I.B. CBE-IQ01

Page 7

SECTION 4:
INSTALLATION AND WIRING

4.1 GENERAL

Enclosed IQ devices are factory wired and tested.
Installation requires solidly mounting the enclosed unit
and connecting field wiring. ALL FIELD WIRING
SHOULD BE #14 AWG MINIMUM.  Included in this
booklet are diagrams of the factory wiring and various
field wiring options. Review and understand the
appropriate diagrams for the catalog number of the unit
you have ordered.

4.2 MOUNTING LOCATION

Choose a location that offers a flat, rigid mounting
surface capable of supporting the weight of the
equipment. Units without an uninterruptable power
supply will weigh 82 lbs (47 kg) maximum. Units
equipped with an uninterruptable power supply will
weigh 102 lbs (37.5 kg) maximum. Mount the equipment
in a suitable environment. These enclosures are
designed for either NEMA 3R or NEMA 12
environments. The catalog number identifies the
enclosure. If there are any doubts as to location
suitability, discuss them with your Cutler-Hammer
representative. Check to make certain that there are no
pipes, wires, or other mounting hazards in the immediate
mounting area that could create a problem. Carefully
remove all packing material from the unit. Even though
an equipment inspection was made when the equipment
was received, make another careful inspection of the
enclosure and the devices inside as packing material is
removed. Be especially alert for distorted metal, loose
wires, or damaged components.

4.3  MOUNTING PROCEDURE

The enclosures are provided with four elongated
mounting holes, two at the top mounting flange and two
at the bottom.

CAUTION

EXTREME CARE SHOULD BE TAKEN TO PROTECT
THE EQUIPMENT FROM DRILL CHIPS, FILINGS,
AND OTHER CONTAMINANTS WHEN MAKING THE
WIRE ENTRY HOLES AND MOUNTING THE
ENCLOSURE TO PREVENT COMPONENT DAMAGE
OR A FUTURE MALFUNCTION.

IF YOUR EQUIPMENT WAS ORDERED WITH THE
UNINTERRUPTABLE POWER SUPPLY OPTION, IT
WAS SHIPPED SEPARATELY. IT MUST REMAIN IN
AN UPRIGHT ORIENTATION. PLACE THE UPS ON
ITS MOUNTING BRACKET AFTER THE ENCLOSURE
HAS BEEN INSTALLED.

STEP 1:  Install required mounting bolt anchors and the

two upper mounting bolts in the mounting
surface.

STEP 2: Gently lift the enclosure and guide the elon-

gated holes in the upper mounting flange over
the  upper mounting bolts, but do not com-
pletely tighten the bolts.

STEP 3: While still supporting the enclosure, install the

two lower mounting bolts in the lower mounting
flange, but do not completely tighten. Use
shims, if required, to prevent deformation of the
enclosure when tighting the bolts, if the mount-
ing surface is distorted.

STEP 4: Tighten all four mounting bolts after any

required shimming is completed.

4.4  WIRING

WARNING

CONTROL WIRING MAY HAVE VOLTAGE PRESENT
THAT CAN CAUSE SEVERE PERSONAL INJURY OR
DEATH. DE-ENERGIZE ALL CONDUCTORS BEFORE
BEGINNING TO PERFORM ANY WIRING ACTIVITY
TO OR WITHIN THE ENCLOSED IQ DEVICE.

THE DISCONNECT SWITCHES IN THIS UNIT
DISCONNECT CONTROL OR SENSING VOLTAGE TO
THE IQ METER. WHEN THESE DISCONNECTS ARE
IN THE 'OFF' POSITION, THE CURRENT
TRANSFORMER CIRCUIT, FUSES, WIRING,
RECEPTACLE, ARII AND INPUT/OUTPUTS ARE
ENERGIZED. A DISCONNECTING MEANS AND
UPSTREAM PROTECTION SHOULD BE INSTALLED
FOR ALL CIRCUITS. A SHORT CIRCUIT TYPE
TERMINAL BLOCK IS PROVIDED FOR THE
CURRENT TRANSFORMER CIRCUIT.

A DEVICE EQUIPPED WITH A SEPARATE SOURCE
POWER SUPPLY MODULE CAN BE WIRED FOR 96-

Summary of Contents for Cutler-Hammer Enclosed IQ

Page 1: ...I B CBE IQ01 Instruction Leaflet for Cutler Hammer Enclosed IQ...

Page 2: ...NAL INJURY FOLLOW PROPER INSTALLATION OPERATION AND MAINTENANCE PROCEDURES TO AVOID THESE VOLTAGES ALL POSSIBLE CONTINGENCIES WHICH MAY ARISE DURING INSTALLATION OPERATION OR MAINTENANCE AND ALL DETAI...

Page 3: ...2 1 CATALOG NUMBER IDENTIFICATION Page 5 2 2 CATALOG NUMBER EXAMPLE Page 5 SECTION 3 RECEIVING HANDLING AND STORAGE 3 1 RECEIVING AND HANDLING Page 6 3 2 STORAGE Page 6 SECTION 4 INSTALLATION AND WIRI...

