Effective 1/98

Page 8

I.B. CBE-IQ01

264 VAC OR  100-350 VDC. THE ADDITION OF AN
ARII RELAY LIMITS CONTROL POWER TO A RANGE
OF 96-144VAC OR 100-125VDC. AN ENCLOSURE
EQUIPPED WITH THE UNINTERRUPTABLE POWER
SUPPLY OPTION IS SUITABLE FOR USE WITH
120VAC ONLY.  SEE FIGURE 21.

Figures 1 through 9 show factory wiring and relative
device location for all catalog numbers and options.

UNDERSTAND THE DIAGRAM(S) THAT PERTAIN TO
YOUR ORDER BEFORE YOU BEGIN THE FIELD
WIRING.

REFER TO INSTRUCTION BOOKLET TD17530 OR
TD17548 FOR MORE INFORMATION REGARDING
THE IQ ANALYZER OR THE IQ DP-4000,
RESPECTIVELY.

4.5  FIELD WIRING

NOTE: ALL FIELD WIRING MUST

BE #14 AWG MINIMUM.

Figures 10 through 25 show the field wiring options
available. Not all these diagrams will pertain to your
order. Understand your system and use the appropriate
figures.

FACTORY WIRING IS SHOWN SOLID, FIELD WIRING
IS SHOWN DASHED.

FIG 10 - DIRECT VOLTAGE CONNECTION,

3-WIRE – UP TO 600 VOLTS ONLY

FIG 11 -  DIRECT VOLTAGE CONNECTION,

4-WIRE – UP TO 600 VOLTS ONLY

FIG 12 - EXTERNAL VOLTAGE CONNECTION, OPEN

DELTA

FIG 13 - EXTERNAL VOLTAGE CONNECTION, WYE

FIG 14 - ANALYZER CURRENT CIRCUIT – 2-CTs

FIG 15 - ANALYZER CURRENT CIRCUIT – 3-CTs

FIG 16 - ANALYZER CURRENT CIRCUIT – 3-CTs

– RESIDUAL GROUND MONITORING

FIG 17 - ANALYZER CURRENT CIRCUIT – 4-CTs

– RESIDUAL GROUND MONITORING

FIG 18 - ANALYZER CURRENT CIRCUIT – 5-CTs

FIG 19 - DP-4000 CURRENT CIRCUIT – 2-CTs

FIG 20 - DP-4000 CURRENT CIRCUIT – 3-CTs

FIG 21 - CONTROL POWER CONNECTIONS

– NOTE VOLTAGE ON DIAGRAMS

FIG 22 - ANALYZER I/O

FIG 23 - DP-4000 I/O

FIG 24 - IPONI MODULE OPTION

FIG 25 - ARII RELAY OPTION

NOTE: WHEN UNIT IS EQUIPPED WITH OPTIONAL

UNINTERRUPTABLE POWER SUPPLY, NO
ADDITIONAL FIELD WIRING IS NEEDED. THE
UPS MOUNTS TO A BRACKET IN THE FLOOR
OF THE ENCLOSURE AND CONNECTION IS
MADE VIA TWO 3-PRONG PLUGS.

Summary of Contents for Cutler-Hammer Enclosed IQ

Page 1: ...I B CBE IQ01 Instruction Leaflet for Cutler Hammer Enclosed IQ...

Page 2: ...NAL INJURY FOLLOW PROPER INSTALLATION OPERATION AND MAINTENANCE PROCEDURES TO AVOID THESE VOLTAGES ALL POSSIBLE CONTINGENCIES WHICH MAY ARISE DURING INSTALLATION OPERATION OR MAINTENANCE AND ALL DETAI...

Page 3: ...2 1 CATALOG NUMBER IDENTIFICATION Page 5 2 2 CATALOG NUMBER EXAMPLE Page 5 SECTION 3 RECEIVING HANDLING AND STORAGE 3 1 RECEIVING AND HANDLING Page 6 3 2 STORAGE Page 6 SECTION 4 INSTALLATION AND WIRI...

Page 4: ...ut not limited to damage or loss of use of equipment plant or power system cost of capital loss of power additional expenses in the use of existing power facilities or claims against the purchaser or...

Page 5: ...IQ ANALYZER WITH SEPARATE SOURCE POWER MODULE AND GRAPHICS DISPLAY IQA6230 IQ ANALYZER WITH SELF POWERED POWER MODULE AND GRAPHICS DISPLAY IQDP4010 IQ DP 4000 WITH SEPARATE SOURCE POWER MODULE IQDP40...

