Figure 8.2 Automatic Trip Operation Record
DIGITRIP
AUTOMATIC TRIP OPERATION RECORD
Circuit No./Address
Circuit Breaker Shop Order Reference
Settings Reference
Trip Function
Factory Rev.
1
Rev. 2
Rev. 3
Curve Type
LSIG*
Slope
I2T
Ir = Long PU x ln
1.0
Long Time
4s
Long Memory
ON
Short Slope
FLAT
Short PU x Ir
3.0
Short Time
0.3s
Inst PU x In
4
Ground* Slope
FLAT
Ground* PU x In
0.4 or 0.24
Ground* Time
0.3s
* if supplied
Date
of Trip
Trip Mode Indicator
Setting Ref.
Setting
Change Made
Investiga