Appendix D - Display Menu Diagrams Continued
Program
Alarms
Notes:
Front Panel Display of NEUTral AMPere ALARM will be in amperes. Equation used is:
Amperes = In (amperes) x Neutral Alarm Pickup Setting ( 0.10 to 1.0 x In is range )
The Neutral Alarm (if not set to OFF) will also alarm if Neutral (Long Pickup value) is exceeded.
The Neutral alarm function is not possible on breakers used in a Source Ground or Zero Sequence
Ground Fault application.
Voltage, Frequency and Phase Rotation alarming requires Digitrip Cat # 11PXXX
.
Save
(Page D-19)
If IEC -EF style
"EARTH" will replace
"GROUND"
*
GROUND
ALARM
A
HighLOAD
ALARM
A
VIEW
range
(0.50 to 1.00 xIr)
OFF
(steps of 0.05)
OFF
0.10 to 1.00, 1200A Max
IEEE
OFF
(steps of 0.01)
1 to 12,500
OFF
(steps of 1)
1 to 12,500
OFF
(steps of 1)
1 to 12,500
OFF
(steps of 1)
1 to 60 s
0.50 to 0.95
OFF
(steps of 0.05)
10% to 30%
OFF
(steps of 1%)
ENABLED
DISABLED
See Note
below
Screen is skipped if
LSI or LSIA style
NEUT AMP
ALARM
A
HighLOAD
TIME
s
OP COUNT
ALARM
kVA
DEMAND
kW
DEMAND
THD
ALARM
%
ALARM TO
EventLOG
LOW PF
ALARM
.
VOLT UN-
BALANCE
s
UNdrVOLT
ALARM
V
UNdrVOLT
TIME
s
OverVOLT
ALARM
V
OverVOLT
TIME
s
UndrFREQ
ALARM
. Hz
UndrFREQ
TIME
. s
OverFREQ
ALARM
. Hz
OverFREQ
TIME
. s
ALARM ON
ROTATION
VOLT UN-
BALANCE
%
90 to 670V
OFF
(steps of 1V)
180 to 720V
OFF
(steps of 1V)
1 to 250s
(steps of 1s)
1 to 250s
(steps of 1s)
58 to 62 (60Hz) or
48 to 52 (50Hz)
0.2 to 5.00 s
(steps of 0.02)
58.0 to 62.0 (60Hz)
48.0 to 52.0 (50Hz)
0.2 to 5.00 s
(steps of 0.02)
ABC, CBA
OFF
5 to 50 %
(steps of 1%)
1 to 250
(steps of 1s)
Appendix D - Page D-16