Page 6: ...ugh handling and or external damage that occurred during transportation Record any external and internal damage for reporting to the transportation carrier and Cutler Hammer once a thorough inspection...

Page 7: ...and two at the bottom CAUTION EXTREME CARE SHOULD BE TAKEN TO PROTECT THE EQUIPMENT FROM DRILL CHIPS FILINGS AND OTHER CONTAMINANTS WHEN MAKING THE WIRE ENTRY HOLES AND MOUNTING THE ENCLOSURE TO PREV...

Page 8: ...m and use the appropriate figures FACTORY WIRING IS SHOWN SOLID FIELD WIRING IS SHOWN DASHED FIG 10 DIRECT VOLTAGE CONNECTION 3 WIRE UP TO 600 VOLTS ONLY FIG 11 DIRECT VOLTAGE CONNECTION 4 WIRE UP TO...

Page 9: ...Effective 1 98 I B CBE IQ01 Page 9 Figure 1 Catalog Numbers IQA6010ENC3R IQA6010ENC12 IQA6210ENC3R IQA6210ENC12 With seperate source With or without graphics...

Page 10: ...Effective 1 98 Page 10 I B CBE IQ01 Figure 2 Catalog Numbers IQA6030ENC3R IQA6030ENC12 IQA6230ENC3R IQA6230ENC12 With line power With or without graphics...

Page 11: ...Effective 1 98 I B CBE IQ01 Page 11 Figure 3 Catalog Numbers IQDP4010ENC3R IQDP4010ENC12 With seperate source Without I O...

Page 12: ...Effective 1 98 Page 12 I B CBE IQ01 Figure 4 Catalog Numbers IQDP4010ENC3R IQDP4010ENC12 With line power Without I O...

Page 13: ...Effective 1 98 I B CBE IQ01 Page 13 Figure 5 Catalog Numbers IQDP4010ENC3R IQDP4010ENC12 With seperate source With I O...

Page 14: ...Effective 1 98 Page 14 I B CBE IQ01 Figure 6 Catalog Numbers IQDP4010ENC3R IQDP4010ENC12 With line power With I O...

Page 15: ...Effective 1 98 I B CBE IQ01 Page 15 Figure 7 Catalog Numbers P PONI option...

Page 16: ...Effective 1 98 Page 16 I B CBE IQ01 Figure 8 Catalog Numbers U UPS option...

Page 17: ...Effective 1 98 I B CBE IQ01 Page 17 Figure 9 Catalog Numbers A ARII option...

Page 18: ...Effective 1 98 Page 18 I B CBE IQ01 Figure 11 Direct Voltage Connection 4 wire up to 600 volts only Figure 10 Direct Voltage Connection 3 wire up to 600 volts only...

Page 19: ...Effective 1 98 I B CBE IQ01 Page 19 Figure 13 External voltage connection WYE Figure 12 External voltage connection open delta 1 2 3...

Page 20: ...Effective 1 98 Page 20 I B CBE IQ01 Figure 15 Analyzer current circuit 3 CTs Figure 14 Analyzer current circuit 2 CTs LINE...

Page 21: ...Effective 1 98 I B CBE IQ01 Page 21 Figure 17 Analyzer current circuit 4 CTs residual ground monitoring Figure 16 Analyzer current circuit 3 CTs residual ground monitoring LINE...

Page 22: ...Effective 1 98 Page 22 I B CBE IQ01 Figure 19 DP 4000 current circuit 2 CTs Figure 18 Analyzer current circuit 5 CTs...

Page 23: ...Effective 1 98 I B CBE IQ01 Page 23 Figure 21 Control power connections note voltage on diagrams Figure 20 DP 4000 current circuit 3 CTs LINE...

Page 24: ...Effective 1 98 Page 24 I B CBE IQ01 Figure 23 DP 4000 I O Figure 22 Analyzer I O...

Page 25: ...Effective 1 98 I B CBE IQ01 Page 25 Figure 25 ARII Relay Option Figure 24 IPONI module option...

Page 26: ...ed SERVICE DISCONNECT Enclosed IQ units supplied with Separate Power Source Modules on the IQ devices are also equipped with a two position ON OFF switch to enable switching control power on and off t...

Page 27: ...ABLE POWER SUPPLY AND THE ARII ADDRESSABLE RELAY WHEN YOUR UNIT IS EQUIPPED WITH THESE DEVICES In general the Enclosed IQ unit is designed to be relatively maintenance free under normal usage However...

Page 28: ...nt is the contract between the purchaser and Cutler Hammer NO WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OR FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OR WARRANTIES ARISING FROM COU...

Reviews: