Effective 10/2004
Page 62
I.L. 70C1036H05
Appendix D - Display Menu Diagrams Continued
INST PU
. xIn
XXXXX A
GROUND
SLOPE
GND PU
.
XXXX A
GROUND
TIME
. s
EXT GND
CT RATIO
NEUTRAL
PROTECT
AMP UN-
BALANCE
%
AMP UN-
BALANCE
s
PHASE
LOSS
2.0 - M1
OFF
(steps of 0.5)
0.10 - 1.00 and OFF (IEC style only)
0.24 - 1.00 (IEEE) with 1200A Max
0.10 -1.00 for LSIA style unit
(steps of 0.01)
0.10 - 0.50
(steps of 0.05)
FLAT
I
2
T
none
1000/1
800/1
400/1
200/1
100/1
50/1
25/1
10/1
50%
100%
5% - 25%
OFF
(steps of 1%)
0 - 240 s
(steps of 1 s)
1 - 30 s
OFF
(steps of 1 s)
Screen is skipped if LSIG
factory style. Also requires
4 pole circuit breaker or
separately wired Neutral
Sensor.
Program
CURRENT
Curve
LSI-G
Screens are
skipped if
LSI style
Save
(Page D-19)
LONG
SLOPE
I T
0.40 - 1.00
(steps of 0.05)
LONG PU
.
Ir=XXXXA
I
2
T:
2.0 - 24.0
(steps of 0.5)
LongTIME
@ 6x Ir
. s
2
4
LONG
MEMORY
ON
OFF
SHORT
SLOPE
1.5 - 10x or
1.5 - 12x or
1.5 - 14x
(steps of 0.5)
(and additional
setting M1 xIn)
SHORT PU
. xIr
XXXXX A
0.10 - 0.50
(steps of 0.05)
SHORT
TIME
. s
FLAT
I
2
T
VIEW
Screen is skipped if
first AMP UN-
BALANCE is set to
"OFF"
I
4
T:
1.0 - 5.0
(steps of 0.5)
If LONG SLOPE =
none denotes default
to In value
= 10x or
= 12x or
= 14x
M1
If IEC -EF style
"EARTH" will replace
"GROUND"
*
(See Section 4.2.2)
Reflects
Ground
Alarm
setting if
LSIA style
Screens
are
skipped
if LSIA
style
Screen
skipped if
circuit
breaker
contacts B-6
is not
connected to
B-7
Appendix D - Page D-13