Effective 1/98
Page 26
I.B. CBE-IQ01
SECTION 5:
OPERATION
5.1 OPERATION
REFER ALSO TO IQ DEVICE INSTRUCTION BOOKS.
REFER TO INSTRUCTION BOOK TD17530 IF YOUR
ENCLOSURE IS EQUIPPED WITH AN IQ ANALYZER.
REFER TO INSTRUCTION BOOK TD17548 IF YOUR
ENCLOSURE IS EQUIPPED WITH AN IQ DP-4000.
REFER TO INSTRUCTION BOOKS FOR THE
UNINTERRUPTABLE POWER SUPPLY AND THE ARII
ADDRESSABLE RELAY WHEN YOUR UNIT IS
EQUIPPED WITH THESE DEVICES.
The Enclosed IQ is equipped with a two-position ON/
OFF switch to enable switching voltage on and off to the
IQ device. This switch is marked SERVICE
DISCONNECT.
Enclosed IQ units supplied with Separate Power Source
Modules on the IQ devices are also equipped with a two-
position ON/OFF switch to enable switching control
power on and off to the IQ device. This switch is marked
CONTROL POWER DISCONNECT.
The terminal blocks for the current circuits are short-
circuit type. Shorting screws are included.
THE DISCONNECT SWITCHES IN THIS UNIT
DISCONNECT CONTROL OR SENSING VOLTAGE TO
THE IQ METER. WHEN THESE DISCONNECTS ARE
IN THE 'OFF' POSITION, THE CURRENT
TRANSFORMER CIRCUIT, FUSES, WIRING,
RECEPTACLE, ARII AND INPUT/OUTPUTS ARE
ENERGIZED. A DISCONNECTING MEANS AND
UPSTREAM PROTECTION SHOULD BE INSTALLED
FOR ALL CIRCUITS. A SHORT CIRCUIT TYPE
TERMINAL BLOCK IS PROVIDED FOR THE
CURRENT TRANSFORMER CIRCUIT.
Summary of Contents for Cutler-Hammer Enclosed IQ
Page 1: ...I B CBE IQ01 Instruction Leaflet for Cutler Hammer Enclosed IQ...
Page 15: ...Effective 1 98 I B CBE IQ01 Page 15 Figure 7 Catalog Numbers P PONI option...
Page 16: ...Effective 1 98 Page 16 I B CBE IQ01 Figure 8 Catalog Numbers U UPS option...
Page 17: ...Effective 1 98 I B CBE IQ01 Page 17 Figure 9 Catalog Numbers A ARII option...
Page 24: ...Effective 1 98 Page 24 I B CBE IQ01 Figure 23 DP 4000 I O Figure 22 Analyzer I O...
Page 25: ...Effective 1 98 I B CBE IQ01 Page 25 Figure 25 ARII Relay Option Figure 24 IPONI module option...