Page 4: ...ut not limited to damage or loss of use of equipment plant or power system cost of capital loss of power additional expenses in the use of existing power facilities or claims against the purchaser or...

Page 5: ...IQ ANALYZER WITH SEPARATE SOURCE POWER MODULE AND GRAPHICS DISPLAY IQA6230 IQ ANALYZER WITH SELF POWERED POWER MODULE AND GRAPHICS DISPLAY IQDP4010 IQ DP 4000 WITH SEPARATE SOURCE POWER MODULE IQDP40...

Page 6: ...ugh handling and or external damage that occurred during transportation Record any external and internal damage for reporting to the transportation carrier and Cutler Hammer once a thorough inspection...

Page 7: ...and two at the bottom CAUTION EXTREME CARE SHOULD BE TAKEN TO PROTECT THE EQUIPMENT FROM DRILL CHIPS FILINGS AND OTHER CONTAMINANTS WHEN MAKING THE WIRE ENTRY HOLES AND MOUNTING THE ENCLOSURE TO PREV...

Page 8: ...m and use the appropriate figures FACTORY WIRING IS SHOWN SOLID FIELD WIRING IS SHOWN DASHED FIG 10 DIRECT VOLTAGE CONNECTION 3 WIRE UP TO 600 VOLTS ONLY FIG 11 DIRECT VOLTAGE CONNECTION 4 WIRE UP TO...

Page 9: ...Effective 1 98 I B CBE IQ01 Page 9 Figure 1 Catalog Numbers IQA6010ENC3R IQA6010ENC12 IQA6210ENC3R IQA6210ENC12 With seperate source With or without graphics...

Page 10: ...Effective 1 98 Page 10 I B CBE IQ01 Figure 2 Catalog Numbers IQA6030ENC3R IQA6030ENC12 IQA6230ENC3R IQA6230ENC12 With line power With or without graphics...

Page 11: ...Effective 1 98 I B CBE IQ01 Page 11 Figure 3 Catalog Numbers IQDP4010ENC3R IQDP4010ENC12 With seperate source Without I O...

Page 12: ...Effective 1 98 Page 12 I B CBE IQ01 Figure 4 Catalog Numbers IQDP4010ENC3R IQDP4010ENC12 With line power Without I O...

Page 13: ...Effective 1 98 I B CBE IQ01 Page 13 Figure 5 Catalog Numbers IQDP4010ENC3R IQDP4010ENC12 With seperate source With I O...

Page 14: ...Effective 1 98 Page 14 I B CBE IQ01 Figure 6 Catalog Numbers IQDP4010ENC3R IQDP4010ENC12 With line power With I O...

Page 15: ...Effective 1 98 I B CBE IQ01 Page 15 Figure 7 Catalog Numbers P PONI option...

Page 16: ...Effective 1 98 Page 16 I B CBE IQ01 Figure 8 Catalog Numbers U UPS option...

Page 17: ...Effective 1 98 I B CBE IQ01 Page 17 Figure 9 Catalog Numbers A ARII option...

Page 18: ...Effective 1 98 Page 18 I B CBE IQ01 Figure 11 Direct Voltage Connection 4 wire up to 600 volts only Figure 10 Direct Voltage Connection 3 wire up to 600 volts only...

Page 19: ...Effective 1 98 I B CBE IQ01 Page 19 Figure 13 External voltage connection WYE Figure 12 External voltage connection open delta 1 2 3...

Page 20: ...Effective 1 98 Page 20 I B CBE IQ01 Figure 15 Analyzer current circuit 3 CTs Figure 14 Analyzer current circuit 2 CTs LINE...

Page 21: ...Effective 1 98 I B CBE IQ01 Page 21 Figure 17 Analyzer current circuit 4 CTs residual ground monitoring Figure 16 Analyzer current circuit 3 CTs residual ground monitoring LINE...

Page 22: ...Effective 1 98 Page 22 I B CBE IQ01 Figure 19 DP 4000 current circuit 2 CTs Figure 18 Analyzer current circuit 5 CTs...

Page 23: ...Effective 1 98 I B CBE IQ01 Page 23 Figure 21 Control power connections note voltage on diagrams Figure 20 DP 4000 current circuit 3 CTs LINE...

Page 24: ...Effective 1 98 Page 24 I B CBE IQ01 Figure 23 DP 4000 I O Figure 22 Analyzer I O...

Page 25: ...Effective 1 98 I B CBE IQ01 Page 25 Figure 25 ARII Relay Option Figure 24 IPONI module option...

Page 26: ...ed SERVICE DISCONNECT Enclosed IQ units supplied with Separate Power Source Modules on the IQ devices are also equipped with a two position ON OFF switch to enable switching control power on and off t...

Page 27: ...ABLE POWER SUPPLY AND THE ARII ADDRESSABLE RELAY WHEN YOUR UNIT IS EQUIPPED WITH THESE DEVICES In general the Enclosed IQ unit is designed to be relatively maintenance free under normal usage However...

Page 28: ...nt is the contract between the purchaser and Cutler Hammer NO WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OR FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OR WARRANTIES ARISING FROM COU...

Reviews: