = 0: Terminal-based operation
Table 9: P-12 = 0: Terminal-based operation
The setpoint and the control commands are set/issued via terminals.
P-15
DI1
(terminal 2)
DI2
(terminal 3)
DI3/AI2
(terminal 4)
DI4/AI1
(terminal 6)
0
START
DIR
Select AI1 REF/f-Fix1
AI1 REF
1
FWD
Select AI1 REF/f-Fix
Select f-Fix Bit0
AI1 REF
2
FWD
Select f-Fix Bit0
Select f-Fix Bit1
Select f-Fix/f-max
3
FWD
Select AI1 REF/f-Fix1
EXTFLT
AI1 REF
4
FWD
Select AI1 REF/AI2 REF
AI2 REF
AI1 REF
5
FWD
REV
Select AI1 REF/f-Fix1
AI1 REF
6
START
DIR
EXTFLT
AI1 REF
7
FWD
REV
EXTFLT
AI1 REF
8
START
DIR
Select f-Fix Bit0
Select f-Fix Bit1
9
FWD
REV
Select f-Fix Bit0
Select f-Fix Bit1
10
Pulse FWD (NO)
Pulse STOP (NC)
Select AI1 REF/f-Fix1
AI1 REF
11
Pulse FWD (NO)
Pulse STOP (NC)
Pulse REV (NO)
AI1 REF
12
FWD
Select t-dec/t-QuickDec
Select AI1 REF/f-Fix1
AI1 REF
13
FWD
Select f-Fix Bit0
EXTFLT
Select f-Fix Bit1
14
Pulse FWD (NO)
Pulse STOP (NC)
Pulse REV (NO)
Select DIG REF/f-Fix1
15
FWD
Select f-Fix4/AI1 REF
Select Fire Mode/Normal OP
AI1 REF
16
FWD
Select f-Fix4/f-Fix2
Select Fire Mode/Normal OP
DIR
17
FWD
Select f-Fix Bit0
Select Fire Mode/Normal OP
Select f-Fix Bit1
Summary of Contents for Cutler Hammer PowerXL DC1 E1 Series
Page 4: ...II...