5 Parameters
5.3 “Extended” parameter group
DC1…E1 Variable Frequency Drives
11/16 MN040022EN
www.eaton.com
41
P-32
t-DCBrake@Stop
0.0 s
25.0 s
Duration of DC braking at Stop and before Start.
Setting “0” disables DC braking. The braking level
is set with P-68
0.0 s
DCBrake
0
2
Sets the instances when DC braking is enabled.
0: DC braking on Stop
1: DC braking before Start
2: DC braking before Start and on Stop
0
P-33
Spin Start Enable
0
2
Spin Start Enable
Enables spin start, where the drive starts from the
detected motor speed. A short start delay is
possible if the rotor is stationary.
Recommended for applications where the motor
spins when applying the FWD/REV signal to the
drive (high inertia loads, fans ...)
0: Spin start disabled
1: Spin start enabled
2: Spin start enabled on trip, brown our coast to
stop (P-05 = 1)
Hint:
The setting of P-33 will be adopted at a change of
P-13 (P-33 = 0 when P-13 = 0 or 1, P-33 = 2 when
P-13 = 2)
0
P-34
Brake Chopper
0
4
Enable Brake Chopper
Enables Brake Chopper on sizes FS2 up to FS4.
Software protection can be selected for brake
resistors with a 200 W rating.
0: Disabled
1: Enabled with software protection
2: Enabled without software protection
3: Enabled during speed reference change with
software protection
4: Enabled during speed reference change without
software protection
Remark:
This parameter can only be set to a value > 0 on
drives sizes FS2 and FS3. Size FS1 does not have a
brake chopper inside the drive.
0
P-35
AI1 Gain
0.00 %
2000.00%
Scaling of the Analog Input 1
Output value = Input value * Scaling.
Example: P-16 = 0…10 V, P-35 = 200 %: at 5 V the
motor turns with max speed (P-01) (5 V * 200 % =
10 V)
In slave mode (P-12 = 14) the slave speed is scaled
with P-35.
100.00 %
Parameter
Designation
Min. value
Max. value
Description
DS