Effective 10/2004
Page 75
I.L. 70C1036H05
Appendix D - Display Menu Diagrams Continued
Factory
Settings
LONG SLOPE
LONG PU
LONG TIME
LONG MEMORY
SHORT SLOPE ***
SHORT PU
SHORT TIME
INST PU
GROUND PU**
GROUND SLOPE****
GROUND TIME****
EXT GND CT RATIO**
NEUTRAL PROTECT*
AMP UNBALANCE
AMP UNBALANCE (time)
PHASE LOSS
I2T
1.00
4.0 s
ON
FLAT
3.0
0.30 s
4.0
0.40
2
FLAT
0.30 s
none
100%
OFF
10 s
OFF
MOD INV
1.00
2.0
3.0
0.30 s
4.0
0.40
2
FLAT
0.30 s
none
100%
OFF
10 s
OFF
PHASE SLOPE
Pickup
PHASE TimeDial
SHORT PU
SHORT TIME
INST PU
EARTH PU**
EARTH SLOPE****
EARTH TIME****
EXT EARTH CT RATIO**
NEUTRAL PROTECT*
AMP UNBALANCE
AMP UNBALANCE (time)
PHASE LOSS
IEC - A
1.00
0.20
3.0
0.30 s
4.0
0.40
FLAT
0.30 s
none
100%
OFF
10 s
OFF
LSIG ON
LSIG Current Curve
IEEE Curve
IEC Curve
DISPLAY
(6 active)
IA IB IC
AUTO
IN IG
ON
L-L VOLTAGE
ON
FwdPower
ON
PF Hz
ON
ENERGY FWD & REV
ON
(all others)
OFF
AuxReLaYs
All relays DISABLED
ALARMS
All alarms OFF
1
ACC BUS
Address1 Relay1 is Aux.-Aux Switch
All other addresses and relays OFF
SYSTEM
FIXED DEMAND 15 Min window
WAVEFORM CAPTURE OFF
FREQ 60Hz
Relay B,C MANUAL
INCOM
INCOM ADDRESS
100 hex
INCOM BAUD RATE 9600
EXT COMM OpenTrip
ENABLED
EXT COMM
TRIP
EXT COMM CLOSE
ENABLED
DT 910 COMM
DISABLED
1. Except LSIA will have Ground Alarm on @ .40x
2. Plug ratings 3200, 4000, 5000, 6300 A are set to .24
CURRENT Protection
VOLTAGE Protection
DISABLED *****
TEST
PH TEST
0.4x In
GND TEST
0.1x In
PHASE SLOPE
Pickup
PHASE TimeDial
SHORT PU
SHORT TIME
INST PU
GROUND PU**
GROUND SLOPE****
GROUND TIME****
EXT GND CT RATIO**
NEUTRAL PROTECT*
AMP UNBALANCE
AMP UNBALANCE (time)
PHASE LOSS
* Applicable on LSI or IEC factory styles only
** Applicable on LSIG, LSIA and IEC-EF
*** Only available on LSIG, LSI, LSIA Current Curve. On IEEE curve and IEC
curve, LONG MEMORY and SHORT I
2
T SLOPE settings are not available.
**** Applicable on LSIG, IEC-EF
***** VOLTAGE PROT and FREQ settings available on Cat #11PXXX
only.
Appendix D - Page D-25